3 Installation
14
3.7
Output of current with HART communication
3.8
HART® communication
HART communicators (HHT) can be connected as shown in the basic circuit diagram. Test sockets (di-
ameter 2.3 mm) are integrated in the screw connection terminal blocks for this purpose.
3.9
Output Voltage
3.10
Voltage supply
The voltage supply is fed in via the connection terminals 1.1 (+) und 1.2 (-) (DC/AC 24 to 230 V).
3.11
Dimensions
Connection for
Electrical
circuit im-
pedance
Connection
DIP-switch position
a
of the input card
at terminal
of the HART
communicator
S1
S2
Source (passiv input card)
250
3.1 (+) and 3.2 (-)
3.1 and 3.2
I
II
250
3.1 (+) and 3.2 (-)
3.2 and 3.3
I
I
Sink (active input card)
250
3.2 (+) and 3.3 (-)
3.2 and 3.3
I
II
250
3.2 (+) and 3.3 (-)
-
I
II
a
The two DIP-switches are located at the front of the device. Settings made to the device with DIP-switches must
occur in a voltage-free state.
Connection for
Connection of the input card at the terminal
DIP-switch position
a
S1
S2
Source – passive input card
3.1 (+) and 3.2 (-)
II
II
a
The two DIP-switches are located at the front of the device. Settings made to the device with DIP-switches must
occur in a voltage-free state.