6 Conf
ig
ur
at
io
n
17
1.
On a display with one or two decimal places the value range and the factory setting
change accordingly (e. g. 1 decimal place
→
value range: -199.9 to +999.9).
Parameter Value range
factory-set Notes
SCL
-1999 to +9999 digit
1
0
Start/end of value range for standard signals
Example: 0—20 mA
→
20—200°C:
SCL = 20 /SCH = 200
SCL and SCH are simultaneously the calibration
for the process value output
v
Section 6.6
SCH
-1999 to +9999 digit
1
100
OFFS
-1999 to +9999 digit
1
0
Process value correction (offset)
The offset can be used to correct the measured value by
a certain amount up or down.
Examples:
Measured value
Offset
Displayed value
294.7 +
0.3
295.0
295.3
– 0.3
295.0