Wiring

 CAUTION

Risk of Electric Shock

Disconnect the power supply before making electrical

connections to avoid electric shock.

 ATTENTION

Risque de décharge électrique

Débrancher l'alimentation avant de réaliser tout rac-

cordement électrique afin d'éviter tout risque de

décharge électrique.

Important: 

Do not connect supply power

to the controller before finishing wiring and

checking all wiring connections. Short circuits

or improperly connected wires can result

in damage to the controller and void any

warranty.

Important: 

Do not exceed the controller

electrical ratings. Exceeding controller electrical

ratings can result in permanent damage to the

controller and void any warranty.

Important: 

Use copper conductors only. Make

all wiring in accordance with local, national, and

regional regulations.

Important: 

Electrostatic discharge can

damage controller components. Use proper

electrostatic discharge precautions during

installation, setup, and servicing to avoid

damaging the controller.

For information on configuring and wiring

a BACnet/IP network, refer to the 

Metasys IP

Networks for BACnet/IP Controllers Configuration

Guide (LIT-12012458).

 For detailed information on

configuring and wiring a SA Bus, refer to the 

MS/TP

Communications Bus Technical Bulletin (LIT-12011034).

VMA terminals and bus ports

See  for input and output terminal and bus port

locations on the controllers. Observe the following

guidelines when wiring a VMA controller.

Input and Output terminals

The input spade terminals are located on the

bottom of the VMA near the FC Bus terminal block.

The output spade terminals are located on the top

of the controller near the power supply . For more

information, see Table .

FC bus terminal block (Or N2 protocol as

required)

The FC Bus terminal block is a blue, removable, 4-

terminal plug that fits into a board-mounted jack.
Wire the removable FC Bus terminal block plugs

on the VMA and other controllers in a daisy-chain

configuration using 3-wire twisted, shielded cable

as shown in Figure 3. See 

Communication bus and

supply power table

 for more information.

Figure 3: FC bus terminal block wiring

Note: 

 The Shield terminal (SHLD) on the FC

Bus terminal block is isolated and can be used

to connect the cable shields on the bus (Figure

3).

SA Bus terminal block

The SA Bus terminal block is a brown, removable,

4-terminal plug with +15 VDC that fits into a board-

mounted jack. Wire the removable SA Bus terminal

block plugs on the VMA and other SA Bus devices

in a daisy-chain configuration using 4-wire twisted,

shielded cable as shown in Figure 4. See Table  for

more information.

VMA1615/1626/1628/1630 VAV Controllers Installation Guide

6

Summary of Contents for VMA1615

Page 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Page 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Page 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Page 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Page 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Page 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Page 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Page 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Page 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Page 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Page 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Page 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Page 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Page 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Page 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Page 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Page 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Page 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Page 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Page 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Page 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Page 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...

Reviews: