background image

Mark the installation location using the enclosed template. Install the concealed appliance 
box, anchor holes for screw fastening Ø = 6 mm. 

Slacken the fastening screws (4) with the enclosed tool – two-hole spanner bit SP-4 – and 
remove the front plate (6). 

Slacken the lid screws (10) on the connection box (8) and remove the lid (9). 

Run the connecting cables through the openings (11) of the connection box. 

Connect the bus wires with the red and black bus terminal to the bus connection (13).  

Connect the power supply with the yellow and white terminal to the connection (12). 

The second wire pair of the bus cable can be used to provide the power supply. 

Close the lid (9). 

The physical address must be noted on the device. If possible load the physical address 
into the device before final mounting (see chapter 5.2. Commissioning). 

Place the device in the concealed box and screw it to the substrate. Use the enclosed 
screw/anchor set (7). 

Push the written push-in labels into the top of the intended slots on the rear side of the front 
plate.  

Attach the front plate. Insert the screw sleeves (5) and fasten them to the housing using the 
fastening screws (4). Max. torque: 0.5 Nm. 

5.2 Commissioning 

Loading the physical address and application software 

The device is connected and ready for operation. 
The power supply and bus voltage are switched on. 

Press the top left and right sensor areas simultaneously. 
The programming LED on the right edge of the panel (3) lights up. 

Assign physical address. 
The programming LED goes out. 

Load the application software into the device. 

Note the physical address on the labels on the rear side of the device and behind the front 
plate. 

Checking the LED function 

The device is connected and ready for operation. 

Press the top left and bottom right sensor areas simultaneously.  
All the LEDS light up in sequence for 2 seconds each in red, green and blue. 

6 Appendix 

6.1 Technical data 

External supply 
Rated voltage 

AC/DC 24 V SELV 

Rated frequency 

50 / 60 Hz 

Power consumption 

max. 2.2 W 

Connection of power supply 

Connection terminal 

Single stranded 

0.6 ... 0.8 mm² 

Front plate 
Dimensions W×H×D 

approx. 236x156x14 mm 

Installation depth 

approx. 39 mm 

Push-in labels 
Dimensions L×W 

approx. 132×39.5 mm 

Ambient conditions 
Ambient temperature 

-20 ... +70 °C 

Storage/transport temperature 

-20 ... +75 °C 

5/7 

82575503 
J:0082575503 

07.12.2010 

Signal panel 