14-88360-03206, Rev. A
VG1600 Valve Series Technical Specifications
Total operation angle
270°
Sequence 1
0...>90°
Dead band
>90…<180°
Sequence 2
>180…270°
Characteristic curve
Linear
ID
10,5 mm
Fluid type
Water, glycol solutions (max 50%) for HVAC applications
Fluid temperature
5 to 95 °C (41 to 203 °F)
Nominal pressure
PN16 (232 psi)
Close off pressure
350 kPa (50 psi)
Max. differential pressure
240 kPa (35 psi)
Range ability
100:1
Max. Cv (Kv)
3.3 (3.8) - ½’’ pipe size
Connections
• Valve Body with Male BSPP Thread (external)
• Valve Body with Female NPT Thread (internal
• Sweat Union Fitting kit
Flow coefficient
Flow control disk
Leakage rate
A, 100,000 cycles in iron-oxide contaminated water and air-bubble-tight (EN 12266-1)
Water quality
Iron-oxide contaminated water (900ppm)
Maintenance
Maintenance Free
Warranty
Minimum 5 years to our customer
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from
misapplication or misuse of its products.