VA9208-GGx-x Series Proportional Electric Spring Return Valve Actuators Installation Instructions 

9

4.

The actuator requires 8-1/2 manual override crank 
rotations from the full spring return position to fully 
reposition the actuator hub. At the end of travel, the 
rotation resistance increases. Do not force the 
manual crank past this point.

5.

While holding the manual crank in the wound 
position, rotate and hold the red lock shaft 
approximately 10° then release the manual crank 
to lock the actuator hub in place.

Note:

Insert and slightly rotate the manual crank 

in the direction indicated by the arrow on the label 
to unlock the actuator hub. Alternately, the actuator 
hub automatically unlocks when power is applied 
to the actuator, and returns the actuator to normal 
drive and spring return operation.

Wiring

   

  

    

!

WARNING: Risk of Electric Shock.

Disconnect or isolate all power supplies 
before making electrical connections. 
More than one disconnection or isolation 
may be required to completely 
de-energize equipment. Contact with 
components carrying hazardous voltage 
can cause electric shock and may result 
in severe personal injury or death.

AVERTISSEMENT : Risque de 
décharge électrique.

Débrancher ou isoler toute alimentation 
avant de réaliser un raccordement 
électrique. Plusieurs isolations et 
débranchements sont peut-être 
nécessaires pour -couper entièrement 
l'alimentation de l'équipement. Tout 
contact avec des composants porteurs 
de tensions dangereuses risque 
d'entraîner une décharge électrique et de 
provoquer des blessures graves, voire 
mortelles.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement.

!

CAUTION: Risk of Property Damage.

Insulate and secure each unused wire 
lead before applying power to the 
actuator. Failure to insulate and secure 
each unused wire lead may result in 
property damage.

MISE EN GARDE : Risque de dégâts 
matériels.

Isoler et protéger chaque fil non utilisé 
avant de mettre l'actuator sous tension. 
Le non-respect de cette obligation 
d'isolation et de protection de chaque fil 
non utilisé risque d'entraîner des dégâts 
matériels.

IMPORTANT:

Make all wiring connections in 

accordance with the National Electrical Code and 
local regulations. Use proper Electrostatic Discharge 
(ESD) precautions during installation and servicing 
to avoid damaging the electronic circuits of the 
actuator.

Summary of Contents for VA9208-GG Series

Page 1: ...Electric Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to th...

Page 2: ...fy acceptance of exposed plastic materials in plenum areas with the local building authority Building codes for plenum requirements vary by location Some local building authorities accept compliance t...

Page 3: ...N32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 1 4 184 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 7 16 189 4 21 64 110 11 32 9 2 11 64 55 2 DN50 2 Way 5 17 32 140 1 15...

Page 4: ...s be connected to the coil Figure 3 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32...

Page 5: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Page 6: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 2 Mount optional M9000 561 Thermal Barrier to...

Page 7: ...0 to 24 lb in 2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 7 Install the actuator on the ball valve Tighten the a...

Page 8: ...instructions Follow the same steps as mounting directly to the valve when mounting the actuator to the thermal barrier Manual Override Use only the supplied manual override crank to reposition the ac...

Page 9: ...rdement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereus...

Page 10: ...de to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed M...

Page 11: ...s the full rotation range of 0 to 100 rotation For example if a DC 0 to 10 V input signal is selected and the rotation range is limited to 75 the rotation range limit will be reached at DC 8 3 V Contr...

Page 12: ...faults to 0 10 V input signal range DA Auxiliary Switch VA9208 xxC 3 Models The VA9208 xxC 3 models include two integral auxiliary switches with a switch adjuster accessible on either face of the actu...

Page 13: ...ator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are availabl...

Page 14: ...beled A is Away from Valve CCW Spring Return Actuator Face Labeled B is Away from Valve CW Spring Return Rated Torque Power On Running 70 lb in 8 N m All Operating Temperatures Power Off Spring Return...

Page 15: ...UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric Actu...

Reviews: