background image

JUDO SPEEDY-LongLife

15

Operation

ATTENTION

(see chapter “Safety information and
dangers due to non-compliance”)

If the interval until the next backwashing is
longer than two months, the particles on the
filter screen can stick or a large filter pres-
sure resistance can result.

Unauthorized persons must not operate the
filter! Persons who operate the filter must
observe the operating instructions. Failure
to observe these instructions can result in
damage to property and personal injuries.

The smaller the mesh size of the screen in-
sert the more frequently backwashing has to
be carried out!

Experience shows that increased dirt is de-
posited during the initial running period. If
so, the unit has to be flushed more often
than usual.

Failure to flush in good time can cause dam-
age to the screen. Larger quantities of fil-
tered particles can deform the screen and as
an extreme incident cause the tearing of the
screen. As a result a filter function is not any
longer ensured. In addition, larger quantities
of dirt can cause mechanical impairment
concerning the backwashing function.

5.4

Modifications / changes / 
spare parts

ATTENTION

(see chapter “Safety information and
dangers due to non-compliance”)

Only original spare parts are to be used!

Arbitrary modifications and changes are
prohibited for safety reasons! They can im-
pair the function of the filter, lead to leaks
and as an extreme incident they can lead to
the bursting of the filter.

The imprinted test marks are only valid if
original spare parts are used.

5.4.1 Servicing / repair

Before carrying out any work on the filter,
that is beyond pure operation induced con-
trol, the filter has to be depressurized! Fail-
ure to observe this can lead to an uncon-
trolled escape of water and therefore lead to
water damages in the building. Strictly com-
ply with the instructions given in the “Instal-
lation” and “Maintenance” chapters.

Summary of Contents for SPEEDY-LongLife JSY-LF 1 1/2"

Page 1: ...ty information before installing and putting the unit into service These must always be issued to the owner user Installation and Operating Instructions JUDO SPEEDY LongLife Backwash protective filter...

Page 2: ...con fidence in us which you have shown by purchasing this device The product you have purchased is a filter developed us ing state of the art technology This filter is suitable for use in cold drink...

Page 3: ...anently be available at the place where the filter is used This instruction manual is intended to make it easier to familiarize yourself with the filter and its possible intended uses The instruction...

Page 4: ...etail failure to observe the general danger symbols can result for example in the following risks Failure of important functions of the filter Danger to persons due to electrical and mechanical effect...

Page 5: ...the art technology and the safety regulations generally accepted in Germany The filter may only be operated in accor dance with the manufacturer s specifica tions Any other operation or operation bey...

Page 6: ...e not splash water proof and are situated in the direct vicinity of the filter may be damaged by water leaking from the filter caused as a result of the device not being operated in accordance with th...

Page 7: ...ciation for the gas and water industries in accordance with the requirements of the standards DIN EN 13443 1 and DIN 19632 100 pressure stage PN 16 for mechanical filters for use in drinking water and...

Page 8: ...the place of installation The room where the unit is installed must be dry and frost free Unauthorised persons must not have ac cess to the filter ATTENTION see chapter Safety information and dangers...

Page 9: ...ontal position The built in rotary flange must be fitted so that mechanical stresses cannot occur Other wise mechanical damage can result the pipe may burst or the built in rotary flange can break Thi...

Page 10: ...th of the wastewater pipe etc The dimensioning must at least allow all the wastewater to be discharged at the same time If it is not possible to provide a wastewater connection directly beneath the fi...

Page 11: ...JUDO SPEEDY LongLife 11 Installation 4 2 1 Backwashing water discharge options JSY LF 1 JSY LF 1 2 Fig 5 Backwashing water discharge options 200 mm min 10 l 200 mm min 10 l 20 mm 40 mm 20 mm 40 mm...

Page 12: ...hing and venting the filter is ready for use 5 2 Functional description Water flows through the built in rotary flange into the filter A coarse filter JSY LF 1 2 prevents large dirt particles from get...

Page 13: ...JUDO SPEEDY LongLife 13 Operation Fig 6 Functional description Built in rotary flange Display button for the next backwashing date Filter bell Handwheelforactuating the backwashing...

Page 14: ...kwashing process can be repeated if necessary ATTENTION see chapter Safety information and dangers due to non compliance This backwashing process must be carried out until the audible locking into pla...

Page 15: ...can deform the screen and as an extreme incident cause the tearing of the screen As a result a filter function is not any longer ensured In addition larger quantities of dirt can cause mechanical imp...

Page 16: ...will become loose at operating pressure or that it can burst Leaking water can cause major material damages to the building In addition people near the filter can be injured by blistering filter parts...

Page 17: ...e kinds of cleaners must therefore not be used 8 Warranty and services In order to comply with the legal warranty claim according to DIN 1988 Part 8 it is necessary that the backwashing takes place at...

Page 18: ...es the pressure class according to which the filter must fulfill the requirements of the standards DIN EN 13443 1 and DIN 19632 100 The maximum operating pressure is lower in order to en sure the opti...

Page 19: ...es JSY LF 2 JUDO Automatic controls set JAUS Order no 8170244 For subsequent upgrade of the manual backwash protective filter to an auto matic backwash protective filter Fig 7 Installation dimensions...

Page 20: ...20 JUDO SPEEDY LongLife Spare parts 10 Spare parts 10 1 JSY LF 1...

Page 21: ...9 2 5 Profile flange seal 1 1200218 5 6 Strainer 1 2070302 70 7 Suction pipe silver plated 1 1120534 38 8 O ring 18x2 5 2 1200291 2 9 Flushing valve premounted 1 2170179 75 10 Suction pipe base 1 1120...

Page 22: ...22 JUDO SPEEDY LongLife Spare parts 10 2 JSY LF 1 2...

Page 23: ...1200291 2 7 Flushing valve premounted 1 2170179 75 8 Suction pipe base 1 1120464 6 9 Filter bell 1 1120459 212 10 Flange 1 1430099 41 11 Display button 1 1120424 2 12 Cover of filter bell JSY LF 1 1...

Page 24: ...88 Fax 32 0 24 61 18 85 e mail info benelux judo eu www judo eu JUDO France S r L 76 Rue de la Plaine des Bouchers Technosud F 67100 Strasbourg Tel 33 0 3 88 65 93 94 Fax 33 0 3 88 65 98 49 e mail inf...