![JUMO LOGOSCREEN 700 Brief Instructions Download Page 75](http://html1.mh-extra.com/html/jumo/logoscreen-700/logoscreen-700_brief-instructions_2031187075.webp)
75
6 Annex
6
Annex
6.1
Technical data
6.1.1
Analog inputs
General
Thermocouples
Number
Max. 18 (see connection diagram)
A/D converter
24 bit delta-sigma
Sampling rate
Up to 18 channels: 125 ms
Input filter
Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s
Galvanic isolation
See "Galvanic isolation"
Designation
Type
Standard
ITS
Measuring range
Accuracy
a
Fe-CuNi
"L"
DIN 43710:1985-12
ITPS-68
-200 to +900 °C
≤
0.1 %
Fe-CuNi
"J"
DIN EN 60584-1:2014
ITS-90
-210 to +1200 °C
≤
0.1 % from -100 °C
Cu-CuNi
"U"
DIN 43710:1985-12
ITPS-68
-200 to +600 °C
≤
0.1 % from -100 °C
Cu-CuNi DIN
"T"
DIN EN 60584-1:2014
ITS-90
-270 to +400 °C
≤
0.1 % from -150 °C
NiCr-Ni DIN
"K"
DIN EN 60584-1:2014
ITS-90
-270 to +1372 °C
≤
0.1 % from -80 °C
NiCr-CuNi
"E"
DIN EN 60584-1:2014
ITS-90
-270 to +1000 °C
≤
0.1 % from -80 °C
NiCrSi-NiSi
"N"
DIN EN 60584-1:2014
ITS-90
-270 to +1300 °C
≤
0.1 % from -80 °C
Pt10Rh-Pt
"S"
DIN EN 60584-1:2014
ITS-90
-50 to +1768 °C
≤
0.1 % from 100 °C
Pt13Rh-Pt
"R"
DIN EN 60584-1:2014
ITS-90
-50 to +1768 °C
≤
0.1 % from 100 °C
Pt30Rh-Pt6Rh
"B"
DIN EN 60584-1:2014
ITS-90
0 to 1820 °C
≤
0.1 % from 600 °C
W5Re/W26Re
"C"
ASTM E230M-11
ITS-90
0 to 2315 °C
≤
0.1 % from 500 °C
W3Re/W25Re
"D"
ASTM E1751M-09
ITS-90
0 to 2315 °C
≤
0.1 % from 500 °C
W5Re/W20Re
"A1"
GOST R 8.585-2001
ITS-90
0 to 2500 °C
≤
0.1 % from 500 °C
Chromel-Copel
"L"
GOST R 8.585-2001
ITS-90
-200 to +800 °C
≤
0.1 % from -80°C
Chromel-Alumel
GOST R 8.585-2001
ITS-90
-270 to +1372 °C
≤
0.1 % from -80 °C
PLII (Platinel II)
0 to 1395 °C
≤
0.1 %
Ambient temperature influ-
ence
≤
100 ppm/K
Smallest measuring span
Type L (Fe-CuNi), J, U, T, K, E, N, Chromel-Alumel, PLII: 100 K
Type S, R, B, C, D, A1, Chromel-Copel: 500 K
Measuring range start/end Freely programmable within the limits, in increments of 0.1 K
Cold junction
Internal (Pt100) or external (constant)
Cold junction accuracy (in-
ternal)
Option with 3 analog inputs (order codes 1 and 2):
±
1 K
Option with 6 analog inputs (order code 3):
±
2 K
Cold junction temperature
(external)
-30 to +85 °C (adjustable)
Base measuring range
20 to 70 mV
a
Accuracy refers to the maximum measuring range. Small measuring spans lead to reduced linearization accuracy.