DANGER! 
Danger of electrical shock!  
When mounting with 230 V socket outlets under a common cover there is a 
danger of electrical shocks in the event of a fault! 
Use only the enclosed plastic screws for fastening to the supporting frame.  

Mount supporting frame (1) in the correct orientation on an appliance box. Note marking 

TOP

; marking 

A

 or 

B

 in front. Use only the enclosed box screws. 

Push frame (2) onto supporting frame. 

Connect push-button module (4) to the KNX using KNX connecting terminal (7) and push 
onto the supporting frame.  

Fix pushbutton module to supporting frame using the enclosed plastic screws (5). Tighten 
the plastic screws only lightly. 

Before mounting the buttons (6), load the physical address into the device (see chapter 
4.2. Commissioning). 

4.2 Commissioning 

Loading the physical address and application software 

Configuration and commissioning with ETS3.0d Patch A or more recent. 
The device is connected and ready for operation.  
The buttons are not mounted yet.  

If the device does not receive any application software, or the wrong application software, 
then the blue operation LED flashes slowly.  

picture 2: Activating programming mode 

Activate programming mode: Press and hold push-button at the upper left (9). Then press 
push-button at the lower right (10, 11 or 12): 

Push-button module 

Prog. push-button 

– 4gang, 3gang 

(9) + (10) 

– 2gang 

(9) + (11) 

– 1gang 

(9) + (12) 

The operation LED (13) flashes quickly. 

Load physical address into the device. 

3/5 

32566613 
J:0082566613 

24.11.2009 

Standard push-button module with integrated BCU 

Summary of Contents for 4071 TSM

Page 1: ...ainable functionality as well as the software itself can be obtained from the manufacturer s product database Planning installation and commissioning of the device are carried out with the aid of KNX certified software The latest versions of product database and the technical descriptions are available on our website Intended use Operation of loads e g light on off dimming blinds up down brightnes...

Page 2: ...t Snapping on the adapter frame o With the adapter frame 3 in the correct orientation snap it from the front onto the pushbutton module 4 picture 1 Note marking TOP Fitting and connecting the device picture 1 Mounting the push button module 1 Supporting frame 2 Design frame 3 Adapter frame 4 Push button module 5 Fastening screws 6 Buttons 7 KNX connection terminal 8 Box screws Supporting frame sid...

Page 3: ...e mounting the buttons 6 load the physical address into the device see chapter 4 2 Commissioning 4 2 Commissioning Loading the physical address and application software Configuration and commissioning with ETS3 0d Patch A or more recent The device is connected and ready for operation The buttons are not mounted yet i If the device does not receive any application software or the wrong application ...

Page 4: ...ent 5 Appendix 5 1 Technical data KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 V 32 V SELV KNX power consumption typical 150 mW Connection mode KNX Connection terminal Safety class III Ambient temperature 5 45 C Storage transport temperature 25 70 C 5 2 Accessories Cover kit 1 gang complete Art No 401 TSA Cover kit 2 gang complete Art No 402 TSA Cover kit 3 gang complete Art N...

Page 5: ...5 80 61 89 mail vka jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail vkm jung de The Œ symbol is a free trade symbol which is solely intended for the authorities and does not guarantee any properties ALBRECHT JUNG GMBH CO KG Volmestraße 1 D 58579 Schalksmühle Telef...