10
130112_Rev 2 GF 160 DV 1/22
Figure 6.2.
Vent Termination Restriction Zones - NG / LP.
See also Snorkel Termination vent run restrictions, pg. 12.
Figure 6.4.
Determine the dial notch position appropriate to your vent
configuration as designated in Fig 6.2. Pivot the dial to align the
lock nut with that notch.
Remove Collar Grills
Figure 6.3.
Use a 10 mm wrench to loosen the Restrictor lock nut.
Pivot
Lever
Lock Nut
Approved Horizontal and Vertical Vent
Terminations
• ALL VENTING MUST TERMINATE (END)
WITHIN ONE OF THE DESIGNATED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE
POSITION THAT CORRESPONDS TO THE
VENT TERMINATION AREA IN THE MATRIX.
When termination is exactly on a division line,
use the less restrictive position. For example,
if termination is 10 feet high and offset 7 feet,
restriction should be set at Position B.
• Up to two 45° elbows or one additional 90° elbow is
permitted in addition to the first elbow, however, a 5
foot reduction in horizontal length must be made for
each
additional elbow whether 45° or 90°.