TFP296

Page 4 of 8

5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)

Response 

Rating

Coverage 

Area

(1)

ft x ft (m x m)

Minimum  

Flow

(2)

gpm (lpm)

Minimum  

Pressure

(2)

psi (bar)

Deflector-to-Ceiling 

Distance

(3)

Inches (mm)

Sprinkler 

Temperature 

Rating, 

°

F

Minimum 

Spacing

(4)

ft (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,48)

4 to 12 (100 to 300)

135, 155, 175

10 (3,1)

Quick

16 x 18 (4,9 x 5,5)

29 (110)

26.8 (1,85)

4 to 12 (100 to 300)

135, 155, 175

10 (3,1)

Quick

16 x 20 (4.9 x 6,1)

32 (121)

32.7 (2,25)

4 to 6 (100 to 150)

135

10 (3,1)

Quick

16 x 22 (4,9 x 6,7)

35 (133)

39.1 (2,70)

4 to 6 (100 to 150)

135

10 (3,1)

Standard

16 x 20 (4,9 x 6,1)

32 (121)

32.7 (2,25)

4 to 6 (100 to 150)

155

10 (3,1)

Standard

16 x 22 (4,9 x 6,7)

35 (133)

39.1 (2,70)

4 to 6 (100 to 150)

155, 175

10 (3,1)

8.0K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)

Response 

Rating

Coverage 

Area

(1)

ft x ft (m x m)

Minimum 

Flow

(2)

gpm (lpm)

Minimum 

Pressure

(2)

psi (bar)

Deflector-to-Ceiling  

Distance

(3)

Inches (mm)

Sprinkler 

Temperature 

Rating, 

°

F

Minimum 

Spacing

(4)

ft (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

10.6 (0,73)

4 to 12 (100 to 300)

135, 155, 175

10 (3,1)/13 (4,0)

(5)

Quick

16 x 18 (4,9 x 5,5)

29 (110)

13.1 (0,90)

4 to 12 (100 to 300)

135, 155, 175

10 (3,1)/13 (4,0)

(5)

Quick

16 x 20 (4.9 x 6,1)

32 (121)

16.0 (1,10)

4 to 6 (100 to 150)

135

10 (3,1)/13 (4,0)

(5)

Quick

16 x 20 (4.9 x 6,1)

33 (125)

17.0 (1,17)

4 to 12 (100 to 300)

135

10 (3,1)/13 (4,0)

(5)

Quick

16 x 22 (4,9 x 6,7)

35 (133)

19.1 (1,32)

4 to 6 (100 to 150)

135

10 (3,1)/13 (4,0)

(5)

Quick

16 x 22 (4,9 x 6,7)

36 (136)

20.3 (1,59)

4 to 12 (100 to 300)

135

10 (3,1)/13 (4,0)

(5)

Quick

16 x 24 (4,9 x 7,3)

39 (148)

23.8 (1,64)

4 to 6 (100 to 150)

135

10 (3,1)/13 (4,0)

(5)

Quick

16 x 24 (4,9 x 7,3)

40 (151)

25.0 (1,72)

4 to 12 (100 to 300)

135

10 (3,1)/13 (4,0)

(5)

Standard

16 x 20 (4.9 x 6,1)

32 (121)

16.0 (1,10)

4 to 6 (100 to 150)

155

10 (3,1)/13 (4,0)

(5)

Standard

16 x 20 (4.9 x 6,1)

33 (125)

17.0 (1,17)

4 to 12 (100 to 300)

155

10 (3,1)/13 (4,0)

(5)

Standard

16 x 22 (4,9 x 6,7)

35 (133)

19.1 (1,32)

4 to 6 (100 to 150)

155, 175

10 (3,1)/13 (4,0)

(5)

Standard

16 x 22 (4,9 x 6,7)

36 (136)

20.3 (1,59)

4 to 12 (100 to 300)

155, 175

10 (3,1)/13 (4,0)

(5)

Standard

16 x 24 (4,9 x 7,3)

39 (148)

23.8 (1,64)

4 to 6 (100 to 150)

155, 175

10 (3,1)/13 (4,0)

(5)

Standard

16 x 24 (4,9 x 7,3)

40 (151)

25.0 (1,72)

4 to 12 (100 to 300)

155, 175

10 (3,1)/13 (4,0)

(5)

Notes:

1.  Backwall (where sprinkler is located) by sidewall (length of throw)
2.  Requirement is based on minimum flow in gpm from each sprinkler. The indicted residual pressures are based on the nominal K-factor.
3.  The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4.  Minimum spacing is for lateral distance between sprinklers located along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-

site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

5.  Minimum spacing is 13 ft (4,0 m) when design pressure exceeds 175 psi (12,1 bar), otherwise the minimum spacing is 10 ft (3 m).

TABLE C 

UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA

Summary of Contents for tyco TY-FRB Series

Page 1: ...r utilizes either a two piece Style 10 1 2 in NPT or Style 40 3 4 in NPT Recessed Escutch eon with 1 2 in 12 7 mm of recessed adjustment or up to 3 4 in 19 1 mm of total adjustment from the flush side wall position or a two piece Style 20 1 2 in NPT or Style 30 3 4 in NPT Recessed Escutcheon with 1 4 in 6 4 mm of recessed adjustment or up to 1 2 in 12 7 mm of total adjustment from the flush sidewa...

Page 2: ...s as outlined in the appliable installation standard recognized by the Approval Agency e g UL recognizes NFPA 13 and FM recognize the FM Loss Preven tion Data Sheets Only the Style 10 20 30 or 40 Recessed Escutcheon as applicable is to be used for recessed installations 2 5 4 6 1 3 WRENCH FLATS 1 1 2 38 1 mm 2 3 16 55 6 mm 7 16 11 1 mm NOMINAL MAKE IN 1 9 16 39 7 mm DEFLECTOR HAT 1 2 NPT 7 7 16 11...

Page 3: ...tual Research Corporation FM per Table D 4 Approved by the City of New York under MEA 354 01 E 5 Where Polyester Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and C UL Listed corrosion resistant sprinklers a Installed with Style 10 1 2 in NPT or Style 40 3 4 in NPT 3 4 in Total Adjustment Recessed Escutcheon as applicable b Installed with Style 20 1 2 in NPT or Style 3...

Page 4: ...4 0 5 Quick 16 x 22 4 9 x 6 7 36 136 20 3 1 59 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 39 148 23 8 1 64 4 to 6 100 to 150 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 40 151 25 0 1 72 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 32 121 16 0 1 10 4 to 6 100 to 150 155 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 33 125 17 0 1 17 4 to 12 100 to 300 155 10 3 1...

Page 5: ...6 20 1 38 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 20 4 9 x 6 1 40 151 25 1 72 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 22 4 9 x 6 7 44 167 30 2 06 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 24 4 9 x 6 7 48 182 36 2 48 4 to 12 100 to 300 135 155 10 3 1 Standard 16 x 16 4 9 x 4 9 32 121 16 1 10 4 to 12 100 to 300 175 10 3 1 Standard 16 x 18 4 9 x 5 5 36 136 20 1 38 4 to 12 100 to 300 175 ...

Page 6: ...6 and 8 0 K factor Extended Coverage Horizon tal Sidewall Sprinklers Quick and Stan dard Response Light Hazard must be maintained and serviced in accordance with this section Before closing a fire protection system main control valve for maintenance work on the fire pro tection system that it controls per mission to shut down the affected fire protection system must be obtained from the proper aut...

Page 7: ...m 1 1 4 31 8 mm CLOSURE 1 4 6 4 mm 1 2 12 7 mm MOUNTING PLATE MOUNTING SURFACE FACE OF SPRINKLER FITTING 2 1 4 DIA 57 2 mm 2 7 8 DIA 73 0 mm SERIES TY FRB EC 1 8 3 2 mm 1 2 1 8 12 7 3 2 mm FIGURE 5 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5 6 K FACOTR 1 2 INCH NPT FIGURE 6 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLE...

Page 8: ...rt Number P N Sprinkler Assembly with NPT Thread Connections Specify Series TY FRB specify SIN Extended Coverage Horizontal Side wall Sprinkler K specify specify temperature rating specify finish P N specify from Table E Recessed Escutcheon Specify Style 10 20 30 or 40 Recessed Escutcheon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkl...

Reviews: