FORM 160.54-O1
ISSUE DATE: 9/10/2014
JOHNSON CONTROLS
58
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Discharge Superheat (Flash Memory Card
version C.MLM.01.02 or later)
Displays the discharge superheat, calculated as (Discharge
Temperature – Condenser Saturation temperature).
High Speed Thrust Bearing
Oil Drain Temperature
Displays the temperature of the oil in the high-speed
thrust bearing drain line. Not applicable to chill-
ers equipped with Flash Memory Card version
C.MLM.01.03 and higher.
High Speed Thrust Bearing
Proximity Differential
Displays the distance between the high-speed thrust
collar and the tip of the Proximity Probe. This mea-
surement takes into account the reference position es-
tablished at the time of compressor manufacture.
High Speed Thrust Solenoid
(LED – Style E-R22 Only)
Indicates whether the solenoid is presently energized.
Vane Motor Switch (LED)
Indicates whether the vanes are completely closed.
Oil Return Solenoid (LED)
Indicates whether the solenoid is presently energized.
Vent Line Solenoid (LED – Style E-R22)
Indicates whether the solenoid is presently energized.
Liquid Line Solenoid (LED – Style E-R22 and
E-R134a J-Compressors)
Indicates whether the solenoid is presently energized.
Pre-rotation Vanes Control Mode
Access Level Required: SERVICE
Indicates whether the vanes are under manual or auto-
matic control.
[Pre-rotation Vanes] Open (LED)
Access Level Required: SERVICE
Indicates whether the vanes are in the process of opening.
[Pre-rotation Vanes] Close (LED)
Access Level Required: SERVICE
Indicates whether the vanes are in the process of closing.
Pre-rotation Vanes Position (Variable Speed
Drive and Hot Gas Option Only)
Access Level Required: SERVICE
This value displays the present position of the Pre-rota-
tion Vanes as a percentage between 0 and 100%.
Full Load Amps
Access Level Required: SERVICE
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Phase A, B, C Current (Solid State Starter
Only)
Access Level Required: SERVICE
Displays the 3-phase motor current values being read
from the Solid State Starter.
Oil Pump Drive Command Frequency
(Variable Speed Oil Pump Only)
The value displays the present frequency at which the
oil pump is being commanded to run.
For fields requiring access level of SER
-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc
-
tions (Form 160.54-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
[Pre-rotation Vanes] Open (Manual)
Access Level Required: SERVICE
This key puts the vane control into manual mode and
sends an OPEN command to the vanes.
[Pre-rotation Vanes] Close (Manual)
Access Level Required: SERVICE
This key puts the vane control into manual mode and
sends a CLOSE
command to the vanes.
[Pre-rotation Vanes] Hold (Manual)
Access Level Required: SERVICE
This key puts the vane control into manual mode and
sends a HOLD command to the vanes.