5.1 Technical data

Supply
Rated voltage

AC/DC 24 V SELV

(± 10%)

Current consumption

100 ... 400 mA

(dependent on the weather)

Protection class

III

Connecting cable
Cable type

LiYCY 4xAWG26

Cable length

16.4 ft (5 m)

Total length per line

49.2 ft (15 m)

Number of weather stations

max. 3 (per line)

KNX
KNX medium

TP

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 30 V SELV

Current consumption KNX

max. 5 mA

Ambient conditions
Housing
Dimensions Ø×H

5.12x2.68 in

(130x68 mm)

Weight

ca. 8.11 oz (230 g)

Wind direction sensor
Measuring range

1 ... 360°

Resolution

Accuracy

± 10 °

Wind speed sensor
Resolution

0.3 ft/s (0.1 m/s)

Accuracy (≤ 10 m/s)

± 3.3 ft/s (± 1 m/s)

Accuracy (>10 m/s)

± 5 %

i

Accuracy as RMS average value over 360°.

Temperature sensor
Measuring range

-22 ... +140 °F

(-30 ... +60 °C)

Resolution

0.1 K

Accuracy

± 1 K (Wind > 6.56 ft/s 

(2 m/s), for 23 ... 77 °F 

(-5 ... +25 °C))

Precipitation sensor
Measuring range

yes/no

Accuracy

Fine drizzle

Brightness sensors
Number

4

Measuring range

approx. 0 ... 13.9 kfc 

(0 ... 150 klx)

Resolution

93 fc (1 klx)

Accuracy

± 3 %

Spectral range

475 ... 650 nm

Twilight sensor
Measuring range

approx. 0 ... 83 fc (0 ... 900 lx)

Resolution

0.1 fc (1 lx)

Accuracy

± 1 fc (± 10 lx)

Air pressure sensor

9/10

Universal weather station

82590115
J0082590115

07.11.2017

Summary of Contents for KNX 2225WSU-01

Page 1: ...Universal weather station Art No 2225WSU 01 Operating instructions 1 Safety instructions 2 Device components Figure 1 View Universal weather station 1 10 82590115 J0082590115 07 11 2017...

Page 2: ...iled information on loadable soft ware and attainable functionality as well as the software itself can be obtained from the manufacturer s product database Planning installation and commissioning of t...

Page 3: ...rmation for electrically skilled persons 4 1 Mounting and electrical connection Select mounting location Figure 3 Minimum distance to surfaces 3 10 Universal weather station 82590115 J0082590115 07 11...

Page 4: ...next to building sections from which water can drip onto the device Select the mounting location so that the weather station will be accessible In the case of flat roofs locate the weather station as...

Page 5: ...ection 7 i If mounted on a mast without the guide blade correct wind direction measurement will not be possible due to the resulting turbulences o Run the connection cable through the mast o Attach th...

Page 6: ...arm to the wall through the boreholes using three suit able screws o Route the connecting cable along the underside of the fastening arm and guide the 7 pin plug through the open pipe socket at the en...

Page 7: ...h are approved for KNX o Connect the bus line and external power supply to the connecting cable red KNX Black KNX orange AC DC 24 V brown AC DC 24 V i The sensor head is translucent Therefore do not s...

Page 8: ...10 Position of the programming LED and reed contact o Switch on the bus voltage o Switch on supply voltage o Hold the supplied programming magnet by the integrated reed contact 12 The programming LED...

Page 9: ...in 130x68 mm Weight ca 8 11 oz 230 g Wind direction sensor Measuring range 1 360 Resolution 1 Accuracy 10 Wind speed sensor Resolution 0 3 ft s 0 1 m s Accuracy 10 m s 3 3 ft s 1 m s Accuracy 10 m s 5...

Page 10: ...control Sensing Control Construction of control Independently Mounted Control for Surface Mounting Pollution Degree PD 2 Impulse Voltage 330 V i All accuracy specifications relate to the respective m...

Reviews: