12
139678
-R
01
F
100
May,
2015
Figure 12
Jøtul F
100
Clearance Chart
All clearances established with included stove rear heat shield installed.
Stove
Unprotected Surface
Protected Surface
Clearances
Installation
per NFPA211 or CAN/CSA -B365-M93
Side
Rear
Corner*
Side
Rear
Corner*
A
B
J
C
D
K
Single-wall Connector
15” 11” 10” 10” 5” 7”
381 mm
280 mm
254 mm
254 mm
127 mm
178 mm
Single-wall Connector
E
F
L
G
H
M
with Connector Shields
17” 8” 10” 10” 5” 7”
or Double-wall Connector*
432 mm
203 mm
254 mm
254 mm
127 mm
178 mm
Chimney Connector
Unprotected Surface
Protected Surface
Vertical Installation
per NFPA211 or CAN/CSA-B365-M93
Single-wall Connector
11” (280 mm)
6” (153 mm)
Single-wall Connector
with Connector Shields
8” (203 mm)
5” (127 mm)
or Double-wall Connector*
Chimney Connector
Unprotected Surface
Protected Surface
Horizontal Installation
per NFPA211 or CAN/CSA-B365-M93
Single-wall Connector
18” (457 mm)
12” (305 mm)
Double-wall Connector*
Manufacturer’s Listing
Manufacturer’s Listing
* Double Wall Connector must be installed with Flue Collar Heat Shield Kit 154996.
Mantel and Trim Clearances
Top and Side Trim is 1” thick or less
Maximum Mantel depth 12”
Unprotected Surfaces
Protected Surfaces
A. Mantel
22” (560 mm)
9” (230 mm)
B: Top Trim
17” (430 mm)
8” (200 mm)
C: Side Trim
14” (355 mm)
7” (430 mm)