background image

Activation outputs A1'...A8' 
Control voltage 

DC 24 V SELV 

Current carrying capacity 

10 mA 

Resistance Ra 

330 Ω 

Connection 
rated voltage/load outputs 
single stranded 

0.5 ... 4 mm² 

finely stranded with conductor sleeve 

0.14 ... 2.5 mm² 

finely stranded without conductor sleeve 

0.34 ... 4 mm² 

Activation outputs/switching outputs/control sections 
single stranded 

1.5 mm² 

finely stranded with conductor sleeve 

0.75 mm² 

finely stranded without conductor sleeve 

1.0 mm² 

Load outputs A1...A8 
Contact type 

µ contact, potential-free NO contact 

Rated voltage 

AC 230 / 240 V ~ 

Minimum switching voltage 

AC 12 V~ 

Switching current per device 

Σ 80 U 

Switching current, adjacent load outputs  

Σ 20 U 

Switching current per channel for AC 250 V~ 
Fluorescent lamps 

16 AX 

Capacitive 

max. 16 U (140 µF) 

Switch-on current 200 µs 

max. 800 U 

Switch-on current 20 ms 

max. 165 U 

Minimum switching current AC 

100 mA 

Connected load per channel for AC 230 V~ 
Ohmic load 

3000 W 

Incandescent lamps 

3000 W 

HV halogen lamps 

2500 W 

Tronic transformers 

1500 W 

Inductive transformers 

1200 VA 

Fluorescent lamps, uncompensated 

1000 VA 

Fluorescent lamps, parallel compensated  

1160 VA (140 µF) 

Fluorescent lamps, duo circuit  

2300 VA (140 µF) 

Mercury vapour lamps, uncompensated 

1000 W 

Mercury vapour lamps, parallel compensated  

1160 W (140 µF) 

Electronic ballast 

Type-dependent 

Blind, fan motors 

1380 VA 

Ambient temperature 

-5 ... +45 °C 

Storage/transport temperature 

-25 ... +70 °C 

Fitting width 

144 mm / 8 modules 

Switch-over time for direction change 

approx. 1 s 

Switch-on time, Venetian blind operation 

approx. 2 min 

6.2 Troubleshooting 

No control is possible via control sections. 

Local control is switched on. 

Switch off local control (see chapter 4. Operation). 

Programming mode is switched on. 

Switch off programming mode (see chapter 5.2. Commissioning). 

Load output A8 cannot be controlled. 

The central function on the relay station is switched on. 

Switch off central function (see chapter 5.2. Commissioning). 
Set the operating mode for the load output 

A8

(see chapter 5.2. Commissioning). 

No Venetian blind operation can be set for load outputs A7...A8 

Central function Central ON, Central OFF is active. 

Switch off central function (see chapter 5.2. Commissioning). 

12/13 

82556943 
J:0082556943 

01.10.2012 

Light Management  

Relay station universal, 8-gang 

Summary of Contents for RS 8 REG HE

Page 1: ...an output it is essential to observe the corresponding instructions of the manufacturers and to use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechan...

Page 2: ...tment Mixed operation with switching toggling and Venetian blind operation is possible Example Load outputs A1 A3 switch operation Load output A4 pushbutton operation Load outputs A5 A8 shutter blinds...

Page 3: ...al control is switched off The red status LEDs A1 A8 4 indicate the switching states of the load outputs LED 10 c is off Pushbutton outputs When local control is switched off the load outputs are swit...

Page 4: ...rical shock when live parts are touched Electrical shocks can be fatal Before working on the device disconnect the power supply and cover up live parts in the working environment Fitting the device Ob...

Page 5: ...ple for mains voltage and loads Connecting a control section Operation take place using the devices listed under Accessories In case of operation with sensor modules 17 or push button modules 17 do no...

Page 6: ...connected in the first two channels for the sake of clarity Supplement further channels correspondingly An 18 wire cable is needed for a full connection Figure 6 Connection example for sensor module...

Page 7: ...button sensor 24 V switches load output A1 of the right hand relay station and Kanal 2 switches load output A2 of the left hand relay station figure 8 Wiring example for central control For the exampl...

Page 8: ...st version V02 To do this the device address of a relay station must be changed see Setting the device address o Connect the sensor module or push button module to two relay stations according to the...

Page 9: ...vice and connected blind motors Before setting the mode of operation check what loads are connected o Press ON n button 11 OFF o 13 button or both buttons at the same time i If a load output A1 A8 is...

Page 10: ...ON n and OFF o buttons simultaneously for approx 3 seconds The green LED of output A1 flashes This means that the device address 1 is set o Press the ON n or OFF o button briefly The green LED of out...

Page 11: ...tons simultaneously until the c ON n and OFF o LED flash The relay station and sensor modules or pushbutton modules are in cloning operation o Within approx 2 minutes press a button on the module that...

Page 12: ...Fluorescent lamps uncompensated 1000 VA Fluorescent lamps parallel compensated 1160 VA 140 F Fluorescent lamps duo circuit 2300 VA 140 F Mercury vapour lamps uncompensated 1000 W Mercury vapour lamps...

Page 13: ...2 Commissioning Venetian blind motor is connected to the wrong load outputs Check installation see chapter 5 1 Fitting and electrical connection 6 3 Accessories Sensor module 8 gang Art No SM 1608 Pus...