Johnson Controls YORK YCAS0098-0208 Start-Up Checklist Download Page 5

FORM 201.19-CL1 (309)

JOHNSON CONTROLS 

5

SYStEm StARt-UP CHECk LISt

JOB nAmE: ______________________________ 
SALES ORDER #: _________________________
LOCAtIOn: _______________________________
SOLD BY:  ________________________________
InStALLIng

COntRACtOR: ___________________________
StARt-UP 

tECHnICIAn/ 

COmPAnY: _______________________________
StARt-UP DAtE :  _________________________

CHILLER mODEL #: _______________________
SERIAL #: ______________________________

__

COmPRESSOR #1 
mODEL#: ________________________________
 SERIAL #: _______________________________

 COmPRESSOR #2 
mODEL#: ________________________________
 SERIAL #:  _______________________________

UnIt CHECkS (nO POwER)

Check the system 24 hours prior to initial start.

  1.  Inspect  the  unit  for  shipping  or  installation  

damage.

  2.  Assure that all piping has been completed.

  3.  Check that the unit is properly charged and that 

there are no piping leaks.

  4.  Open  each  compressor  suction  service 

valve,   discharge  service  valve,  economizer 

service   valve, liquid line stop valve, and oil 

line ball valves.

  5.  The compressor oil level should be maintained  

so that an oil level is visible in either of the two 

oil separator sight glasses. In other words, oil  

level should always be maintained, running or  

not, above the bottom of the lower sight glass 

and below the top of the upper sight glass.

 

 

If it is necessary to add oil, connect a YORK oil 

pump to the charging valve on the oil separator, 

but do not tighten the flare nut on the delivery 

tubing. With  the  bottom  (suction  end)  of  the 

pump submerged in oil to avoid entrance of air, 

operate the pump until oil drips from the flare nut 

joint, allowing the air to be expelled, and tighten 

the flare nut. Open the oil charging valve on the 

oil separator and pump in oil until it reaches the 

proper level as described above.

In actual operation, due to splashing, 

an oil level may be seen in both sight 

glasses. Run the compressor for a few 

minutes fully loaded, shut the system 

down, and assure there is an oil level 

showing  in  the  bottom  or  top  sight 

glass with the compressor “OFF”.

  6.  Assure water pumps are on. Check and adjust 

water pump flow rate and pressure drop across 

the evaporator.

Excessive flow may cause catastrophic 

damage to the evaporator.

  7.  Check the control panel to assure it is free of 

foreign material (wires, metal chips, etc.).

  8.  Visually  inspect  wiring  (power  and  control). 

Wiring MUST meet N.E.C. and local codes. 

  9.  Check tightness of power wiring inside the power 

panel on both sides of the motor contactors and 

inside the motor terminal boxes.

  10. Check for proper size fuses in main and control 

circuits.

  11.Verify  that  field  wiring  matches  the  3‑phase  

power  requirements  of  the  compressor.  See 

chiller nameplate.

 

12. Assure 115VAC Control Power has 30A mini-

mum capacity. 

 

13. Be certain all water temp sensors are inserted 

completely  in  their  respective  wells  and  are 

coated with heat conductive compound.

  14.Assure that evaporator EEV bulbs are strapped 

onto the suction lines at 4 or 8 o’clock posi-

tions. 

  15. Assure  that  the  15  ton  economizer  TXV 

bulbs   are  strapped  onto  the  compressor 

economizer supply lines at 4 or 8 o’clock posi-

tions.

Summary of Contents for YORK YCAS0098-0208

Page 1: ...rating charge Reference the Technical Data Section in the IOM Valves Open each compressor suction economizer and dis charge valve fully counter clockwise then close one turn of the stem to ensure operating pressure is fed to the pressure transducers Open the liquid line service valve fully and ensure the oil return line ball valve is open in each system Compressor Oil To add oil to a circuit conne...

Page 2: ... above 96 F 36 C the compressor heaters must be on for at least 8 hours before start up to ensure all refrigerant liquid is driven out of the compressor If the ambient temperature is below 86 F 30 C then allow 24 hours Water System Verify that the chilled liquid system has been installed correctly and has been commissioned with the correct direction of water flow through the evaporator The inlet s...

Page 3: ...position Start up Remove the locking device from the unit Auto OFF switch which prevents unauthorized starting of the unit before commissioning Press the Status key then turn the unit switch to the 1 position to start the unit there may be a few seconds delay before the first compressor starts because of the anti recycle timer Be ready when each compressor starts to switch the unit OFF immedi atel...

Page 4: ...line temperature on the copper line beside the main liquid line service valve Measure liquid pressure at the liquid line service valve Sub cooling should be 12 F to 15 F 6 7 C to 8 3 C No bubbles should show in the sight glass If subcooling is out of range add or remove refrigerant as required Do not overcharge the unit The liquid flow to the main evaporator TXV is subcooled further by the economi...

Page 5: ...delivery tubing With the bottom suction end of the pump submerged in oil to avoid entrance of air operate the pump until oil drips from the flare nut joint allowing the air to be expelled and tighten the flare nut Open the oil charging valve on the oil separator and pump in oil until it reaches the proper level as described above In actual operation due to splashing an oil level may be seen in bot...

Page 6: ...lve electronic should always be selected when an EEV is installed Verify the selections by pressing the OPTIONS Key on the control panel Check them off in the chart above Damage to the chiller could result if switches are improperly pro grammed 5 Program the required operating values into the micro for cut outs safeties etc and record them in the chart below Record programmed values in the chart b...

Page 7: ...scharge condensing pressure can be found in the refriger ant temperature pressure chart use entering air temperature 30 F 17 C for normal condens ing temperature b The temperature of the liquid refrigerant out of the condenser should be not be more than 15 F 8 C less than the condensing temperature The temperature corresponding to the condensing pressure from the refrigerant temperature pres sure ...

Page 8: ...on superheat should be checked The superheat should be checked only after steady state operation of the chiller has been established the leaving water temperature has been pulled down to the required leaving water temperature and the unit is running in a fully loaded condition Correct superheat setting for a system is 10 12 F 6 7 C The superheat is calculated as the difference between the actual t...

Page 9: ...mately 15 minutes between adjustments for the system and the thermal expansion valve to respond and settle out Assure that superheat is set between 10 12 F 6 7 C 1 Record the motor gas temperature economizer pressure economizer pressure converted to temperature and economizer superheat below SYS 1 SYS 2 Economizer Press PSIG kPa Economizer Temp F C Economizer Press Converted to Temp F C Superheat ...

Reviews: