The following table shows the rated capacity for units with all load points less than 1785 lb (810 kg).
Table 4: Type A model detail
Type A model P/N
Color code
Rated capacity, lb
Rated capacity, kg
YORK P/N
029-25334-002 (433668) Black
Up to 434
Up to 197
029-25334-002
029-25334-003 (433669) Dark green
435–765
198–347
029-25334-003
029-25334-004 (433670) Gray
766–1020
348–463
029-25334-004
029-25334-005 (433871) White
1021–1156
464–524
029-25334-005
029-25334-006 (433872) Gray/red
1157–1785
525–810
029-25334-006
The following table shows the rated capacity for units with any load point above 1518 lb (689 kg).
Table 5: Type B model detail
Type B model P/N
Color code
Rated capacity, lb
Rated capacity, kg
YORK P/N
029-25334-008 (433997) Dark purple
Up to 1148
Up to 521
029-25334-008
029-25334-009 (433998) Dark green
1149–1530
522–694
029-25334-009
029-25334-010 (433999) Gray
1531–2040
695–925
029-25334-010
029-25334-012 (434000) White
2041–2312
926–1049
029-25334-012
029-25334-013 (434001) Gray/red
2313–3570
1050–1619
029-25334-013
Note:
•
All dimensions are in inches in accordance with ANSI Y14.
•
Standard finish for housing is powder coated, for spring is powder coated, and for
hardware is zinc electroplate. For color, see the previous tables.
•
Installation requires a bolting or anchoring mount to support the structure with a
minimum two 5/8 in. diameter bolt or two 1/2 in. diameter concrete anchors.
•
All springs are designed for 50% over-travel.
•
Installation of optional spring isolators
for installation instructions.
•
Isolators with 1 in. deflection must be of the same class for the entire unit. That is, C2Ps
must be used at all locations on a selected unit, or all CPs.
•
Pin 63 is for isolators, X = no isolators only active selection, 1 = 1 in. deflection not active,
N = neoprene not active.
Installation of optional elastomeric isolators
If ordered, elastomeric type isolator assemblies are supplied with the unit. The isolator load rating
can vary based on the location on the chiller. This is due to the weight distribution of the unit and
the isolators must be located as prescribed in the technical data portion of the chiller submittal
package. See Figure 13 for the locations. See Table 7 for isolator details.
Spring isolators are shipped fully assembled and must be positioned in accordance with the
submittal drawings or as otherwise recommended.
1. Set the isolators on the floor, housekeeping pad, or subbase, and ensure that all isolator
centerlines match the equipment mounting holes.
2. VMC Group recommends that the isolator base (A) be installed on a level surface. Shim or
grout as required, leveling all isolator bases to the same elevation. The maximum difference
that can be tolerated is 1/32 in. (0.794 mm).
3. Bolt or anchor all isolators to supporting structure using base slotted holes (B).
4. Remove the top bolt and washer.
5. Place the equipment on top of the isolators, making sure that the mounting holes of the
equipment line up with the isolator threaded hole (C).
YVAM Air-Cooled Centrifugal Liquid Chiller
22