7 Appendi
x
46
7.4
Technical data
Inputs
These values include the linearisation tolerances.
Transducer
Control range
Measurement accuracy/
Ambient
temperature error
Measurement circuit
monitoring
1
Sensor break Short-circuit
Process value input
Pt 100
2
-200 +850°C
≤
0.1% /
≤
25ppm /°C
X
X
Pt 1000
2
-200 +850°C
≤
0.1% /
≤
25ppm/°C
X
X
Fe-Con L
3
-200
+900°C
≤
0.25% /
≤
100ppm/°C
X
–
Fe-Con J
3
-200 +1200°C
≤
0.25% /
≤
100ppm/°C
X
–
NiCr-Ni K
3
-200 +1372°C
≤
0.25% /
≤
100ppm/°C
X
–
Cu-Con U
3
-200
+600°C
≤
0.25% /
≤
100ppm/°C
X
–
NiCrSi-NiSi N
3
-100 +1300°C
≤
0.25% /
≤
100ppm/°C
X
–
Pt10Rh-Pt S
3
0 — 1768°C
≤
0.25% /
≤
100ppm/°C
X
–
Pt13Rh-Pt R
3
0 — 1768°C
≤
0.25% /
≤
100ppm/°C
X
–
Pt30Rh-Pt6Rh B
3
0 — 1820°C
≤
0.25% /
≤
100ppm/°C
4
X
–
0 — 20mA
5
scalable
≤
0.1% /
≤
100ppm/°C
–
–
4 — 20mA
5
scalable
≤
0.1% /
≤
100ppm/°C
X
X