background image

15

3.0 Installation

3.1 Floor

Foundation

You need to make sure the foundation is suitable for a fireplace. 
See “2.0 Technical Data” for specified weight. 

Requirements for protection of wooden 
flooring beneath the fireplace

The Jøtul I 

500

 Series has a heat shield underneath to protect the 

floor from radiated heat. The product can therefore be positioned 
directly on a wooden floor that is covered by a sheet of metal or 
other non-inflammable material. The recommended minimum 
thickness is 

0.9 mm

. The plate must cover the entire floor surface 

within the surround. 

We recommend the removal of any flooring that is not attached 
to the foundation (“floating floors”) beneath the installation. 
Any floor covering of inflammable material, such as linoleum, 
carpets, etc. must be removed from under the floor plate. 

Requirements for protection of inflammable 
floors in front of the fireplace

The floor in front of the fireplace must be protected by a sheet 
of metal or other non-inflammable material. The recommended 
minimum thickness is 0.9 mm. The floor plate must comply with 
national laws and regulations. 

Contact your local building authorities regarding restrictions and 
installation requirements. 

3.2 Wall

Distance to inflammable wall protected by 
insulation (Fig. 1) 

Insulation requirements 
50 mm

 rock wool 120 kg/m

3

 with aluminium foil on one side. 

Distance to inflammable wall protected by 
firewall (Fig. 1) 

Requirements for regulation firewalls

The firewall must be at least 100 mm thick and made of brick, 
concrete or lightweight concrete. Other materials and structures 
with satisfactory documentation may also be used. 

Contact your local building authorities regarding restrictions and 
installation requirements. 

Distance to non-inflammable wall (Fig. 1) 

“Non-inflammable wall” here means a non-bearing wall of 
continuous brickwork/concrete. 

Requirements for fireplace surround

Fireplace surrounds must be made of a non-inflammable 
material

Note that the entire back wall and, if any, side walls within the 
surround must be covered with insulation/firewalls. 

If the cowl is built up to the ceiling and the ceiling is of 
inflammable material, extra panelling must be installed above 
the top of the heating chamber and above the cowl’s vents in 
order to prevent the ceiling becoming hot. Use for example: Rock 
wool, 

100 mm

 thick, on a steel plate 

(min. 0.9 mm)

. See 

Fig. 2A

.  

Ensure there is adequate ventilation in the top of the cowl – e.g. 
a gap under the ceiling. 

NB: Remember that it must be possible to sweep and inspect 
the installation. 

3.3 Air supply (Fig. 2) 

Air must flow between the insert and the brickwork, and it is 
extremely important that there is an unimpeded air supply to 
the air inlets.
 

The air inlet dimensions specified in the text are minimum 
requirements. 

Required air vent sizes (for air circulation): 

Base:  Minimum of 500 cm

2

 free opening. 

Top:  Minimum of 750 cm

2

 free opening. 

This is a safety measure to ensure that the build-up of heat inside 
the surround does not become too great and that the output of 
heat to the room is adequate. 

If the house is poorly ventilated, the room must be fitted with 
an additional supply of outside air, e.g. by means of a separate 
duct under the fireplace, 

Fig. 2 C

. The outside air duct should be 

as straight as possible and must be made of a non-inflammable 
material. It must be possible to close the ducts with a damper in 
order to keep out cold air when the stove is not being used. We 
recommend Jøtul’s outside air damper, catalogue no. 340654. 

3.4 Ceiling

The fireplace can be fitted with the top edge of the hot air opening 
of the surround 

at least 400 mm

 below a ceiling of inflammable 

material. See 

Fig. 2

. Ensure there is adequate ventilation in the 

top of the cowl – e.g. a gap under the ceiling. 

3.5 Chimney and flue pipe

•  The fireplace can be connected to a chimney and flue pipe 

approved for solid fuel fireplaces with flue gas temperatures 
as specified in 

“2.0 Technical Data”

•   The cross-section of the chimney must be at least that of the 

flue pipe. Use 

“2.0 Technical Data”

 to calculate the correct 

chimney cross-section.

•  Several solid fuel stoves can be connected to the same chimney 

system if the chimney cross section is adequate. 

•   Before a hole is made in the chimney, the fireplace should be 

test-mounted in order to correctly mark the position of the 
fireplace and the hole in the chimney. See Fig. 1 for minimum 
dimensions. 

•   Make sure that the flue pipe rises all the way up to the 

chimney. 

•   Use a flue pipe bend with a sweep hatch to allow sweeping. 

Please note

 that it is extremely important for connections to 

have a degree of flexibility. This is to prevent any movement in 
the installation leading to the formation of cracks. 

NB:

 A correct and airtight connection is extremely important for 

the function of the product. 

ENGLISH

Reviews: