background image

16

139684_Rev_7   /  C 450 Kennebec    7 / 17

Adding Fuel to the Fire

When reloading the stove while a bed of hot embers 

still exists, follow this reloading  procedure:
•  Always wear stove gloves when tending to the fire.
•  Push the Air Control Lever to the full open position 

(far right).

•  Wait a few seconds before opening the door. This 

allows the renewed air circulation to clear unburned 

gases from the firebox.

•  Use a stove tool or poker to distribute the hot embers 

equally around the firebox.

•  Load the fuel, usually with smaller logs first.
•  Close the doors and secure the latch.
•  Wait 5 – 10 minutes for the fire to re-establish before 

adjusting the Air Control Lever for the desired heat 

output. If a thick bed of live coals is present, you may 

be able to add fuel and immediately set the air con-

trol without waiting for the fire to be re-established.

Creosote Formation

The Jøtul C 

450

 is designed to burn wood cleanly and 

efficiently when operated as described in this manual.  

However, when wood is burned slowly and at low 

temperatures, tar and other organic vapors are produced 

which condense on the relatively cooler chimney flue 

surfaces to form creosote. Failure to keep the chimney 

system free of creosote build up could result in a 

chimney fire. 

The creosote that accumulates in the chimney 

is highly flammable and is the fuel of chimney fires.  

To prevent chimney fires, it is important to have the 

chimney flue and connector pipe inspected every two 

months during frequent use and cleaned whenever 

accumulation of 1/4” or more is evident. A qualified 

chimney sweep or other authorized service person can 

provide this service.

It is also important to remember that chimney size, 

temperature and height all affect draft which in turn 

affects the formation of creosote.  An exterior chimney, 

whether masonry or prefabricated steel, will be exposed to 

cold outside temperatures, and consequently, will be more 

prone to creosote accumulation than an interior flue.

A chimney flue located within the home interior 

will benefit from the insulating characteristics of the 

building itself. Consequently, the flue system will be 

less conducive to condensation of unburned gases and 

minimal creosote accumulation will result.

As a general rule, try to avoid burning the insert at 

the lowest air control settings. Although a low setting 

will prolong burn time, it may also result in incomplete 

combustion. In reducing the fire intensity, draft is 

weakened and the chimney flue cools. This, together 

with the increase in unburned gases, leads to rapid 

creosote accumulation.

Figure 20.  Top-down Firebuilding

Starting and Maintaining a Fire

Burn only solid wood directly on the bottom grate of the stove. 

Do not elevate the fire in any way.

Traditional Fire Building  

1.  With the primary air control lever in the full open 

position 

(to the right)

, start with several sheets of 

crumbled newspaper placed directly on the grate. On 

top of the newspaper, place several pieces of small 

dry kindling (approx. 1” in diameter) with two to three 

larger logs (approx. 3” to 5” in diameter) on top.  

2.  Light the fire and close the door, slowly building the 

fire by adding larger and larger logs. Be sure to follow 

the break-in procedure before creating a hot fire that 

might damage the stove.  

3.  Once the fire has become well established, adjust the 

primary air control lever as necessary to generate the 

desired heat output and burn time.

Top-Down Fire Building -

 See fig. 20.

Many people find this method to be superior to the 

traditional method.
1.  With the primary air control lever in the full open 

position 

(to the right)

, place two short 1/4-split logs on 

the firebox floor, perpendicular to the rear wall, about 

6 inches apart. 

2.  Place kindling across the base logs.
3.  Place one or two smaller logs on top of the kindling.
5.  Place newspaper between the two bottom logs under 

the kindling. Light the news paper and close the door.  

Continue to add kindling and small logs as necessary 

to build the fire. Keep the air control fully open until 

the fire is well-established.

                                                   

Summary of Contents for C 450 Kennebec

Page 1: ...only Do not burn any other fuels Read this entire manual before you install and use this appliance Save these instructions for future reference and make them available to anyone using or servicing th...

Page 2: ...are and Replacement 17 General Maintenance 18 Gasket Replacement 18 Appendix A Alternate Hearth Protection 19 Appendix B Alternate Mantel Clearances 20 Illustrated Parts Breakdown Exploded View 21 Par...

Page 3: ...uilding inspector or authority having jurisdiction to determine what regulations apply in your area THE JOTUL C 450 KENNEBEC FIREPLACE INSERT IS NOT APPROVED FOR USE IN MOBILE HOMES This heater meets...

Page 4: ...replace Safety Notices BURN SOLID WOOD FUEL ONLY DO NOT BURN ANY OTHER FUELS DO NOT USE CHEMICALS OR FLUIDS TO START THE FIRE DO NOT BURN Garbage OR FLAMMABLE FLUIDS IF THIS ROOM HEATER IS NOT PROPERL...

Page 5: ...same for both Kennebec Lattice and Clean Face versions Figure 2 Minimum Sleeve Adjustment Figure 1 Maximum Sleeve Adjustment Firebox Sleeve Firebox Sleeve Firebox Firebox to Door Opening 2 7 Surround...

Page 6: ...chimney top Some liner manufacturers require insulation in order to achieve a UL 1777 or ULC S635 listing Check with the manufacturer of the liner being used to determine if insulation is required In...

Page 7: ...40 Wide A Front The protection must extend at least 18 inches 457 mm forward from the door opening B Sides Protection must extend 20 inches 508 mm to both sides of the centerline of the insert Note t...

Page 8: ...its There may be no combustible materials located anywhere within 36 914 mm of the front of the door This precaution includes items such as drapes or doors that could swing into the area within 36 of...

Page 9: ...installations where the flue tile is greater than 8 x 12 for internal chimneys or 9 x 8 for external chimneys In Canada The insert must be installed with a continuous chimney liner of 6 152 mm diamete...

Page 10: ...locations in the firebox flue collar Secure the flue connector pipe using three 10 x 1 2 sheet metal screws 4 Adjust the position of the Firebox to ensure that the Surround Panel Hangers are flush wi...

Page 11: ...l If you will be installing the a Mantel Heat Shield use the instructions included with that kit 5 Attach the Assembly to the Firebox Lift the entire assembly upright and position it in front of the i...

Page 12: ...shroud legs 6 Insert the Control Switch and Power Receptacle Use a flat head screwdriver and pliers to pry the knockouts from the appropriate ash lip support Work from the inside to avoid marring the...

Page 13: ...oft brush attachment to clean the blower housing and compartment as well as the area under the insert firebox 8 Attach the Air Deflector Using the two remaining 8 sheet metal screws attach the Air Def...

Page 14: ...too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log which will show little or no check mark...

Page 15: ...Air Control Settings A single lever regulates the Primary Air flow that controls the intensity of the fire and consequent heat output and burn time This lever is located within the slot on the upper...

Page 16: ...o creosote accumulation than an interior flue A chimney flue located within the home interior will benefit from the insulating characteristics of the building itself Consequently the flue system will...

Page 17: ...ontainer of ashes should be placed on a noncombustible floor or on the ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwis...

Page 18: ...lifting it up and tilting it back down and out The chimney can be swept directly into a bucket placed under the flue outlet Gaskets Check door and glass gaskets for seal integrity The gaskets should b...

Page 19: ...rmine overall R value 3 If the overall R value of the system is greater than the R value of the specified floor protector the alternate is acceptable Example The specified floor protector should be 3...

Page 20: ...gure 22 Clearance Diagram No Heat Shielding Figure 23 Mantel Clearances measured from the hearth surface to the lowest mantel surface Mantel Clearance with Optional Heat Shield 155346 Clearance may be...

Page 21: ...14 15 17 21 22 48 47 34 36 41 40 11 42 43 3 49 Kennebec Classic Style Surround Assembly 4 58 62 59 48 45 6 5 52 31 32 45 44 30 63 46 35 18 64 65 61 39 19 2 20 23 24 25 26 16 66 67 27 28 29 40 Figure 2...

Page 22: ...ft Matte Black 10425992 Kenn Surround Leg Left Blue Black 10425927 4 Kenn Surround Leg Right Matte Black 10426092 Kenn Surround Leg Right Blue Black 10426027 5 Kenn Breastplate Left Matte Black 104257...

Page 23: ...er firing can also be identified by warped plates rust colored cast iron paint pigment that has turned dusty white or bubbling cracking and discoloration of the enamel finish Misuse includes without l...

Page 24: ...nce must be installed in conformance with local and national building regulations It is important that these instructions be carefully read and understood before beginning the installation J tul pursu...

Reviews: