TFP658
Page 7 of 16
ALLOW MINIMUM 2 HOUR CURE TIME BEFORE SYSTEM PRESSURE
TESTING
REFER TO PERMABOND LH056 TECHNICAL DATA SHEET FOR MORE
INFORMATION, GO TO: www.permabond.com
APPLY SEALANT AROUND FIRST 4 (MINIMUM) SPRINKLER INLET
THREADS LEAVING FIRST THREAD FREE OF SEALANT
ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER
WATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENT
FAILURE
USE ONLY PERMABOND LH056 SEALANT FOR SEALING SPRINKLER
INLET THREAD CONNECTION IN CPVC PIPE SYSTEM
NOTES:
5.
6.
2.
4.
1.
3.
INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT
CPVC SPRINKLER
HEAD ADAPTER FITTING,
ISO 228 G3/8" THREAD
SPRINKLER
INLET
THREADS
RAVEN STUDIO SPRINKLER
WITH PAINT CAP OR
W-TYPE 25 WRENCH
PERMABOND LH056
SEALANT
APPLICATOR
CPVC
PIPE FROM
SYSTEM
APPLY SEALANT AROUND FIRST 2-3 (MINIMUM) SPRINKLER INLET
THREADS
NOTES:
3.
1.
ALLOW MINIMUM 1 HOUR CURE TIME BEFORE SYSTEM PRESSURE
TESTING
REFER TO LOCTITE 243 TECHNICAL DATA SHEET FOR MORE
INFORMATION, GO TO: www.loctite.com
ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER
WATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENT
FAILURE
INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT
6.
7.
5.
4.
2. DO NOT USE LOCTITE 243 SEALANT IN CPVC PIPE SYSTEMS
USE ONLY LOCTITE 243 SEALANT FOR SEALING SPRINKLER
INLET THREAD CONNECTION IN STEEL PIPE SYSTEM
SPRINKLER
INLET
THREADS
RAVEN STUDIO SPRINKLER
WITH PAINT CAP OR
W-TYPE 25 WRENCH
LOCTITE 243
SEALANT
BOTTLE
STEEL
PIPE FROM
SYSTEM
MALLEABLE OR CAST IRON
SPRINKLER FITTING
WITH THREAD ADAPTER
FIGURE 10
RAVEN STUDIO SPRINKLERS
PERMABOND LH056 SEALANT APPLICATION — CPVC PIPE SYSTEM INSTALLATIONS
FIGURE 9
RAVEN STUDIO SPRINKLERS
LOCTITE 243 SEALANT APPLICATION — STEEL PIPE SYSTEM INSTALLATIONS