Table 8: VRF BACnet Points for Outdoor Units
Contents of Information
Object Type
Object Description
Object Name
BACnet
Instance
Number
–
Run
Stop
Status
BI
Inverter Status
INV-S
29
–
Run
Stop
Status
BI
Fan Status
FAN-S
30
The following table lists the ODU custom enum values for SYSTEM-MODE.
Table 9: ODU System Mode
Metasys Enum String
Metasys Enum Value
Heat
1
Cool
2
Auto
3
The following table lists the ODU custom enum values for SYSTEM-S.
Table 10: ODU System Status
Metasys Enum String
Metasys Enum Value
Thermo off
1
Pump down
2
SW on start
3
Thermo on start
4
After defrost
5
Start control 1
6
Start control 2
7
Normal
8
Oil return
9
Defrost ready 1
10
Defrost ready 2
11
Differential pressure control
12
Defrost
13
The following table lists the ODU custom enum values for HX-STATE.
Table 11: ODU Heat Exchanger Status
Metasys Enum String
Metasys Enum Value
Evaporator Mode Low Pressure
1
Condenser Mode High Pressure
2
Evaporator Mode
3
Condenser Mode
4
The following table lists the ODU custom enum values for INV-STATE and FAN-STATE.
Table 12: ODU Inverter and Fan Status
Metasys Enum String
Metasys Enum Value
Normal stop
1
Fault
2