23
6 Operation
6.4
Parameter
6.4.1
Input
6.4.2
Analog output
Parameter
Display
Setting range
a
a
The default setting is highlighted in
bold
.
Unit of pressure
bar
kPa
MPa
psi
mbar
Note:
The units kPa and mbar are not configurable for all
measuring ranges.
Offset
(zero point correction)
-20.00 to
0,00
to +20.00 % of the measuring
range
Note:
Automatic offset correction, see
chapter 7.5 "Setting the zero point (offset) (Off.P)",
Page 31
Damping
(filter time constant)
0.00
to 99.99 s
Parameter
Display
Setting range
a
a
The default setting is highlighted in
bold
.
Type of signal
(only with analog output)
4 to 20 mA
0 bis 20 mA
0 to 10 V
Scaling start
(only with analog output)
0.00
to 75.00% of the nominal measuring range
Scaling end
(only with analog output)
25.00 to
100%
of the nominal measuring range
Signal in case of error
(only for analog output)
3.4 mA or 22 mA
for output signals 4 to 20 mA
0 mA or 22 mA
for output signals 0 to 20 mA
0 V or 10.7 V
for output signals 0 to 10 V
chapter 7.9 "Setting the error signal (S.Err)",
Page 38
Note:
Depending on the configured output signal
Summary of Contents for DELOS SI