background image

17

Jøtul C 

550

 CB Rockland    139656_04     5/15/15

 

 

  ­€‚ƒ€

„‚

…

„„

„„

„‚

…

Blower Operation

Access the blower control panel by lifting the cast iron 

lower grille up off the insert.
     The dual blowers will enhance heat circulation around 

the firebox and out into the room. In the 

Automatic

 

setting, the blowers are controlled by a heat activated 

switch (snapstat) that will only function when the speed 

control is ON. After the fire has been burning for a time, 

the snapstat will react to the heat and activate the 

blowers. Conversely,  the blower will continue to operate 

until the snapstat cools as the fire wanes. The blowers will 

then shut off automatically.

The 

Manual

 setting overrides the snapstat 

functionality allowing blower operation regardless of 

temperatures.

For best performance, do not turn the switch on until 

after the fire is well-established.

If the blower is not needed, place the blower control 

switch in the OFF position. 

See

 Blower Maintenance,

 page 19 for further 

information.

Figure 19.  C 550 CB Wiring diagram.

Color Key

 

BR - Brown 

BL - Blue 

BK - Black 

GY - Gray 

G - Green

Figure 18.  Blower and speed controls.

 

THIS BLOWER MUST BE ELECTRICALLY 

GROUNDED IN ACCORDANCE WITH LOCAL 

CODES OR, IN THE ABSENCE OF LOCAL 

CODES, WITH THE CURRENT ANSI/NFPA 

70, NATIONAL ELECTRICAL CODE OR CSA 

C22.1-CANADIAN ELECTRICAL CODE.

 

THIS UNIT IS SUPPLIED WITH A THREE-

PRONG (GROUNDING) PLUG FOR 

PROTECTION AGAINST SHOCK HAZARD 

AND SHOULD BE PLUGGED DIRECTLY INTO 

A PROPERLY GROUNDED THREE-PRONG 

RECEPTACLE.  DO NOT CUT OR REMOVE 

THE GROUNDING PRONG FROM THE PLUG. 

  DO NOT USE ANY POWER SUPPLY CORD 

OTHER THAN THAT SUPPLIED WITH THIS 

UNIT. 

 

 ALWAYS DISCONNECT THE POWER 

SUPPLY WHEN PERFORMING ANY SERVICE 

ON THE FIREPLACE INSERT.

WARNING !

It is also important to remember that chimney size, 

temperature and height all affect draft which in turn 

affects the formation of creosote.  An exterior chimney, 

whether masonry or prefabricated steel, will be exposed 

to cold outside temperatures, and consequently, will be 

more prone to creosote accumulation than an interior 

flue.

A chimney flue located within the home interior will 

benefit from the insulating characteristics of the building 

itself. Consequently, the flue system will be less conducive 

to condensation of unburned gases and minimal creosote 

accumulation will result.

As a general rule, try to avoid burning the insert at 

the lowest air control settings. Although a low setting 

will prolong burn time, it may also result in incomplete 

combustion. In reducing the fire intensity, draft is 

weakened and the chimney flue cools. This, together with 

the increase in unburned gases, leads to rapid creosote 

accumulation. 

Summary of Contents for C 550 CB

Page 1: ...land 139656_04 5 15 15 J tul C 550 CB Rockland Fireplace Insert Keep these instructions for future reference Installation and Operating Instructions for the United States Canada V2 J tul C 550 CB Rock...

Page 2: ...Starting Maintaining the Fire 16 Adding Fuel 16 Formation of Creosote 16 Blower Operation 17 Maintenance Ash Removal 18 Glass Care 18 General Maintenance 19 Gaskets 19 Illustrated Parts Breakdown Expl...

Page 3: ...s 4 5 g hr Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made availa...

Page 4: ...appliance will not guarantee proper chimney performance Consult your local J tul authorized dealer regarding specific installation performance issues Preparation We strongly urge you to have your auth...

Page 5: ...te specific conditions The J tul C 550 CB Rockland Fireplace Insert meets U S EPA emission limits for wood heaters sold after July 1990 and is tested and listed to ANSI UL 1482 and CAN ULC S628 93 It...

Page 6: ...and may be installed into a factory built fireplace with the following conditions The factory built fireplace must be listed per UL 127 or ULC S610 The factory built chimney system must be fully lined...

Page 7: ...h combustible floor materials Figure 5 Canada only Minimum depth with code approved raised hearth Min 18 from door opening 2 1 2 The convection chamber louvers of the zero clearance fireplace MUST NOT...

Page 8: ...uch as drapes or doors that could swing into the area within 36 of the insert Mantel Clearances The installation must conform to the minimum mantel clearances specified in the chart below These cleara...

Page 9: ...ine as noted below A Hearth Protection width from centerline 18 1 2 470 mm B Hearth Protection forward from door opening US 16 CAN 20 508 mm C To Side Trim 1 max thickness from centerline 21 3 4 552 m...

Page 10: ...to the first flue tile is acceptable provided the tile is no larger than 8 x 12 5 For external chimneys one or more sides are exposed to the outside below the roof line including garages a positive co...

Page 11: ...nts from the fireplace Alternatively you can wire the damper plate to lock it in the open position Thoroughly clean the firebox and smokeshelf area with a wire brush 2 If the fireplace has been modifi...

Page 12: ...REPLACE 2 Insert the AC power receptacle lead through the ap propriate inlet in the side of the firebox See fig 10 Remove the 8 x 5 8 phillips screw already in place and engage the receptacle bracket...

Page 13: ...Surround Brackets on the firebox Extend the blower power cord out beyond the front of surround panel 6 Attach the Bottom Trim assembly to the two studs located in the firebox floor between the blowers...

Page 14: ...d seasoned more than 2 years will burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log w...

Page 15: ...fire Limit the first fire to just kindling and a couple of 1 2 inch logs and add progressively more and larger logs to subsequent fires keeping the Air Control set to the fully open position It is nor...

Page 16: ...aces to form creosote Failure to keep the chimney system free of creosote build up could result in a chimney fire The creosote that accumulates in the chimney is highly flammable and is the fuel of ch...

Page 17: ...RENT ANSI NFPA 70 NATIONAL ELECTRICAL CODE OR CSA C22 1 CANADIAN ELECTRICAL CODE THIS UNIT IS SUPPLIED WITH A THREE PRONG GROUNDING PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIREC...

Page 18: ...ials pending final disposal If the ashes are disposed of by burial in soil or otherwise dis persed they should be kept in the closed container until all coals and cinders have thoroughly cooled NEVER...

Page 19: ...or seal integrity The gaskets should be soft enough to be somewhat resilient to the touch Over time gaskets will compress and harden Replace worn out or hardened gaskets with the appropriate size mate...

Page 20: ...A 24 127215 Blower Maintenance In order to ensure that the blower delivers many years of reliable performance you should inspect it regularly and clean it of any household dust and debris that may hav...

Page 21: ...21 J tul C 550 CB Rockland 139656_04 5 15 15 This page is intentionally blank...

Page 22: ...l C 550 CB Rockland Illustrated Parts Diagram Use only genuine J tul replacement parts Do not substitute parts from any other manufacturer See your local Authorized J tul Dealer or contact us directly...

Page 23: ...No Description Part Number 1 Rear Shroud 222027 2 Screw 8 x 1 2 Hex Slt 117917 3 Nut M6 Flange 117968 4 Right Baffle Plate 157045 5 Left Baffle Plate 157044 6 Secondary Air Tube Front 223262 7 Seconda...

Page 24: ...Total R R brick R mineral board 0 8 0 431 1 231 Step 3 Compare proposed system R 1 231 to specified R of 0 893 Since R is greater than required the system is acceptable Definitions Thermal conductanc...

Page 25: ...red Over firing can also be identified by warped plates rust colored cast iron paint pig ment that has turned dusty white or bubbling cracking and discolor ation of the enamel finish Misuse includes w...

Page 26: ...26 J tul C 550 CB Rockland 139656 5 15 15 This page is intentionally blank...

Page 27: ...27 J tul C 550 CB Rockland 139656_04 5 15 15 This page is intentionally blank...

Page 28: ...ulations It is important that the these instructions be carefully read and understood before beginning the instal lation J tul pursues a policy of continual product development Consequently products m...

Reviews: