background image

7

Jøtul C 

550

 CB Rockland    139656_04     5/15/15

Hearth Protection Requirements

The floor area in front of fireplace insert must be 

protected from live sparks and radiant heat. 

• Materials: 

Hearth protection must be non com-

bustible insulating board such as 1/2” millboard, or 

the equivalent mortared masonry material. Alter-

nate protection must be composed of materials as 

specified by NFPA 

211.

•  Protected Area:   

U.S:  16” Deep x 37” Wide 

CAN:  20” Deep x 37”  Wide  

    See exception for 18” depth below. 

U.S. : Front -  

The protection must extend at least 16 inches  

forward from the fireplace insert door opening as 

in fig. 4. (14 7/8” from Surround facing).

 

Canada: Front -  

The protection must extend at least 20 in. forward 

from the fireplace insert door opening, (18 7/8” 

from Surround facing). 

  Front protection may be reduced to 18” under the 

following conditions:

  a) it is composed of noncombustible material 

having an R value of .5 or higher such as 1/2” thick 

millboard. See Appendix A on page 23 for exam-

ples.

  b)  it is raised a minimum of 2 1/2” and constructed 

on noncombustible materials in a code-approved 

masonry fireplace. See fig. 5.

  U.S. & Canada:  Sides -  

Protection must extend a 

minimum 18 1/2 in. to both sides of the centerline 

of the insert. See fig 6, A.

Factory-Built Fireplace Requirements, cont’d.

Figure 4.  Required hearth protection if flush with 

combustible floor materials. 

Figure 5.  Canada only: 

Minimum depth with code-approved raised hearth.  

Min.  

18” from 

door 

opening

2 1/2” 

•  The convection chamber/louvers of the zero-

clearance fireplace MUST NOT be blocked off.  The use 

of the cast iron surround panels may not be possible 

in these instances.  A custom-built surround panel 

system may be used provided it does not interfere 

with air circulation through the convection chamber/ 

louvers.

•  Air flow within and around the factory-built fireplace 

shall not be altered by installation of the insert.

•   Alteration of the fireplace in any manner is not 

permitted; i.e. firebrick or refractory panels MUST 

NOT be removed in order to accommodate the insert. 

Exceptions to this are:

  a. 

External trim pieces, that do not affect the  

 

function of the fireplace, may be removed  

 

providing they can be stored on or within  

 

the fireplace for reassembly if the insert    

 

were to be removed.

  b. 

The chimney damper may be removed to   

 

install the chimney liner.

•  Inserts that project from the factory-built fireplace 

must be furnished with appropriate means 

of support. The weight of the insert must not 

compromise the means of support for the factory-

built fireplace.

•   Fireplace Conversion Notice 220508 must be 

permanently attached to the back of the fireplace. 

This metal label is included in the bag containing this 

manual. 

•  Final approval is contingent on the authority having 

local jurisdiction.

Combustible 

Flooring

Min.  

16” U.S. 

20” CAN  

from door 

opening

Min.  

14 7/8” U.S. 

18 7/8” CAN  

from 

 surround 

Summary of Contents for C 550 CB

Page 1: ...land 139656_04 5 15 15 J tul C 550 CB Rockland Fireplace Insert Keep these instructions for future reference Installation and Operating Instructions for the United States Canada V2 J tul C 550 CB Rock...

Page 2: ...Starting Maintaining the Fire 16 Adding Fuel 16 Formation of Creosote 16 Blower Operation 17 Maintenance Ash Removal 18 Glass Care 18 General Maintenance 19 Gaskets 19 Illustrated Parts Breakdown Expl...

Page 3: ...s 4 5 g hr Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made availa...

Page 4: ...appliance will not guarantee proper chimney performance Consult your local J tul authorized dealer regarding specific installation performance issues Preparation We strongly urge you to have your auth...

Page 5: ...te specific conditions The J tul C 550 CB Rockland Fireplace Insert meets U S EPA emission limits for wood heaters sold after July 1990 and is tested and listed to ANSI UL 1482 and CAN ULC S628 93 It...

Page 6: ...and may be installed into a factory built fireplace with the following conditions The factory built fireplace must be listed per UL 127 or ULC S610 The factory built chimney system must be fully lined...

Page 7: ...h combustible floor materials Figure 5 Canada only Minimum depth with code approved raised hearth Min 18 from door opening 2 1 2 The convection chamber louvers of the zero clearance fireplace MUST NOT...

Page 8: ...uch as drapes or doors that could swing into the area within 36 of the insert Mantel Clearances The installation must conform to the minimum mantel clearances specified in the chart below These cleara...

Page 9: ...ine as noted below A Hearth Protection width from centerline 18 1 2 470 mm B Hearth Protection forward from door opening US 16 CAN 20 508 mm C To Side Trim 1 max thickness from centerline 21 3 4 552 m...

Page 10: ...to the first flue tile is acceptable provided the tile is no larger than 8 x 12 5 For external chimneys one or more sides are exposed to the outside below the roof line including garages a positive co...

Page 11: ...nts from the fireplace Alternatively you can wire the damper plate to lock it in the open position Thoroughly clean the firebox and smokeshelf area with a wire brush 2 If the fireplace has been modifi...

Page 12: ...REPLACE 2 Insert the AC power receptacle lead through the ap propriate inlet in the side of the firebox See fig 10 Remove the 8 x 5 8 phillips screw already in place and engage the receptacle bracket...

Page 13: ...Surround Brackets on the firebox Extend the blower power cord out beyond the front of surround panel 6 Attach the Bottom Trim assembly to the two studs located in the firebox floor between the blowers...

Page 14: ...d seasoned more than 2 years will burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log w...

Page 15: ...fire Limit the first fire to just kindling and a couple of 1 2 inch logs and add progressively more and larger logs to subsequent fires keeping the Air Control set to the fully open position It is nor...

Page 16: ...aces to form creosote Failure to keep the chimney system free of creosote build up could result in a chimney fire The creosote that accumulates in the chimney is highly flammable and is the fuel of ch...

Page 17: ...RENT ANSI NFPA 70 NATIONAL ELECTRICAL CODE OR CSA C22 1 CANADIAN ELECTRICAL CODE THIS UNIT IS SUPPLIED WITH A THREE PRONG GROUNDING PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIREC...

Page 18: ...ials pending final disposal If the ashes are disposed of by burial in soil or otherwise dis persed they should be kept in the closed container until all coals and cinders have thoroughly cooled NEVER...

Page 19: ...or seal integrity The gaskets should be soft enough to be somewhat resilient to the touch Over time gaskets will compress and harden Replace worn out or hardened gaskets with the appropriate size mate...

Page 20: ...A 24 127215 Blower Maintenance In order to ensure that the blower delivers many years of reliable performance you should inspect it regularly and clean it of any household dust and debris that may hav...

Page 21: ...21 J tul C 550 CB Rockland 139656_04 5 15 15 This page is intentionally blank...

Page 22: ...l C 550 CB Rockland Illustrated Parts Diagram Use only genuine J tul replacement parts Do not substitute parts from any other manufacturer See your local Authorized J tul Dealer or contact us directly...

Page 23: ...No Description Part Number 1 Rear Shroud 222027 2 Screw 8 x 1 2 Hex Slt 117917 3 Nut M6 Flange 117968 4 Right Baffle Plate 157045 5 Left Baffle Plate 157044 6 Secondary Air Tube Front 223262 7 Seconda...

Page 24: ...Total R R brick R mineral board 0 8 0 431 1 231 Step 3 Compare proposed system R 1 231 to specified R of 0 893 Since R is greater than required the system is acceptable Definitions Thermal conductanc...

Page 25: ...red Over firing can also be identified by warped plates rust colored cast iron paint pig ment that has turned dusty white or bubbling cracking and discolor ation of the enamel finish Misuse includes w...

Page 26: ...26 J tul C 550 CB Rockland 139656 5 15 15 This page is intentionally blank...

Page 27: ...27 J tul C 550 CB Rockland 139656_04 5 15 15 This page is intentionally blank...

Page 28: ...ulations It is important that the these instructions be carefully read and understood before beginning the instal lation J tul pursues a policy of continual product development Consequently products m...

Reviews: