3 Function 

System information 

This device is a product of the KNX system and complies with the KNX directives. Detailed 
technical knowledge obtained in KNX training courses is a prerequisite to proper 
understanding.  
The function of this device depends upon the software. Detailed information on loadable 
software and attainable functionality as well as the software itself can be obtained from the 
manufacturer´s product database. Planning, installation and commissioning of the device are 
carried out with the aid of KNX-certified software. The latest versions of product database and 
the technical descriptions are available on our website. 

Intended use 

Switching of electrical loads for AC 230 V mains voltage. 

Installation in appliance box to DIN 49073 

Connection with enclosed terminals 

Product characteristics 

Two binary inputs for potential-free contacts, usable as extension inputs for local operation 

Operation as NO or NC contacts 

Feedback function for each output 

An additional function for each output: logical, forced-position or time function 

Time functions: switch-on delay, switch-off delay, staircase lighting timer 

Supply via bus, no additional power supply necessary 

Switch actuator 2gang: When activated by a central telegram the relay outputs of the 
actuator switch with a slight time delay. 

4 Information for electrically skilled persons 

4.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before working on the device, disconnect the power supply and cover up live 
parts in the working environment. 

Connecting and mounting the device 

DANGER! 
When connecting the bus/extensions and mains voltage wires in a shared 
appliance box, the KNX bus line may come into contact with the mains voltage. 
This endangers the safety of the entire KNX installation. People at remote 
devices may also receive an electric shock. 
Do not place bus/extensions and mains voltage terminals in a shared 
connection compartment. Use an appliance box with a fixed partition wall 
(figure 4) or separate boxes. 

3/6 

82553923 
J:0082553923 

18.09.2012 

Switch actuators flush mounted – 1gang 16A, 2gang 6A 

Summary of Contents for KNX 2131.16 UP

Page 1: ...e and other hazards Danger of electric shock on the KNX installation Do not connect any external voltage to the inputs Doing so may damage the device s and the SELV potential on the KNX bus line will no longer be available Danger of electric shock Before working on the device or before exchanging light bulbs disconnect mains voltage and switch off circuit breakers These instructions are an integra...

Page 2: ...r 1gang BN brown connection external conductor L output L Switch actuator 2gang BK black connection external conductor L PK pink connection output L 1 GY grey connection output L 2 Figure 3 Connection assignment of control cable RD red KNX BK black KNX GN green input 1 YE yellow input 2 WH white COM input 1 BN brown COM input 2 2 6 82553923 J 0082553923 18 09 2012 Switch actuators flush mounted 1g...

Page 3: ...An additional function for each output logical forced position or time function Time functions switch on delay switch off delay staircase lighting timer Supply via bus no additional power supply necessary i Switch actuator 2gang When activated by a central telegram the relay outputs of the actuator switch with a slight time delay 4 Information for electrically skilled persons 4 1 Fitting and elect...

Page 4: ...wer dissipation o Connect the load Use the supplied sprung screwless terminals Flexible cable ends must be tin plated o Connect the device to KNX o If necessary connect potential free contacts to the inputs figure 3 o Install the device in the appliance box Function of Inputs 1 and 2 in the as delivered state Input contact Switch actuator 1gang Switch actuator 2gang 1 close Toggle Switch over outp...

Page 5: ...Inductive transformers 1000 VA Tronic transformers 1000 W Control cable and inputs Control cable preterminated YY6x0 6 Input type Potential free Total length of extension unit cable max 5 m Poll voltage extension inputs approx 19 V Dimensions Ø H 53 28 mm Ø Centre hole 7 5 mm Connection of outputs Connection mode Screwless terminal enclosed KNX KNX medium TP 1 Commissioning mode S mode Rated volta...

Page 6: ... V SELV Connection type for bus Connection terminal Power consumption KNX typical 150 mW 5 2 Warranty We reserve the right to make technical and formal changes to the product in the interest of technical progress We provide a warranty as provided for by law Please send the unit postage free with a description of the defect to our central customer service office ALBRECHT JUNG GMBH CO KG Volmestraße...