TFP296
Page 4 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)
Response
Rating
Coverage
Area
(1)
,
ft x ft (m x m)
Minimum
Flow
(2)
,
gpm (lpm)
Minimum
Pressure
(2)
,
psi (bar)
Deflector-to-Ceiling
Distance
(3)
,
Inches (mm)
Sprinkler
Temperature
Rating,
°
F
Minimum
Spacing
(4)
,
ft (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
21.6 (1,48)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)
Quick
16 x 18 (4,9 x 5,5)
29 (110)
26.8 (1,85)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)
Quick
16 x 20 (4.9 x 6,1)
32 (121)
32.7 (2,25)
4 to 6 (100 to 150)
135
10 (3,1)
Quick
16 x 22 (4,9 x 6,7)
35 (133)
39.1 (2,70)
4 to 6 (100 to 150)
135
10 (3,1)
Standard
16 x 20 (4,9 x 6,1)
32 (121)
32.7 (2,25)
4 to 6 (100 to 150)
155
10 (3,1)
Standard
16 x 22 (4,9 x 6,7)
35 (133)
39.1 (2,70)
4 to 6 (100 to 150)
155, 175
10 (3,1)
8.0K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Response
Rating
Coverage
Area
(1)
,
ft x ft (m x m)
Minimum
Flow
(2)
,
gpm (lpm)
Minimum
Pressure
(2)
,
psi (bar)
Deflector-to-Ceiling
Distance
(3)
,
Inches (mm)
Sprinkler
Temperature
Rating,
°
F
Minimum
Spacing
(4)
,
ft (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
10.6 (0,73)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)/13 (4,0)
(5)
Quick
16 x 18 (4,9 x 5,5)
29 (110)
13.1 (0,90)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)/13 (4,0)
(5)
Quick
16 x 20 (4.9 x 6,1)
32 (121)
16.0 (1,10)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)
(5)
Quick
16 x 20 (4.9 x 6,1)
33 (125)
17.0 (1,17)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)
(5)
Quick
16 x 22 (4,9 x 6,7)
35 (133)
19.1 (1,32)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)
(5)
Quick
16 x 22 (4,9 x 6,7)
36 (136)
20.3 (1,59)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)
(5)
Quick
16 x 24 (4,9 x 7,3)
39 (148)
23.8 (1,64)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)
(5)
Quick
16 x 24 (4,9 x 7,3)
40 (151)
25.0 (1,72)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)
(5)
Standard
16 x 20 (4.9 x 6,1)
32 (121)
16.0 (1,10)
4 to 6 (100 to 150)
155
10 (3,1)/13 (4,0)
(5)
Standard
16 x 20 (4.9 x 6,1)
33 (125)
17.0 (1,17)
4 to 12 (100 to 300)
155
10 (3,1)/13 (4,0)
(5)
Standard
16 x 22 (4,9 x 6,7)
35 (133)
19.1 (1,32)
4 to 6 (100 to 150)
155, 175
10 (3,1)/13 (4,0)
(5)
Standard
16 x 22 (4,9 x 6,7)
36 (136)
20.3 (1,59)
4 to 12 (100 to 300)
155, 175
10 (3,1)/13 (4,0)
(5)
Standard
16 x 24 (4,9 x 7,3)
39 (148)
23.8 (1,64)
4 to 6 (100 to 150)
155, 175
10 (3,1)/13 (4,0)
(5)
Standard
16 x 24 (4,9 x 7,3)
40 (151)
25.0 (1,72)
4 to 12 (100 to 300)
155, 175
10 (3,1)/13 (4,0)
(5)
Notes:
1. Backwall (where sprinkler is located) by sidewall (length of throw)
2. Requirement is based on minimum flow in gpm from each sprinkler. The indicted residual pressures are based on the nominal K-factor.
3. The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4. Minimum spacing is for lateral distance between sprinklers located along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
5. Minimum spacing is 13 ft (4,0 m) when design pressure exceeds 175 psi (12,1 bar), otherwise the minimum spacing is 10 ft (3 m).
TABLE C
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA