SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
131
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, following
instructions in
OptiView Control Center – Service In-
structions (Form 160.54-M1)
, establishes this configu-
ration per the desired operation. This screen also serves
as a gateway to more subscreens for defining general
system parameters.
DISPLAY ONLY
031-01730-000 Microboard
Chilled Liquid Pump Operation:
Displays
Standard
or
Enhanced
Motor Type:
Displays
Fixed Speed
or
Variable Speed
Refrigerant Selection:
Displays
R-22
or
R134a
Anti-Recycle:
Displays
Disabled
or
Enabled
Power Failure Restart:
Displays
Manual
or
Automatic
Liquid Type:
Displays
Water
or
Brine
Coastdown:
Displays
Standard
(150 seconds) or
Enhanced
(15
minutes – Steam Turbine applications)
Pre-Run:
Displays
Standard
(50 seconds) or
Extended
(180
seconds)
Oil Pump Package:
Displays
Fixed Speed
or
Variable Speed
Power Line Frequency (VSD only):
Displays
60Hz
or
50Hz
031-02430-000 and 031-02430-001 Microboard
Refrigerant Selection
Displays
R22
or
R134a
Liquid Type
Displays
Water
or
Brine
SETUP SCREEN
LD15426a
FIGURE 44 -
SETUP SCREEN