Johnson Controls WT-4002-MCM Installation Instructions Manual Download Page 8

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions

8

Received Signal Strength Indicator

Indicates the relative strength of the wireless signal 
between the room thermostat and the device it is 
communicating with.

a.

-39 and higher

: A strong and solid wireless 

connection exists; no further analysis is 
required.

b.

-44 to -40

: The wireless signal is getting 

through; however, the room thermostat should 
be monitored. If the signal strength 
deteriorates further, there is a risk of data loss. 
Consider adding a WT-ROUTER Router 
between the devices to strengthen the signal.

c.

-45 and lower, or --- 

: The room thermostat 

has a very weak wireless connection or it is 
failing to connect to other devices on the 
network, resulting in the loss of a significant 
number of data packets. The room thermostat 
may be located too far from the other devices 
or there may be wireless interference in the 
area. To strengthen the wireless signal, add a 
WT-ROUTER Router between the problematic 
devices on the network to create an additional 
connection point.

Room Temperature or Requested Setpoint

Indicates the current room temperature. Pressing the 
Up/Down buttons once shows the locally-defined 
setpoint temperature.

Adjusting the Room Setpoint Temperature

The WT-4000 Series Room Thermostat operates in 
conjunction with the preset building configuration 
parameters; therefore, the room setpoint temperature 
can only be changed within predefined Comfort Zone 
limits.

1.

Confirm that the room thermostat is in the 
scheduled Occupied Mode; the top of the LCD 
must read 

Occupied

.

2.

The temperature reading on the LCD displays the 
current room temperature. To increase or decrease 
the room setpoint temperature, press the Up/Down 
buttons to select the desired setpoint.

a.

When the Up/Down buttons are pressed once, 
the LCD shows the user-defined room setpoint 
value and the LCD reads 

Setpoint

.

Note:

When the room temperature and the setpoint 

value are the same, the HVAC equipment is off.

b.

If neither the Up or Down button is pressed 
again, the LCD returns to the main screen 
within 5 seconds.

c.

When the setpoint is displayed, keep pressing 
the Up/Down buttons to reach the desired 
room setpoint temperature.

d.

If the Up/Down buttons are pressed and the 
setpoint stops increasing or decreasing, 
predefined Comfort Zone limits have been 
reached. If the setpoint does not change, the 
local controls are disabled.

Note:

Contact the building administrator if the room 

temperature minimum or maximum allowable settings 
are not comfortable.

e.

The room thermostat decides to heat or cool 
based on the current room temperature and 
the specified setpoint.

3.

When the desired setpoint is specified, the LCD 
returns to the main screen within 5 seconds.

4.

If the LCD reads 

Unoccupied

, the room 

thermostat is scheduled to be in the Unoccupied 
Mode. If the area requires heating or cooling while 
the room thermostat is in the Unoccupied Mode, 

press the Override button 

 to change the 

room thermostat to the Override Mode. See 

Using 

the Override Mode Button

 that follows.

Using the Override Mode Button

If the LCD reads 

Unoccupied

, the room thermostat is 

scheduled to be in the Unoccupied Mode and the local 
room thermostat controls are disabled. If the area 
requires heating or cooling:

1.

Press the Override button 

 to change the 

room thermostat to the Override Mode.

2.

The room thermostat stays in the Override Mode, 
as defined by the configuration parameters (default 
2 hours). The room setpoint temperature can be 
adjusted within predefined Comfort Zone limits for 
the duration of the Override Mode period.

3.

See Step 2 in the 

Adjusting the Room Setpoint 

Temperature

 section to change the room setpoint 

temperature.

4.

Once the Override Mode period expires, the room 
thermostat returns to its originally scheduled mode. 
If the heating or cooling period needs to be 

extended, press the Override button 

 again 

and follow Step 2 in the 

Adjusting the Room 

Setpoint Temperature

 section.

Summary of Contents for WT-4002-MCM

Page 1: ...nergy savings in high energy usage environments such as schools dormitories offices and hospitals by adjusting the temperature of the space based on the occupancy status All WT 4000 Series Room Thermo...

Page 2: ...e should be at least two routers or one router and one gateway located within a 200 ft 61 m radius of every room thermostat In order for the devices to connect to the same mesh network they all must h...

Page 3: ...reless network before installation by identifying room thermostat locations To document the location of where each wireless device is installed Mounting Procedure Mount the WT 4000 Series Room Thermos...

Page 4: ...ialization 7 Check the wireless connectivity at the intended room thermostat installation location It may take approximately 30 seconds for the room thermostat to initialize a Look at the wireless con...

Page 5: ...the following An air dryer that is operating properly A coalescing air filter that is replaced and maintained properly In line air filters before each room thermostat where necessary Order of Installa...

Page 6: ...ers Manual Override Occupied Mode Light Button Lights the Display for 10 Seconds Up Button Increases the Room Temperature Setpoint Down Button Decreases the Room Temperature Setpoint LCD See Figure 4...

Page 7: ...onnected to the WT BAC IP Gateway b 1 One connection exists c 2 Two or more connections exist and the room thermostat is operating properly Battery Voltage Level a The battery is fully charged b The b...

Page 8: ...LCD reads Setpoint Note When the room temperature and the setpoint value are the same the HVAC equipment is off b If neither the Up or Down button is pressed again the LCD returns to the main screen...

Page 9: ...late from the room thermostat 2 Install the four 3 6 V lithium batteries included with the room thermostat into the battery compartment Be sure to match the positive battery ends with the positive bat...

Page 10: ...the Up Down buttons to select the Maintenance option Figure 8 2 Press to confirm the selection 3 Press the Up Down buttons to select the Dir Acting SP Psi Gain Prop Bnd or Unoc Psi option Figure 9 4 P...

Page 11: ...oportional band proportional range throttling range The valid range is 0 to 10F 0 to 6C adjustable in increments of 1F 0 6C The default setting is 6F 3 6C b Press the Down button to decrease the propo...

Page 12: ...255 1 111 111 DI to change the unique thermostat device ID Two fields separated by a period first field is 1 through 159 and second field is 1 through 246 1 71 40 Pneumatic Direction Direct acting br...

Page 13: ...ust the operation of HVAC equipment manually outside of the schedule but within set energy policy parameters The WT 4000 Series Room Thermostats are designed to support any 0 to 22 psig 0 to 152 kPa p...

Page 14: ...remote monitoring adjustment and trending to provide longer and more dependable and maintenance free operation Note For each room thermostat in the wireless mesh network only one object can be writte...

Page 15: ...o the occupancy schedule A complete 7 day schedule consists of two independent components Weekday Schedule Monday through Friday Weekend Schedule Saturday through Sunday Each component is split into t...

Page 16: ...part is being edited Occupied or Unoccupied Defines the occupancy mode of the part Time in 24 Hour Format Defines the start time of the part FIG occpd_mde Figure 18 WT 4000 Series Pneumatic to DDC Ro...

Page 17: ...right corner of the LCD indicating stand alone operation Stand Alone Room Thermostat Configuration To set the time and program the stand alone room thermostat occupancy schedule and temperature setpo...

Page 18: ...use the Up Down buttons to navigate to Weekday to program the weekday schedule 10 Press to open the weekday schedule 11 Set the Weekday 1 schedule Figure 25 which is usually the start of the Occupied...

Page 19: ...cy mode start time upper temperature limit and lower temperature limit menu items f Press to open a specific menu item g Press the Up button or the Down button to change the value then press to save t...

Page 20: ...pied from 3 P M to 6 A M Monday through Sunday Program the WT 4000 Series Room Thermostat schedule setup screen as illustrated in Figure 29 Weekend 1 Unoccupied 09 00 85 55 Weekend 2 Unoccupied 17 00...

Page 21: ...tat allows users to adjust the room temperature using the local room thermostat as long as the desired room temperature is within the range of the Comfort Zone If the user requests heating or cooling...

Page 22: ...ning a 5 day 8 A M to 6 P M occupancy schedule but one day the occupants are leaving at 2 P M the zone can be manually set into Shoulder Mode at 2 P M The room thermostat remains in Shoulder Mode unti...

Page 23: ...its Configuration tool Override Mode Override duration default 120 minutes Room thermostat override duration 240 minute maximum duration after time limit expires room thermostat goes into regularly sc...

Page 24: ...wer delta Defines lower temperature limit in Shoulder Mode Configuration tool Direction Direct acting branch line pressure increase turns on cooling decrease turns on heating Reverse acting branch lin...

Page 25: ...F maximum 14 F AV 31 Shoulder_Up_D Upper delta default 5 F In shoulder mode the device does not call for cool if space temperature is below setpoint plus upper delta AV Shoulder_Lo_D Lower delta defa...

Page 26: ...ne pressure of the system at that time in PSI AI 79 Temp_Unit The unit of temperature 0 represents F and 1 represents C The default is F Any change to this value reboots the device AV MS_Grace The gra...

Page 27: ...Display LCD indicates room temperature branch line pressure temperature setpoint occupied setback mode battery voltage and wireless connection status supports temperature setpoint adjustment network c...

Page 28: ...he marks of their respective owners 2017 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 28 European Single Point of Contact NA SA Single Point of Contact APA...

Reviews: