Table 2: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal block label

Terminal labels Function, ratings, and requirements

To determine wire size and maximum

cable length

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
External 1k to 50k ohm load required

See Guideline A in Table 3.

OUT

n

Binary Output 24 VAC Triac

Connects OUT to OCOM when activated.
External Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current

See Guideline C in Table 3.

Analog Output Signal Common

: All

Configurable Outputs defined as Analog

Outputs share a common, which is isolated

from all other commons except the Binary

Input common.

CONFIGURABLE

(Outputs)

OCOM

n

Binary Output Signal Common

: All

Configurable Outputs defined as Binary

Outputs are isolated from all other commons,

including other Configurable Output

commons.

Same as (Configurable) 

OUT

n

.

Table 3: Cable Length Guidelines for Recommended Wire Sizes

Guideline

Wire Size/Gauge and Type

Maximum Cable Length and

Type

Assumptions

1.0 mm (18 AWG) stranded copper

457 m (1,500 ft) twisted wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

183 m (600 ft) twisted wire

A

0.5mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

107 m (350 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable length

and the connected input or

output device, you may have

to define an offset in the setup

software for the input or output

point.

1.0 mm (18 AWG) stranded copper

229 m (750 ft) twisted wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

91 m (300 ft) twisted wire

B

0.5 mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

61 m (200 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable length

and the connected input or

output device, you may have

to define an offset in the setup

software for the input or output

point.

C

See Figure  to select wire size/gauge.
Use stranded copper wire.

See Figure  to determine cable

length.
Use twisted wire cable.

N/A

Maximum cable length versus load
current

Use Figure 8 to estimate the maximum cable length

relative to the wire size and the load current (in mA)

when wiring inputs and outputs.

VMA1615/1626/1628/1630 VAV Controllers Installation Guide

10

Summary of Contents for VMA1615

Page 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Page 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Page 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Page 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Page 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Page 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Page 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Page 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Page 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Page 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Page 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Page 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Page 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Page 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Page 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Page 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Page 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Page 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Page 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Page 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Page 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Page 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...

Reviews: