Johnson Controls tyco TY-FRB Series Manual Download Page 6

TFP296

Page 6 of 8

Installation

TYCO Series TY-FRB 5.6 and 8.0 

K-factor Extended Coverage Horizon-

tal Sidewall Sprinklers Quick and Stan-

dard Response (Light Hazard) must 

be installed in accordance with this 

section.
Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm).
A leak tight 1/2 inch NPT sprinkler joint 

should be obtained with a torque of 

7 to 14 lb-ft (9,5 to 19,0 N·m). A leak 

tight 3/4 in. NPT sprinkler joint should 

be obtained with a torque of 10 to  

20 lb-ft (13,4 to 26,8 N·m). Higher levels 

of torque may distort the sprinkler inlet 

and cause leakage or impairment of the 

sprinkler.
Do not attempt to make-up for insuf-

ficient adjustment in the escutcheon 

plate by under- or over-tightening the 

sprinkler. Readjust the position of the 

sprinkler fitting to suit.

Series TY-FRB EC 

Sidewall Sprinkler

The Series TY-FRB EC Sidewall Sprin-

klers must be installed in accordance 

with the following instructions:

Step 1.

 Horizontal sidewall sprinklers 

are to be installed with their center-

line perpendicular to the back wall and 

parallel to the ceiling. The word “TOP” 

on the deflector is to face towards the 

ceiling.

Step 2.

 With pipe thread sealant 

applied to the pipe threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

6 Sprinkler Wrench (Ref. Figure 3). 

With reference to Figures 1 and 2, the 

W-Type 6 Sprinkler Wrench is to be 

applied to the sprinkler wrench flats.

Series TY-FRB Recessed EC 

Sidewall Sprinkler

The Series TY-FRB Recessed EC 

Sidewall Sprinklers must be installed 

in accordance with the following 

instructions:

Step 1.

 Horizontal sidewall sprinklers 

are to be installed with their center-

line perpendicular to the back wall and 

parallel to the ceiling. The word “TOP” 

on the deflector is to face towards the 

ceiling.

Step 2.

 After installing the Style 10, 20, 

30, or 40 Mounting Plate, as applica-

ble, over the sprinkler threads and with 

pipe thread sealant applied to the pipe 

threads, hand tighten the sprinkler into 

the sprinkler fitting.

Step 3.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

7 Recessed Sprinkler Wrench (Ref. 

Figure 4). With reference to Figure 1 

or 2, the W-Type 7 Recessed Sprinkler 

Wrench is to be applied to the sprinkler 

wrench flats.

Step 4.

 After the wall has been installed 

or the finish coat has been applied, 

slide on the Style 10, 20, 30, or 40. 

Closure over the Series TY-FRB Sprin-

kler and push the Closure over the 

Mounting Plate until its flange comes 

in contact with the wall.

Care and 

Maintenance

TYCO Series TY-FRB 5.6 and 8.0 

K-factor Extended Coverage Horizon-

tal Sidewall Sprinklers Quick and Stan-

dard Response (Light Hazard) must be 

maintained and serviced in accordance 

with this section. Before closing a fire 

protection system main control valve 

for maintenance work on the fire pro-

tection system that it controls, per-

mission to shut down the affected fire 

protection system must be obtained 

from the proper authorities and all per-

sonnel who may be affected by this 

action must be notified.
The owner must assure that the sprin-

klers are not used for hanging of any 

objects; otherwise, non-operation in 

the event of a fire or inadvertent oper-

ation may result.
Absence of an escutcheon, which is 

used to cover a clearance hole, may 

delay the time to sprinkler operation in 

a fire situation.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. (Refer to Installa-

tion Section.)
Frequent visual inspections are rec-

ommended to be initially performed 

for corrosion resistant coated sprin-

klers, after the installation has been 

completed, to verify the integrity of the 

corrosion resistant coating. Thereafter, 

annual inspections per NFPA 25 should 

suffice; however, instead of inspecting 

from the floor level, a random sampling 

of close-up visual inspections should 

be made, so as to better determine the 

exact sprinkler condition and the long 

term integrity of the corrosion resistant 

coating, as it may be affected by the 

corrosive conditions present.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Asso-

ciation (e.g., NFPA 25), in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions. It is recommended 

that automatic sprinkler systems be 

inspected, tested, and maintained by 

a qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

WRENCH RECESS

(END "A" USED FOR

1/2" NPT MODELS)

WRENCH RECESS

(END "B" USED FOR

3/4" NPT MODELS)

WRENCH

RECESS

PUSH WRENCH

IN TO ENSURE

ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

FIGURE 3 

W-TYPE 6 

SPRINKLER WRENCH

FIGURE 4 

W-TYPE 7 RECESSED 

SPRINKLER WRENCH

Summary of Contents for tyco TY-FRB Series

Page 1: ...r utilizes either a two piece Style 10 1 2 in NPT or Style 40 3 4 in NPT Recessed Escutch eon with 1 2 in 12 7 mm of recessed adjustment or up to 3 4 in 19 1 mm of total adjustment from the flush side wall position or a two piece Style 20 1 2 in NPT or Style 30 3 4 in NPT Recessed Escutcheon with 1 4 in 6 4 mm of recessed adjustment or up to 1 2 in 12 7 mm of total adjustment from the flush sidewa...

Page 2: ...s as outlined in the appliable installation standard recognized by the Approval Agency e g UL recognizes NFPA 13 and FM recognize the FM Loss Preven tion Data Sheets Only the Style 10 20 30 or 40 Recessed Escutcheon as applicable is to be used for recessed installations 2 5 4 6 1 3 WRENCH FLATS 1 1 2 38 1 mm 2 3 16 55 6 mm 7 16 11 1 mm NOMINAL MAKE IN 1 9 16 39 7 mm DEFLECTOR HAT 1 2 NPT 7 7 16 11...

Page 3: ...tual Research Corporation FM per Table D 4 Approved by the City of New York under MEA 354 01 E 5 Where Polyester Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and C UL Listed corrosion resistant sprinklers a Installed with Style 10 1 2 in NPT or Style 40 3 4 in NPT 3 4 in Total Adjustment Recessed Escutcheon as applicable b Installed with Style 20 1 2 in NPT or Style 3...

Page 4: ...4 0 5 Quick 16 x 22 4 9 x 6 7 36 136 20 3 1 59 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 39 148 23 8 1 64 4 to 6 100 to 150 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 40 151 25 0 1 72 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 32 121 16 0 1 10 4 to 6 100 to 150 155 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 33 125 17 0 1 17 4 to 12 100 to 300 155 10 3 1...

Page 5: ...6 20 1 38 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 20 4 9 x 6 1 40 151 25 1 72 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 22 4 9 x 6 7 44 167 30 2 06 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 24 4 9 x 6 7 48 182 36 2 48 4 to 12 100 to 300 135 155 10 3 1 Standard 16 x 16 4 9 x 4 9 32 121 16 1 10 4 to 12 100 to 300 175 10 3 1 Standard 16 x 18 4 9 x 5 5 36 136 20 1 38 4 to 12 100 to 300 175 ...

Page 6: ...6 and 8 0 K factor Extended Coverage Horizon tal Sidewall Sprinklers Quick and Stan dard Response Light Hazard must be maintained and serviced in accordance with this section Before closing a fire protection system main control valve for maintenance work on the fire pro tection system that it controls per mission to shut down the affected fire protection system must be obtained from the proper aut...

Page 7: ...m 1 1 4 31 8 mm CLOSURE 1 4 6 4 mm 1 2 12 7 mm MOUNTING PLATE MOUNTING SURFACE FACE OF SPRINKLER FITTING 2 1 4 DIA 57 2 mm 2 7 8 DIA 73 0 mm SERIES TY FRB EC 1 8 3 2 mm 1 2 1 8 12 7 3 2 mm FIGURE 5 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5 6 K FACOTR 1 2 INCH NPT FIGURE 6 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLE...

Page 8: ...rt Number P N Sprinkler Assembly with NPT Thread Connections Specify Series TY FRB specify SIN Extended Coverage Horizontal Side wall Sprinkler K specify specify temperature rating specify finish P N specify from Table E Recessed Escutcheon Specify Style 10 20 30 or 40 Recessed Escutcheon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkl...

Reviews: