6 Annex
78
6.1.2
Digital inputs
6.1.3
Analog outputs
Number
Max. 18 (see connection diagram)
Input
Level
Logic level 0:
<
3.5 V; logic level 1:
>
10 V
Sampling rate
125 ms (max. counting frequency: 4 Hz)
Potential-free contact
R
ON
:
<
1 k
Ω
; R
OFF
:
>
50 k
Ω
(use of auxiliary voltage 24 V)
High-speed input
Usable inputs
1, 2, 7, 8, 13, 14 (only for analog(HI)/digital option, see connection diagram)
Function
Counts each positive edge of the input signal
Max. counting frequency
12.5 kHz
Mark-to-space ratio
30 to 70 % (high-pulse
≥
30
μ
s, low-pulse
≥
30
μ
s)
Accuracy for
flow measurement
0.5 % of measured value; ambient temperature influence: 50 ppm/K
Auxiliary voltage supply
Voltage
DC 24 V +10/-15 %
Current
Max. 50 mA per slot (for analog (HI)/digital option: incl. digital output currents)
Number
Max. 3 (see connection diagram)
Voltage
Output signal
DC 0 to 10 V
Load resistance
>
500
Ω
Current
Output signal
DC 0(4) to 20 mA
Load resistance
<
450
Ω
Accuracy
0.5 %
Ambient temperature influence
150 ppm/K