To assign the central function for load output 

A1

, press the 

ON/

n

 button. 

The green LED of load output 

A1

 flashes. The central function has been assigned. 

To remove the central function for load output 

A1

, press the 

OFF/

o

 button. 

The red LED of load output 

A1

 flashes. The central function has been removed. 

Press 

MODE

 button briefly. 

The central function for the next load output can be assigned. 

In the case of Venetian blind outputs, the central function can be assigned individually for 
each direction of travel. Thus for example in the case of Central OFF the Venetian blind 
moves to the lower end position, but in the case of Central OFF the Venetian blind does 
not move. 

Exit programming mode 

Press the 

MODE

 button (15) as many times as necessary until LED 

c

 (10) goes out. 

The status LEDs (4) indicate the operating mode and the switching state of load outputs 

A1...A8

After 15 seconds without a button-press the programming mode is automatically 
terminated. 

Setting the device address 

If two relay stations are connected in parallel, the device address of a relay station has to be 
reprogrammed before the sensor modules or pushbutton modules are commissioned. In the 
state as supplied each relay station has the device address 1. 
Several sensor modules or pushbutton modules are connected. 

Press 

ON/

n

 and 

OFF/

o

 buttons simultaneously for approx. 3 seconds. 

The green LED of output 

A1

 flashes. This means that the device address 1 is set. 

Press the 

ON/

n

 or 

OFF/

o

 button briefly. 

The green LED of output 

A2

 flashes. Device address 2 has been set. 

Press the buttons 

ON/

n

 and 

OFF/

o

 again simultaneously for approx. 3 seconds or wait 

for 15 seconds. 
The relay station switches to normal operation. 
The relay station has the device address 2. 

Switching on central function Central ON, Central OFF 

Activation of the central function on the relay station when push-button sensors 24 V, 
pushbutton modules 24 V or unlit installation buttons are used. 

With the sensor module and pushbutton module the central function is set on the modules. 

Press 

Central Switching Mode

 button (3) for approx. 5 seconds until status LED (3) lights 

up red (figure 1). 
Activation output 

A8'

 is input for Central OFF. 

Switch input 

E8

 is input for central ON. 

Red and green status LEDs (4) for load output 

A8

 flash alternately. 

Load output 

A7

 is in push-button operation. 

When the central function is activated, load output 

A8

 has no function. 

Switching off central function Central ON, Central OFF 

Press 

Central Switching Mode

 button (3) for approx. 5 seconds until status LED (3) lights 

up green (figure 1). 
Red status LED (4) of load output 

A8

 is off, green status LED (4) indicates the operating 

mode. 
Load output 

A8

 is in the "Toggle" or "Switching" operating mode. 

10/13 

82556943 
J:0082556943 

01.10.2012 

Light Management  

Relay station universal, 8-gang 

Summary of Contents for RS 8 REG HE

Page 1: ...an output it is essential to observe the corresponding instructions of the manufacturers and to use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechan...

Page 2: ...tment Mixed operation with switching toggling and Venetian blind operation is possible Example Load outputs A1 A3 switch operation Load output A4 pushbutton operation Load outputs A5 A8 shutter blinds...

Page 3: ...al control is switched off The red status LEDs A1 A8 4 indicate the switching states of the load outputs LED 10 c is off Pushbutton outputs When local control is switched off the load outputs are swit...

Page 4: ...rical shock when live parts are touched Electrical shocks can be fatal Before working on the device disconnect the power supply and cover up live parts in the working environment Fitting the device Ob...

Page 5: ...ple for mains voltage and loads Connecting a control section Operation take place using the devices listed under Accessories In case of operation with sensor modules 17 or push button modules 17 do no...

Page 6: ...connected in the first two channels for the sake of clarity Supplement further channels correspondingly An 18 wire cable is needed for a full connection Figure 6 Connection example for sensor module...

Page 7: ...button sensor 24 V switches load output A1 of the right hand relay station and Kanal 2 switches load output A2 of the left hand relay station figure 8 Wiring example for central control For the exampl...

Page 8: ...st version V02 To do this the device address of a relay station must be changed see Setting the device address o Connect the sensor module or push button module to two relay stations according to the...

Page 9: ...vice and connected blind motors Before setting the mode of operation check what loads are connected o Press ON n button 11 OFF o 13 button or both buttons at the same time i If a load output A1 A8 is...

Page 10: ...ON n and OFF o buttons simultaneously for approx 3 seconds The green LED of output A1 flashes This means that the device address 1 is set o Press the ON n or OFF o button briefly The green LED of out...

Page 11: ...tons simultaneously until the c ON n and OFF o LED flash The relay station and sensor modules or pushbutton modules are in cloning operation o Within approx 2 minutes press a button on the module that...

Page 12: ...Fluorescent lamps uncompensated 1000 VA Fluorescent lamps parallel compensated 1160 VA 140 F Fluorescent lamps duo circuit 2300 VA 140 F Mercury vapour lamps uncompensated 1000 W Mercury vapour lamps...

Page 13: ...2 Commissioning Venetian blind motor is connected to the wrong load outputs Check installation see chapter 5 1 Fitting and electrical connection 6 3 Accessories Sensor module 8 gang Art No SM 1608 Pus...

Reviews: