7 Startup
38
7.9
Setting the error signal (S.Err)
NOTE!
An error signal for overrange or underrange is only transmitted on devices with analog output.
Setting
1. Unlock the device.
chapter 7.2 "Unlocking the device (enter the code).", Page 27
2. "Turn" until "S.Err" appears in the bottom line.
3. "Press"
Example:
3.4 nA = In case of measuring range
underflow
Error signal = 0 mA for output of 0 to 20 mA
Error signal = 3.4 mA for output of 4 to 20 mA
Error signal = 0 V for output of 0 to 10 V
22 nA = In case of measuring range
overflow
Error signal = 22 mA for output of 0 to 20 mA
Error signal = 22 mA for output of 4 to 20 mA
Error signal = 10.7 V for output of 0 to 10 V