JUMO 00577948 Safety Manual Download Page 19

19

5 Safety-related applications

5

Safety-related applications

The following information applies for the device:

The safety-oriented repeater power supply and input isolating amplifier mentioned above is certified for
compliance with DIN EN 61508 and IEC 62061.
Test certificate: ZP/C006/21

5.1

Safety function and safety requirements

The safety function of the device consists of galvanically isolated transmission of a standard signal of
4 to 20 mA with a max. deviation of 2 %.
Output values outside the range of 3.6 to 21 mA are considered a safe operating state, which is detected
by the downstream control system.
Safe faults in the device are therefore those where the device delivers an output signal that does not
deviate more than 2 % from the input signal.
Hazardous, unidentifiable faults are those where the device does not follow a change in the input signal
or deviates by more than 2 % from the input signal and is not outside the range.
Hazardous, identifiable faults are those that deliver a signal outside of the range (< 3.6 mA/> 21 mA).

5.2

1-channel operation as a repeater power supply and input isolating am-
plifier for SIL2 (1oo1) applications

5.2.1

Safety/integrity requirements

Fault rates

Type A device (according to IEC/EN 61508-2)

Safety integrity level (SIL) 2 (1oo1 structure)

Systematic capability (SC) 3 (1oo2 structure)

HFT 0

MTTR  24 h

MTR  8 h

Mission time 10 years

Safety response time 2 s

Ambient temperature 40 °C

Proof test coverage (PTC) 97 %

Process safety time 500 ms

Switch-on duration 2 s

Safety characteristics according to IEC 61508 Edition 2

The entire failure rate is 558 FIT.
The MTBF is therefore 205 years.
The fault rates are used to calculate the average probability of failure of the designed function in the
event of a request for the operating type "low demand" and the probability of a hazardous failure per hour
for the operating type "continuous demand".

Designation

Part no.

JUMO Ex-i repeater power supply and input isolating amplifier

00577948

SU

SD

DU

DD

SFF

DC

D

251

0

62.1

0

80.17 %

0 %

Summary of Contents for 00577948

Page 1: ...70753000T99Z001K000 V1 00 EN 00770263 2022 05 13 JUMO Ex i Repeater power supply and input isolating amplifier Safety Manual...

Page 2: ......

Page 3: ...tput of current without HART communication 13 3 7 Output of current with HART communication 14 3 8 HART communication 14 3 9 Output Voltage 14 3 10 Voltage supply 14 3 11 Dimensions 14 3 12 Mounting 1...

Page 4: ...Contents 5 6 Notes for operation 22 5 7 Regular tests 23 5 8 Repairs 23 5 9 Standards 24 5 10 Abbreviations 24...

Page 5: ...word indicates that personal injury may occur if the respective precautionary measures are not carried out CAUTION This symbol indicates that components could be destroyed by electrostatic discharge...

Page 6: ...ed value on the Ex or non Ex side and transmitted bidirectional To increase the HART impedance in low resistance systems an additional resistor can be activated in the output circuit using the switch...

Page 7: ...vice is intended for a clean and dry environment Do not expose the device to any mechanical and or thermal stresses that exceed the described lim its Only use the device up to a pollution degree of 2...

Page 8: ...tors in non intrinsi cally safe electrical circuits or actuating DIP switches is only permitted in a de energized state or if no potentially explosive atmosphere is present The device must be taken ou...

Page 9: ...output voltage Uo 25 2 V Max output current Io 93 mA Max output power Po 587 mW Max external inductance Lo max external capacitance Co Simple electrical circuit IIB 4 mH 820 nF Simple electrical circu...

Page 10: ...2 Safety requirements and installation instructions 10...

Page 11: ...provide adequate protection against electric shock or burns Provide a switch power switch close to a device that is marked as the disconnecting device for this device or the entire control cabinet Pr...

Page 12: ...toggling current voltage output S2 resistance in the output circuit to increase HART impedance 3 Green LED PWR voltage supply 4 Snap on foot for mounting rail installation 3 1 3 2 3 3 1 1 1 2 1 3 PWR...

Page 13: ...d 4 3 3 6 Output of current without HART communication Zone 2 Div 2 IN OUT 24 230 V AC DC 4 3 4 2 3 3 3 2 250 4 1 3 1 1 2 1 1 250 S2 S1 PLC DCS passive 3 2 3 1 active 3 3 3 2 AI Sensor Field or 4 2 4...

Page 14: ...positiona of the input card at terminal of the HART communicator S1 S2 Source passiv input card 250 3 1 and 3 2 3 1 and 3 2 I II 250 3 1 and 3 2 3 2 and 3 3 I I Sink active input card 250 3 2 and 3 3...

Page 15: ...e conductor cross section 0 2 mm2 to 2 5 mm2 1 Strip 7 mm of the wire and provide it with ferrules 2 Insert the wire into the relevant connection terminal 3 Tighten the screw in the opening above the...

Page 16: ...evel conversion between the input and output is not provided for 4 to 20 mA input signals therefore become 4 to 20 mA output signals In the same manner active input signals of 0 to 20 mA become galvan...

Page 17: ...nductances Li the full values of C0nd L0 can be used chapter 2 6 Safety data according to ATEX Page 9 Proof of intrinsic safety mixed intrinsically safe electrical circuit Condition for the mixed intr...

Page 18: ...4 Comparison of the safety data 18...

Page 19: ...ut signal and is not outside the range Hazardous identifiable faults are those that deliver a signal outside of the range 3 6 mA 21 mA 5 2 1 channel operation as a repeater power supply and input isol...

Page 20: ...d rate is taken as the basis The proportion of the device at PFH PFD of the entire safety loop is less than 10 5 3 2 channel operation as a repeater power supply and input isolating am plifier for SIL...

Page 21: ...27 10 9 h The requirements when it comes to the PFH value for a SIL3 system are therefore met The values for 1 2 3 4 5 6 7 8 and 10 years mean that the calculated PFDavg values are within the permissi...

Page 22: ...sensor simulator and a calibrated digital multimeter may be required to test the device with a connected transmitter Put the safety circuit into operation and check it for correct functioning 5 6 Note...

Page 23: ...ut of the transmitter 4 Connect the digital multimeters to the input and output of the repeater power supply and input iso lating amplifier respectively 5 Set a signal in the range of 4 to 20 mA at th...

Page 24: ...onal unit to continue performing a required function in cases in which fault or deviations exist D Rate of dangerous failures Rate of dangerous failures per hour DD Rate of dangerous detected failures...

Page 25: ......

Page 26: ...oy Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email I...

Reviews: