VA9208-GGx-x Series Proportional Electric Spring Return Valve Actuators Installation Instructions

8

Mounting the Thermal Barrier

Figure 16 shows the optional M9000-561 Thermal 
Barrier.

To mount the optional thermal barrier:

1.

Install the thermal barrier drive shaft into the 
thermal barrier by aligning the tab on the drive 
shaft with the slot on the thermal barrier 
(Figure 17). 

2.

Rotate the drive shaft to align marks on the top of 
the thermal drive shaft with matching marks on the 
valve stem.

3.

Mount the thermal barrier onto the valve using the 
four included M5x16 mm machine screws and four 
M5 flange nuts. Tighten the screws to a 
recommended torque of 21 to 25 lb·in. 
(2.4 to 2.8 N·m).(Figure 18).  

4.

Proceed to actuator mounting instructions. Follow 
the same steps as mounting directly to the valve 
when mounting the actuator to the thermal barrier.

Manual Override

Use only the supplied manual override crank to 
reposition the actuator hub when using the manual 
override feature.

To reposition the actuator hub, proceed as follows:

1.

De-energize the actuator.

2.

Insert the hex end of the manual override crank 
into the manual override adjustment point on the 
face of the actuator.

3.

Rotate the manual override crank in the direction 
indicated by the arrow on the label. 

Figure 16:  Optional M9000-561 Thermal Barrier

Barrier

Drive
Shaft

Machine Screws

Flange

Nuts

Figure 17:  Installing the Drive 

Shaft into the Thermal Barrier

IMPORTANT:

Applying excessive torque to the 

manual override or operating the manual override 
with a power tool may damage the internal 
components of the actuator and cause premature 
failure.

Figure 18:  Installing the Barrier

F

IG

:i

n

_

a

ct

Summary of Contents for VA9208-GG Series

Page 1: ...Electric Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to th...

Page 2: ...fy acceptance of exposed plastic materials in plenum areas with the local building authority Building codes for plenum requirements vary by location Some local building authorities accept compliance t...

Page 3: ...N32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 1 4 184 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 7 16 189 4 21 64 110 11 32 9 2 11 64 55 2 DN50 2 Way 5 17 32 140 1 15...

Page 4: ...s be connected to the coil Figure 3 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32...

Page 5: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Page 6: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 2 Mount optional M9000 561 Thermal Barrier to...

Page 7: ...0 to 24 lb in 2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 7 Install the actuator on the ball valve Tighten the a...

Page 8: ...instructions Follow the same steps as mounting directly to the valve when mounting the actuator to the thermal barrier Manual Override Use only the supplied manual override crank to reposition the ac...

Page 9: ...rdement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereus...

Page 10: ...de to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed M...

Page 11: ...s the full rotation range of 0 to 100 rotation For example if a DC 0 to 10 V input signal is selected and the rotation range is limited to 75 the rotation range limit will be reached at DC 8 3 V Contr...

Page 12: ...faults to 0 10 V input signal range DA Auxiliary Switch VA9208 xxC 3 Models The VA9208 xxC 3 models include two integral auxiliary switches with a switch adjuster accessible on either face of the actu...

Page 13: ...ator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are availabl...

Page 14: ...beled A is Away from Valve CCW Spring Return Actuator Face Labeled B is Away from Valve CW Spring Return Rated Torque Power On Running 70 lb in 8 N m All Operating Temperatures Power Off Spring Return...

Page 15: ...UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric Actu...

Reviews: