SECTION 1 - INSTALLATION

FORM 145.13-NO1 

ISSUE DATE: 10/06/2016

1

Supply Fan VFD Sequence for 208/230-460 VAC units 

(Discrete 2 Speed Fan Control):

Speed 1

• 

Supply fan only
OR

• 

Supply fan and compressor #1 running

• 

Factory set at 35 Hz (do not set lower than 35 Hz)

• 

Set at parameter 1202

• 

24 VDC applied to terminal 12 of VFD

Speed 2

• 

Supply fan and compressors #1 and #2 are running

• 

Factory set at 60hz

• 

Set at parameter 1204

• 

24 VDC applied to terminal 12 and 13 of VFD

Supply Fan VFD Sequence for 575 VAC units (only 

Discrete 2 Speed Fan Control is used):

Speed 1

• 

Supply fan only
OR

• 

Supply fan and compressor #1 running

• 

Factory set at 35 Hz (do not set lower than 35 Hz)

• 

Set at parameter 1202

• 

24 VDC applied to terminal 4 of VFD

Speed 2

• 

Supply fan and compressors #1 and #2 are running

• 

Factory set at 60hz

• 

Set at parameter 1204

• 

24 VDC applied to terminal 4 and 6 of VFD

VFD KEYPAD

VFD requires a keypad to program the VFD. Once the 

VFD is programmed, the keypad is not required in or-

der to operate the unit. Each unit comes with factory 

installed and programmed remote keypad and short 

Ethernet clip-on connector. An Ethernet communica-

tion cable is not factory supplied. A single keypad can 

be used to program multiple units. If needed, consult 

with local Johnson Controls sales office to order ad-

ditional keypads.

LD20860

FIGURE 3 - 

VFD KEYPAD

  

 LD20861  LD20862

FIGURE 4 - 

VFD KEYPAD AND ETHERNET 

CONNECTOR

INSTALLATION

Install a field supplied 1/4-inch push-on tube to the 

return air side of the unit. Pass the tube through the 

opening on the side of the corner post adjacent to the 

VFD controls, and connect to the negative (LOW) side 

fitting.  
Install a field supplied Pitot tube in the supply duct as 

required, run 1/4-inch push-on tube to the corner post 

opening, and connect to the positive (HIGH) side fit-

ting.

Summary of Contents for VFD-2DS-234HE-2

Page 1: ...E FOR D SERIES DSV DSH AIR COOLED SELF CONTAINED UNITS B STYLE AND C SERIES CSV WATER COOLED SELF CONTAINED UNITS B STYLE Issue Date October 6 2016 INDOOR PACKAGED EQUIPMENT INSTALLATION OPERATION NEW...

Page 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Page 3: ...controls com It is the responsibility of rigging lifting and operating service personnel to verify the applicability of these documents to the equipment If there is any question regarding the applicab...

Page 4: ...tor 236HE 3 0 HP Motor 237HE 5 0 HP Motor 238HE 7 5 HP Motor 239HE 10 0 HP Motor 1 2 3 4 5 6 7 8 9 10 11 12 13 VFD PTD 234HE 2 A Product Category VFD VFD Program Parameter Set VFD Option PTD VAV with...

Page 5: ...ntrol 8 FIGURE 3 VFD Keypad 9 FIGURE 4 VFD Keypad and Ethernet Connector 9 FIGURE 5 Connecting Negative and Positive Side Fittings 10 FIGURE 6 VFD Grille Cover 10 FIGURE 7 Input Output Diagram 11 FIGU...

Page 6: ...JOHNSON CONTROLS 6 FORM 145 13 NO1 ISSUE DATE 10 06 2016 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 7: ...ided and routed from condenser to evaporator SECTION 1 INSTALLATION DO NOT enter Setup mode when power ing on the VFD There are two main VFD options Differ ential Pressure Transducer and Discrete 2 Sp...

Page 8: ...fitting Only on 208 230 460 VAC units not on 575 VAC Parameters 4009 and 4011 are factory set at 0 5 WC These are field adjusted points that need to be adjusted at start up These setpoints are based...

Page 9: ...60hz Set at parameter 1204 24 VDC applied to terminal 4 and 6 of VFD VFD KEYPAD VFD requires a keypad to program the VFD Once the VFD is programmed the keypad is not required in or der to operate the...

Page 10: ...sure the tubes are secure inside duct and firmly con nected to transducer fitting otherwise unit will not op erate as intended INSTALL GRILLE COVER When unit is wired and push on tubing has been con n...

Page 11: ...ner the setpoint value is displayed It goes from 0 to 100 That is the actual setpoint for the controller Setpoint can be 0 which is 0 0 WC or 100 which is 2 5 WC Example 20 corresponds to 0 5 WC setpo...

Page 12: ...K SELECT 1 ACT1 4016 ACT1 INPUT 1 AI1 4018 ACT1 MIN 20 4019 ACT1 MAX 100 Table 2 FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208 230 460 VAC ABB ACS320 PARAMETER DESCRIPTION VALUE GROUP 99 9901 LANGUAG...

Page 13: ...T SPEED 2 35 See Note 1204 CONSTANT SPEED 3 0 1205 CONSTANT SPEED 4 60 NOTE If only one speed fan operation is wanted adjust to 60 Table 4 DRIVE DEPENDENT PARAMETERS GROUP 99 VFD PROGRAM PART AJAX MOT...

Page 14: ...A1 6 575 3 60 2 30 VFD 2DS 236HE 2 MTR 236HE EM3211T ACS320 03U 10A8 2 208 230 3 60 3 00 8 50 1765 VFD 2DS 236HE 4 ACS320 03U 05A6 4 460 3 60 4 20 VFD 2DS 236HE 5 MTR 536HE EM3211T 5 ACS250 03U 04A1 6...

Page 15: ...NO1 ISSUE DATE 10 06 2016 3 LD20867 Figure 9 EVAPORATOR VFD OPTION FOR DUCT STATIC PRESSURE WIRING SCHEMATIC 208 230V 460V 3PH 60HZ LD20868 Figure 10 EVAPORATOR VFD OPTION FOR DISCRETE 2 SPEED WIRING...

Page 16: ...sylvania USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2016 www johnsoncontrols com ALL RIGHTS RESERVED Form 145 13 NO1 1016 Issue Date Octo...

Reviews: