JUMO 00577948 Safety Manual Download Page 23

23

5 Safety-related applications

5.7

Regular tests

Regularly test the function of the entire safety loop according to IEC/EN 61508 and EN 61511. 
The intervals for the inspection are specified by the intervals for the individual devices in the safety loop.
It is the responsibility of the operator to select the type of inspection and the intervals in the specified
period of time.
The test must be carried out so that the correct function of the safety device can be demonstrated in
conjunction with all components.
In SIL applications, the devices have to be checked after the maximum maintenance/test interval at the
latest if they make up a proportion of the entire safety circuit that is not more than 10 %.

Possible behavior for the recurring tests in order to detect dangerous and undetected device faults

A calibrated simulator (current 0/4 to 20 mA) or a sensor simulator and one or (preferably) two calibrated
digital multimeters are required to test the devices.

1. Carry out the appropriate steps in order to prevent misuse.

2. Disconnect the safety circuit from further processing steps.

3. Connect the current simulator to the input of the repeater power supply and input isolating amplifier

or connect the sensor simulator to the input of the transmitter.

4. Connect the digital multimeters to the input and output of the repeater power supply and input iso-

lating amplifier respectively.

5. Set a signal in the range of 4 to 20 mA at the input of the device or set a suitable signal at the input

of the connected transmitter with the sensor simulator.

6. Measure the current in the repeater power supply and input isolating amplifier. The output must ad-

just to the same value.

7. You can verify that subsequent processing steps can detect and accordingly evaluate signals outside

of the range by applying a setting of 

3.6 mA/> 21 mA. If the output value deviates by more than 3x

the specified class accuracy from the input value, the device should be inspected. Replace the de-
vice with an equivalent device in the event of a fault.

8. Establish the full function of the safety circuit.

9. Establish normal operation again.

5.8

Repairs

The devices have a long life cycle, are protected against malfunctions, and are maintenance-free. 
If a device fails despite this, send it back to JUMO GmbH & Co. KG. Specify the type of malfunction and
the possible reason for the malfunction when doing so.
Use the original package or a suitably secure transport container to send back devices for repair.
Download the "Supplementary sheet for product returns" from our website, please fill it out, and send it
together with the faulty device to:
JUMO GmbH & Co. KG
Moritz-Juchheim-Straße 1
36039 Fulda
GERMANY

Summary of Contents for 00577948

Page 1: ...70753000T99Z001K000 V1 00 EN 00770263 2022 05 13 JUMO Ex i Repeater power supply and input isolating amplifier Safety Manual...

Page 2: ......

Page 3: ...tput of current without HART communication 13 3 7 Output of current with HART communication 14 3 8 HART communication 14 3 9 Output Voltage 14 3 10 Voltage supply 14 3 11 Dimensions 14 3 12 Mounting 1...

Page 4: ...Contents 5 6 Notes for operation 22 5 7 Regular tests 23 5 8 Repairs 23 5 9 Standards 24 5 10 Abbreviations 24...

Page 5: ...word indicates that personal injury may occur if the respective precautionary measures are not carried out CAUTION This symbol indicates that components could be destroyed by electrostatic discharge...

Page 6: ...ed value on the Ex or non Ex side and transmitted bidirectional To increase the HART impedance in low resistance systems an additional resistor can be activated in the output circuit using the switch...

Page 7: ...vice is intended for a clean and dry environment Do not expose the device to any mechanical and or thermal stresses that exceed the described lim its Only use the device up to a pollution degree of 2...

Page 8: ...tors in non intrinsi cally safe electrical circuits or actuating DIP switches is only permitted in a de energized state or if no potentially explosive atmosphere is present The device must be taken ou...

Page 9: ...output voltage Uo 25 2 V Max output current Io 93 mA Max output power Po 587 mW Max external inductance Lo max external capacitance Co Simple electrical circuit IIB 4 mH 820 nF Simple electrical circu...

Page 10: ...2 Safety requirements and installation instructions 10...

Page 11: ...provide adequate protection against electric shock or burns Provide a switch power switch close to a device that is marked as the disconnecting device for this device or the entire control cabinet Pr...

Page 12: ...toggling current voltage output S2 resistance in the output circuit to increase HART impedance 3 Green LED PWR voltage supply 4 Snap on foot for mounting rail installation 3 1 3 2 3 3 1 1 1 2 1 3 PWR...

Page 13: ...d 4 3 3 6 Output of current without HART communication Zone 2 Div 2 IN OUT 24 230 V AC DC 4 3 4 2 3 3 3 2 250 4 1 3 1 1 2 1 1 250 S2 S1 PLC DCS passive 3 2 3 1 active 3 3 3 2 AI Sensor Field or 4 2 4...

Page 14: ...positiona of the input card at terminal of the HART communicator S1 S2 Source passiv input card 250 3 1 and 3 2 3 1 and 3 2 I II 250 3 1 and 3 2 3 2 and 3 3 I I Sink active input card 250 3 2 and 3 3...

Page 15: ...e conductor cross section 0 2 mm2 to 2 5 mm2 1 Strip 7 mm of the wire and provide it with ferrules 2 Insert the wire into the relevant connection terminal 3 Tighten the screw in the opening above the...

Page 16: ...evel conversion between the input and output is not provided for 4 to 20 mA input signals therefore become 4 to 20 mA output signals In the same manner active input signals of 0 to 20 mA become galvan...

Page 17: ...nductances Li the full values of C0nd L0 can be used chapter 2 6 Safety data according to ATEX Page 9 Proof of intrinsic safety mixed intrinsically safe electrical circuit Condition for the mixed intr...

Page 18: ...4 Comparison of the safety data 18...

Page 19: ...ut signal and is not outside the range Hazardous identifiable faults are those that deliver a signal outside of the range 3 6 mA 21 mA 5 2 1 channel operation as a repeater power supply and input isol...

Page 20: ...d rate is taken as the basis The proportion of the device at PFH PFD of the entire safety loop is less than 10 5 3 2 channel operation as a repeater power supply and input isolating am plifier for SIL...

Page 21: ...27 10 9 h The requirements when it comes to the PFH value for a SIL3 system are therefore met The values for 1 2 3 4 5 6 7 8 and 10 years mean that the calculated PFDavg values are within the permissi...

Page 22: ...sensor simulator and a calibrated digital multimeter may be required to test the device with a connected transmitter Put the safety circuit into operation and check it for correct functioning 5 6 Note...

Page 23: ...ut of the transmitter 4 Connect the digital multimeters to the input and output of the repeater power supply and input iso lating amplifier respectively 5 Set a signal in the range of 4 to 20 mA at th...

Page 24: ...onal unit to continue performing a required function in cases in which fault or deviations exist D Rate of dangerous failures Rate of dangerous failures per hour DD Rate of dangerous detected failures...

Page 25: ......

Page 26: ...oy Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email I...

Reviews: