10138

Modbus - SmartSwitch Gateway

Summary of Contents for 10138

Page 1: ...10138 Modbus SmartSwitch Gateway ...

Page 2: ...tions or up to 50 five wire SmartSwitch stations Each button has its own momentary and maintain registers Button press buffer register allows for monitoring a single register for all button presses Supports intensity color and flash patterns for station LEDs certain station types only Modbus RTU RS485 Interface Baud rates up to 115 2K supported ...

Page 3: ... Parity Stop Bits DIP D Modbus RS232 Port E Modbus RS485 Port F 5 Wire SmartSwitch Port G 2 Wire SmartSwitch Port A B C G D E F Specifications Electrical Rate Voltage 18 24 V AC or DC Power supply must be Class 2 Power Consumption 1 7VA 0 75VA for each SmartSwitch attached Dimensions 1 76 width x 5 6 long ...

Page 4: ... Lighting Controls Page 4 2 Wire SmartSwitches backside shown To additional 2 wire SmartSwitches total 8 Use Belden 9740 cable or Equivalent Wire connections are not polarity sensitive Max cable length is 500 feet ...

Page 5: ...aisy chain manner Up to 50 Five wire SmartSwitches can be daisy chained together GND 5 Wire SmartSwitch Port Pinout Data 24V 24V Data SmartSwitches can be connected to either the 2 wire or 5 wire port Both ports can be used at the same time allowing for a mix of 2 wire and 5 wire stations ...

Page 6: ... GND Modbus RS 232 Port Pinout Modbus RS 485 Port Pinout Modbus communication to the gateway can be either through the RS 232 port or through the RS 485 port Only use one port at a time There is no configuration to change to switch from one port to the other ...

Page 7: ...N ON ON ON OFF OFF 61 ON OFF ON ON ON ON OFF OFF 62 OFF ON ON ON ON ON OFF OFF 63 ON ON ON ON ON ON OFF OFF Positional Value 1 2 4 8 16 32 64 128 Switch Number 1 2 3 4 5 6 7 8 Address 64 OFF OFF OFF OFF OFF OFF ON OFF 65 ON OFF OFF OFF OFF OFF ON OFF 66 OFF ON OFF OFF OFF OFF ON OFF 67 ON ON OFF OFF OFF OFF ON OFF 68 OFF OFF ON OFF OFF OFF ON OFF 69 ON OFF ON OFF OFF OFF ON OFF 70 OFF ON ON OFF OF...

Page 8: ...ON OFF ON 188 OFF OFF ON ON ON ON OFF ON 189 ON OFF ON ON ON ON OFF ON 190 OFF ON ON ON ON ON OFF ON 191 ON ON ON ON ON ON OFF ON Positional Value 1 2 4 8 16 32 64 128 Switch Number 1 2 3 4 5 6 7 8 Address 192 OFF OFF OFF OFF OFF OFF ON ON 193 ON OFF OFF OFF OFF OFF ON ON 194 OFF ON OFF OFF OFF OFF ON ON 195 ON ON OFF OFF OFF OFF ON ON 196 OFF OFF ON OFF OFF OFF ON ON 197 ON OFF ON OFF OFF OFF ON ...

Page 9: ...Parity and Stop bits using the SW2 DIP switches all unused switches should be off 1 2 3 Baud OFF OFF OFF 9600 ON OFF OFF 19200 OFF ON OFF 28800 ON ON OFF 38400 OFF OFF ON 57600 ON OFF ON 76800 OFF ON ON 115 2K 4 Parity OFF Even ON NONE 5 Stop Bits OFF 1 ON 2 ...

Page 10: ... Touch Plate Lighting Controls Page 10 ...

Page 11: ...s of the SmartSwitches have 8 buttons so each station is take 8 registers On SmartSwitches with less than 8 buttons some registers will be unused Register 1000 Station 1 8 Button ExampleF 1000 Station 7 1 8 Button 3 1000 6 8 3 Register 1051 Maintain inputs will read as a 1 while the button is pressed and held and read as 0 when the button is released Register Address Register Type Description 6100...

Page 12: ...14 D6 215 D7 Blue 25 25 19 26 1A 27 1B 28 1C 29 1D 30 1E 31 1F Blue 50 89 59 90 5A 91 5B 92 5C 93 5D 94 5E 95 5F Blue 75 153 99 154 9A 155 9B 156 9C 157 9D 158 9E 159 9F Blue 100 217 D9 218 DA 219 DB 220 DC 221 DD 222 DE 223 DF Yellow 25 33 21 34 22 35 23 36 24 37 25 38 26 39 27 Yellow 50 97 61 98 62 99 63 100 64 101 65 102 66 103 67 Yellow 75 161 A1 162 A2 163 A3 164 A4 165 A5 166 A6 167 A7 Yello...