VRF Air-Conditioner IOM

 

system shall not be more than 15. 

 

The bending radius of curve  shall be larger than 

10cm. 

 

Pinch  off  evaporator  process  pipe  with  pincers 

before  connecting  pipe,  discharge  the  gas  in  the 

evaporator,  and  then  twist  the  evaporator  union 

nut with a spanner. 

 

Coat  a  layer  of  sealing  oil  at  joint  and  horn 

mouth before connecting pipe. 

 

When connecting and dismantling piping to/from 

air  conditioner,  simultaneously  use  an  ordinary 

spanner and a torque spanner. 

 

Figure 9 Piping Connection Diagram 

 

 

For  relevant  tightening  torque,  please  refer  to 

Table 1. 

Table 1 

Pipe diameter 

Tightening torque 

(N.m) 

φ6.35(1/4") 

14.2~17.2 

φ9.53(3/8") 

32.7~39.9 

φ12.7(1/2") 

49.5~60.3 

φ15.88(5/8") 

61.8~75.4 

 

 

Excessive  tightening  may  damage  horn  mouth 

and lead to refrigerant leakage. 

 

Indoor unit inside has gas with a certain pressure, 

so  do  not  directly  loose  nut  to  discharge  gas  in 

order  to  avoid  personnel  injury;  please  do  not 

overexert in order to avoid damaging the flaring. 

 

9.

 

Air Tightness Leakage Detection 

 

Conduct 

air 

tightness 

leakage 

detection 

confirmation at the end of piping work. 

 

Leakage detection method: 

(a)

 

Fill  dry  compressed  nitrogen  into  indoor  unit 

and  piping  system,  and  slowly  boost  the 

pressure to 4.3MPa; 

(b)

 

After  maintaining  pressure  for  10min,  coat 

soapy  water  or  other  foaming  agent  at  the 

connection  position  such  as  weld  and  thread 

joint, and observe whether there is leakage; 

(c)

 

If  any  leakage,  tighten  or  repair  weld  leaking 

position after pressure relief. 

(d)

 

Fill  into  dry  compressed  nitrogen  again  and 

slowly boost the pressure to 4.3MPa; 

(e)

 

Start  to  record  the  reading  of  pressure  gauge 

after  maintaining  pressure  for  6h,  and  then 

record the reading of pressure gauge again after 

24h; 

(f)

 

If  no  pressure  drop,  then  the  air  tightness  is 

qualified.  If  any  pressure  drop,  find  out  the 

leakage  point  and  repair,  and  then  repeat  the 

above d and e procedures until qualified. 

 

 

Pressure  reading  is  related  to  temperature 

variation,  so  the  temperature  variation  factor 

shall  be  considered  when  judging  whether  there 

is  pressure  drop.  The  relation  of  pressure 

correction value and temperature variation is: 





+

+

=

1

273

273

1

2

1

t

t

P

P

 

P

P

P

=

2

correction

 

 

P--Pressure correction value              (bar) 

P

correction

---Corrected pressure value      (bar) 

P

1

---The first pressure reading              (bar) 

P

2

---The second pressure reading          (bar) 

t

1

---Temperature  at  the  first  pressure  reading 

(

)

 

t

2

---Temperature  at  the  second  pressure  reading 

(

)

 

 

In  air  tightness  test,  do  not  connect  indoor  unit 

and outdoor unit, otherwise, nitrogen may leak to 

outdoor unit. 

10.

 

Thermal Insulation 

 

If  no leakage after inspection,  respectively  wrap 

liquid  pipe,  gas  pipe  and  each  connecting 

position 

with 

thick-enough 

heat-resistant 

Caution 

Caution 

Evaporator 
process 
pipe 

Summary of Contents for YORK YDHW022

Page 1: ...VRF Air Conditioner Installation Manual FORM NO YDHW IOM EN 1212 ...

Page 2: ...x890x215 295x890x215 Connecting Pipes Liquid Gas φ mm 6 35 9 52 6 35 9 52 6 35 12 7 Drainage Pipe φ mm 16 O D Model YDHW045 YDHW056 YDHW071 Cooling Capacity kW 4 5 5 6 7 1 Heating Capacity kW 5 6 3 7 15 Power supply 220V 50Hz Rated Power W 50 50 70 Rated Current A 0 25 0 25 0 25 Air Flow Rate m3 h 730 730 1050 External Static Pressure Pa 0 Dimension HxWxD mm 295x890x215 302x1070x220 302x1070x220 C...

Page 3: ...ALLATION POSITION 2 4 MOUNTING PLATE FIXING 2 5 WIRING 2 6 DRAINAGE HOSE INSTALLATION 3 7 INSTALLATION OF INDOOR UNIT 3 8 PIPING CONNECTION 3 9 AIR TIGHTNESS LEAKAGE DETECTION 4 10 THERMAL INSULATION 4 11 DRAINAGE PIPE LAYOUT 5 12 SEALING OF WALL HOLE AND FIXING OF PIPE 5 13 ELECTRIC INSTALLATION 5 ...

Page 4: ...telephone line Poor earthing may lead to electric shock accident Leakage earthing breaker must be installed If leakage earthing breaker is not installed there will be electric shock hazard or fire hazard Please arrange drainage piping according to this instruction to guarantee smooth drainage and insulate the piping in case of condensed water accumulation Improper piping may lead to water leakage ...

Page 5: ...t with outdoor unit 4 Mounting Plate Fixing Level with line pulling method or levelling rod and guarantee the indoor unit slightly inclining to water outlet direction of defrosting tray in installation so as to facilitate to remove the condensed water Fix the mounting plate on the wall with screws Pull the suspension plate with hands after installation to confirm whether it is firm The suspension ...

Page 6: ...6 6 1 Piping trend Cut off 1 part on the indoor unit when the piping comes out from right side Refer to Fig 7 Cut off 2 part on the indoor unit when the piping comes out from left side Refer to Fig 7 Do not overexert when breaking off pipe in order to avoid flat pipe Figure 7 7 Installation of Indoor Unit Let pipeline pass through wall hole and hang the indoor unit on the mounting plate clip the i...

Page 7: ...for 10min coat soapy water or other foaming agent at the connection position such as weld and thread joint and observe whether there is leakage c If any leakage tighten or repair weld leaking position after pressure relief d Fill into dry compressed nitrogen again and slowly boost the pressure to 4 3MPa e Start to record the reading of pressure gauge after maintaining pressure for 6h and then reco...

Page 8: ...wire or fuse exceeding the designated class Only use the accessories designated by the company and require the manufacturer or authorized dealer to provide installation and technical service If accessories are controlled improperly controller failure or electric shock consequence may be caused Control mainboard and transformer shielding layer must be installed with earthing wire Do not connect ear...

Page 9: ... in electric schematic diagram on electric control box Recommended specification and model for power supply is RVV2x2 5 1x1 5 13 3 Communication wire connection Figure 14 The recommended model for communication wire is RVSP2X0 75 shield 2 core Connect according to the diagram do not allow A and B polarity connection error if not communication failure or controller damage may be caused In order to ...

Page 10: ...7 YDHW IOM EN 1212 NONE YDHW IOM 0812 ...

Reviews: