6.2
External setpoint input
Via this input (option) a setpoint can be provided using a standard signal.
1.
On displays with one or two decimal places the value range and the factory setting
change accordingly (e. g. 1 decimal place
→
value range: -199.9 to +999.9).
C111 Transducer
X
X X
no function
0
Standard signal 0 — 20mA
1
Standard signal 4 — 20mA
2
Standard signal 0 — 10V
3
Standard signal 2 — 10V
4
k
= factory setting
X=position functionally not relevant
Parameter Value range
factory-set Notes
SPL
-1999 to +9999 digit
1
-200
Display start/end with external setpoint input.
Low/high setpoint limit for SP1 and SP2.
Example: 4 — 20mA
→
0 — 250°C:
SPL = 0, SPH = 250
Setpoint limits
Setpoint inputs below or above these limits are not
accepted.
The value of SPL / SPH flashes on the display.
SPH
-1999 to +9999 digit
1
850