background image

www.johnsonsystems.com

6

Power Supply Requirement

The control station requires a regulated DC power supply from 10.6VDC to 18VDC. A 12VDC 

power supply is recommended. The power supply common (V-) connects to the “COM” 

connection on J1 and the power supply positive (V+) connects to the “V+” connection on J1.

Control Station Wiring

CS-DMX Series control stations can be wired for various applications. The control station wiring 

can be configured for the functionality required.
A 6-position breakaway connector (J1) is used to connect the power supply (COM, V+), three 

switches (ON, DIM, RST), as well as the master pot (MP) analog output (not used with CS-DMX 

Series control stations).
The recommended wire for these connections is stranded, #18 AWG copper wire, however 

smaller gauge wire may be suitable for some applications where distances are less than         

150' (50m). The breakaway connector will accept wire sizes from #28 to #12 AWG.
Breakaway connectors are provided for all wiring terminations. For proper termination, the strip 

length should be 0.28" (7mm). A 1/8" (3.2mm) flat head screwdriver should be used to tighten the 

connections and torque to 3.5Lb-In (0.4Nm).

DMX Input and Output Wiring

All CS-DMX Series have a 3-position breakaway connector used to receive DMX in (DMX IN) and 

a 3-position breakaway connector used to transmit DMX out (DMX OUT). The DMX received on 

the DMX in (if applicable) connector is merged with the DMX generated by the control station and 

retransmitted through the DMX out connector. Merged DMX data is highest takes precedence 

(HTP) for equivalent DMX control channels. There is only a 1-packet (28msec) delay in the 

retransmitted DMX from the original DMX received!
For proper termination, the strip length should be 0.28" (7mm). A 1/8" (3.2mm) flat head 

screwdriver should be used to tighten the connections and torque to 3.5Lb-In (0.4Nm). Be sure to 

isolate and protect all shield wires and comply with standard RS-485 termination practices.

•  DMX IN (SHIELD/COMMON, DATA-, DATA+) is terminated on the J1 connector.

•  DMX OUT (SHIELD/COMMON, DATA-, DATA+) is terminated on the J2 connector.

•  Complies with USITT DMX512-A (ANSI E1.11 - 2008), standard protocol for digital data 

control.

•  Recommended cable is Belden 9829, 9842, Cat 5 or equivalent (low-capacitance, twisted pair).

•  Wiring must follow a daisy-chain topology.

•  Maximum of 32 receiving devices on a single DMX line.

•  Maximum cable length is 1,500 feet (455 meters).

•  For more information, Google DMX, or visit: http://www.usitt.org/DMX512FAQ.aspx

NOTE:  For long DMX lines exceeding 1,000 feet (305 meters) the “DMX TERM” jumper (JP1) 

should be in the terminated (upper) position.

NOTE:  Be sure the last DMX receiving device (end-of-line) is terminated with a 100Ω to 120Ω 

resistor.

Summary of Contents for CS-DMX Series

Page 1: ... Calgary Alberta Canada T2G 5M1 tel 403 287 8003 fax 403 287 9003 e mail info johnsonsystems com website www johnsonsystems com User Manual CS DMX Series Programmable Manual DMX Stations JOHNSON SYSTEMS INC www johnsonsystems com ...

Page 2: ... Secondary 3 6 9 or 12 Sliders 5 Control Station Security Feature 5 Power Supply Requirement 6 Control Station Wiring 6 DMX Input and Output Wiring 6 Wiring an Independent Control Station 7 Wiring a Single or Multiple Entrance Control Stations to a Master Control Station 7 Wiring Two or More Master Control Stations Together with Take Control 7 Wiring Two or More Control Stations Together with Mimi...

Page 3: ...tensity allow customization for demanding applications Durable powder coat finish is available in either black or white CS DMX Series Programmable Manual DMX Station Features Manual DMX at your fingertips Six models sizes available including two and three button entrance stations 512 DMX channels of control per station Multiple stations can be daisy chained on the same DMX line Digitally adjustabl...

Page 4: ...g Output DMX Output Range Calibration Jumper JP1 Security Enable Disable Jumper JP2 Factory Only Jumper s DMX Input Connector J1 DMX Output Connector J2 DMX Termination Jumper JP1 ON DIM and OFF Buttons With Integral LED s Master M Slider Infared LED Sensor Secondary 3 6 9 or 12 Sliders CS DMX Series Control Station Diagrams ...

Page 5: ...nnels patched to the sliders The OFF button corresponds with the RST reset connection on J1 and is optionally connected to other control stations for various applications NOTE The control station will still transmit DMX output levels at zero percent 00 in the OFF state Master M Slider The master slider controls the overall maximum DMX output level for the secondary sliders It has similar functiona...

Page 6: ...X in DMX IN and a 3 position breakaway connector used to transmit DMX out DMX OUT The DMX received on the DMX in if applicable connector is merged with the DMX generated by the control station and retransmitted through the DMX out connector Merged DMX data is highest takes precedence HTP for equivalent DMX control channels There is only a 1 packet 28msec delay in the retransmitted DMX from the ori...

Page 7: ...ly installed at an entrance location and used to trigger a master control station into the ON DIM or OFF state The entrance station s and master station mimic each other when a button is pressed Wiring between a single or multiple entrance stations and master station requires 2 conductors for V and common and 3 conductors for the switches ON DIM and RST 1 conductor for each switch function A singl...

Page 8: ...the control station from electrostatic discharge NOTE Ensure the back box mounting hole threads are not damaged Damaged threads on the back box can damage the threads on the mounting screws and cause stripping The back box threads can quickly be cleaned up by running a 6 32 tap through the mounting hole Be sure not to over tighten the mounting screws or this could result in stripping the back box ...

Page 9: ... is counted press the ON button to save the time fade and exit To set the time fade to zero no fading press and hold the ON button for approximately 10 seconds until the ON LED extinguishes Release the ON button and immediately press the ON button again before the ON LED flashes on Set the Button LED Intensity The button LED intensity can be adjusted to a preferred intensity level for various envi...

Page 10: ...ED flashes off for 0 1 seconds every 2 seconds to indicate remote lockout mode is activated Procedure To activate the remote lockout mode press and hold the DIM button for approximately 10 seconds until the DIM LED flashes off for 0 1 seconds To deactivate the remote lockout mode press and hold the DIM button for approximately 10 seconds until the DIM LED flashes off for 0 1 seconds Short Circuit ...

Page 11: ...www johnsonsystems com 11 CS DMX Series Typical Wiring Applications ...

Page 12: ...ang 2 button on off entrance station with adjustable on voltage for stand alone applications 5 x 18 AWG 1 gang 1 80 W x 2 75 H x 2 00 D 4 6cm x 7 0cm x 5 1cm CS SA ENT3B 1 gang 3 button entrance station w on preset and off 6 x 18 AWG 1 gang 1 80 W x 2 75 H x 2 00 D 4 6cm x 7 0cm x 5 1cm CS IPRO Hand held Infrared Station Programmer 2 75 W x 4 95 H x 1 00 D 70cm x 125cm x 25cm Wireless N A N A DMX ...

Reviews: