Design 

Criteria

Standard Coverage Criteria

RAVEN Studio 5.6K Pendent and Hori-

zontal Sidewall Sprinklers (TY1281 and 

TY1381) are intended for use in light 

hazard or ordinary hazard applica-

tions as defined by NFPA 13, utilizing 

the density/area method for hydrau-

lically calculated systems, and with 

fire protection systems designed in 

accordance with the standard instal-

lation rules recognized by the applica-

ble listing or approval agency (e.g., UL 

Listing is based on NFPA 13 require-

ments). RAVEN Studio Horizontal 

Sidewall Sprinklers (TY1381) must be 

installed with a deflector-to-ceiling dis-

tance of 4 to 12 in. (100 to 300 mm). To 

meet this requirement, the centerline of 

the sprinkler waterway must be located 

4-7/16 to 12-7/16 in. (112,7 to 315,9 mm) 

below the ceiling (Ref. Figures 13 and 

15).

Extended Coverage Criteria

RAVEN Studio 5.6K Pendent and Hori-

zontal Sidewall Sprinklers (TY1282 and 

TY1382) must be installed in accor-

dance with the flow rate criteria pro-

vided in Table A. They must be installed 

and utilized in light hazard occupancies 

only under smooth, flat, horizontal ceil-

ings as outlined in the applicable instal-

lation standard recognized by the listing 

or approval agency (e.g., UL Listing is 

based on NFPA 13 requirements).
RAVEN Extended Coverage, Horizontal 

Sidewall Sprinklers (TY1382) must be 

installed with a deflector-to-ceiling dis-

tance of 4 to 12 in. (100 to 300 mm). To 

meet this requirement, the centerline of 

the sprinkler waterway must be located 

4-7/16 to 12-7/16 in. (112,7 to 315,9 mm) 

below the ceiling (Ref. Figures 13 and 

15).

Operation

Water is prevented from flowing from 

the RAVEN Studio Sprinkler by means 

of a sealing assembly held in place 

by operating parts secured by a link 

assembly. The link assembly is com-

prised of two link halves soldered 

together with an eutectic solder that 

melts when exposed to heat. When 

the link reaches its rated temperature, 

the link halves separate and release 

the operating parts and sealing assem-

bly, allowing the deflector assembly to 

extend from the body and water to flow 

from the sprinkler.

Care and 

Maintenance

TYCO RAVEN Studio Sprinklers 5.6K 

Pendent and Horizontal Sidewall 

 

(HSW) Quick Response, Standard and 

Extended Coverage must be main-

tained and serviced in accordance with 

this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Service inspections should be made 

on a regular basis to detect possible 

damage or alterations to the sprin-

kler and escutcheon. Inspections 

should include making certain that the 

escutcheon is held fast to the mount-

ing surface. Damaged or altered sprin-

klers are to be replaced immediately 

to avoid personal injury and to prevent 

use for causing personal injury, as well 

as to maintain the sprinkler system in 

an operative condition.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced.
Frequent visual inspections are recom-

mended to be initially performed for 

sprinklers installed in potentially corro-

sive atmospheres to verify the integrity 

of the materials of construction as they 

may be affected by the corrosive con-

ditions present for a given installation. 
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the approval agency and standards 

of any other authority having jurisdic-

tion. Contact the installing contrac-

tor or product manufacturer with any 

questions.
Sprinklers are recommended to be 

inspected, tested, and maintained by 

a qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

5.6K Extended Coverage Pendent (TY1282)

Response 

Rating

Coverage Area 

ft x ft (m x m)

Minimum 

Flow

(a)

 

gpm (lpm)

Minimum 

Pressure

(b)

 

psi (bar)

Deflector-to-Ceiling 

Distance

Sprinkler 

Temperature Rating 

°F (°C)

Minimum 

Spacing 

ft (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,49)

Flush Mounted

165 (74)

8 (2,4)

5.6K Extended Coverage Horizontal Sidewall (TY1382)

Response 

Rating

Coverage Area 

ft x ft (m x m)

Minimum 

Flow

(a)

 

gpm (lpm)

Minimum 

Pressure

(b)

 

psi (bar)

Deflector-to-Ceiling 

Distance

(c)

 

Inches (mm)

Sprinkler 

Temperature Rating 

°F (°C)

Lateral 

Minimum 

Spacing

(d)

 

ft (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,49)

4 to 12 (100 to 300)

165 (74)

8 (2,4)

Notes:

a.  Requirement is based on minimum flow in gpm (lpm) from each sprinkler.
b.  Indicated residual pressures are based on the nominal K-factor.
c.  Centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 15).
d.  Minimum spacing is for lateral distance between sprinklers located along a single wall; otherwise, adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an 

opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

TABLE A 

RAVEN STUDIO SPRINKLERS 

UL AND C-UL LISTING EXTENDED COVERAGE AREAS FOR LIGHT HAZARDS AND FLOW RATE CRITERIA

Summary of Contents for tyco RAVEN

Page 1: ...CIATION NFPA in addition to the standards of any authorities having jurisdiction Failure to do so may impair the performance of these devices Johnson Controls specifically dis claims any liability for damages or injury including death arising out of or caused by manipulation disman tling or misuse of RAVEN Studio Sprin klers or the use or attempted use of the RAVEN Studio Sprinklers or any com pon...

Page 2: ...AL SIDEWALL SHOWN LINK ASSEMBLY FACTORY PAINTED AREA EXPOSED BRASS SHOULDER BODY A INSTALLATION LIP BASE FLANGE CLEARANCE HOLE C B A PRONGS Application Coverage SIN Dust Cap Color A Inches mm Pendent Standard TY1281 Red 1 7 8 48 Extended TY1282 Horizontal Sidewall Standard TY1381 Green 2 13 16 56 Extended TY1382 Dimensions Inches mm Dim Escutcheon Style J K A Dia 3 76 4 101 B 7 16 11 C Dia Min 2 5...

Page 3: ...THREADS OF CPVC SPRINKLER ADAPTER FITTING THREAD ADAPTER NOT REQUIRED REFER TO CPVC INSTALLATION HANDBOOK IH 1900 FOR GUIDANCE ON INSTALLING FITTINGS IN CPVC PIPE SYSTEMS CPVC SPRINKLER ADAPTER FITTINGS WITH ISO 228 G3 8 OUTLET THREADS DESIGNED FOR USE IN LOW PROFILE LIMITED SPACE INSTALLATIONS 90 ELBOW TEE D Y C C X Y D A A B E C X X B A Fitting Type A Nominal Pipe Size Inches DN B Outlet Thread ...

Page 4: ...ING FACE OF THREAD ADAPTER SPRINKLER FITTING AND WATERWAY CENETRLINE STYLE J OR K ESCUTCHEON CEILING OR WALL ESCUTCHEON MOUNTING SURFACE CLEARANCE HOLE CEILING OR WALL COVERING MATERIAL FACE OF FRAMING MEMBER SPRINKLER BODY ENGAGED BY ESCUTCHEON PRONGS A B SPRINKLER FITTING THREAD ADAPTER Thread Adapter Size Thread Adapter Length Inches mm A Inches mm B Nominal Inches mm Pendent Horizontal Sidewal...

Page 5: ...TYLE J OR K ESCUTCHEON CEILING OR WALL ESCUTCHEON MOUNTING SURFACE CLEARANCE HOLE CEILING OR WALL COVERING MATERIAL FACE OF FRAMING MEMBER SPRINKLER BODY ENGAGED BY ESCUTCHEON PRONGS A CPVC PIPE FROM SYSTEM CPVC SPRINKLER ADAPTER FITTING WITH ISO 228 G3 8 OUTLET THREADS REF FIGURE 4 Fitting Type Fitting Size Inches x ISO 228 Outlet Threads A Inches mm Pendent Horizontal Sidewall Min Max Min Max 90...

Page 6: ...ION AND REMOVAL CAP PRONGS UNIQUELY SPACED TO ENGAGE SPRINKLER WRENCHING NOTCHES RAVEN STUDIO SPRINKLER UP INDICATES TOP OF HORIZONTAL SIDEWALL SPRINKLER DEFLECTOR CAP FLAT ACCOMMODATES LEVEL IF NECESSARY FOR HORIZONTAL SIDEWALL SPRINKLER INSTALLATION CENTER MARKING POINT FINGER GRIP CAP IS FOR SINGLE USE ONLY DO NOT RE USE AFTER PAINTING USE CAP FOR SPRINKLER INSTALLATION AND PROTECTION WHILE PAI...

Page 7: ... SYSTEM APPLY SEALANT AROUND FIRST 2 3 MINIMUM SPRINKLER INLET THREADS NOTES 3 1 ALLOW MINIMUM 1 HOUR CURE TIME BEFORE SYSTEM PRESSURE TESTING REFER TO LOCTITE 243 TECHNICAL DATA SHEET FOR MORE INFORMATION GO TO www loctite com ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER WATERWAY FAILURE TO DO SO MAY RESULT IN EQUIPMENT FAILURE INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT 6 7 5 4...

Page 8: ...STALLATION TOOL 36 0 9 m BEAM ACCOMMODATES VARIETY OF FRAMING SPACINGS FACE OF WALL OR CEILING FRAMING MEMBER WIDE BASE OF BEAM FLUSH AGAINST FACE OF FRAMING MEMBERS ADJUST TO SUIT FRAMING SPACING AND FITTING LOCATION LOCK UNLOCK GAUGE CARRIAGE IMPERIAL SCALE 0 to 1 1 2 METRIC SCALE 0 to 40 mm GAUGE LOCK HANDLE LIP OF SPRINKLER BODY NOT BRASS SHOULDER FLUSH AGAINST SPRINKLER BODY STOP SURFACE ADJU...

Page 9: ...CE OF FINISHED CEILING RAVEN STUDIO HORIZONTAL SIDEWALL SPRINKLER SPRINKLER FITTING THREAD ADAPTER ESCUTCHEON MOUNTING SURFACE SPRINKLER FITTING AND WATERWAY CENTERLINE 12 7 16 316 mm 4 7 16 133 mm REFERENCE DIMENSION D TOTAL CEILING OR WALL COVERING MATERIAL THICKNESS DRYWALL PLYWOOD ETC PLUS TAPE PLASTER ETC 1 NOTES CLEARANCE HOLE D REF PLASTER TAPE ETC CEILING OR WALL COVERING MATERIAL CEILING ...

Page 10: ...he mount ing surface Damaged or altered sprin klers are to be replaced immediately to avoid personal injury and to prevent use for causing personal injury as well as to maintain the sprinkler system in an operative condition Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise alter...

Page 11: ...ECTOR SPRINKLER DEFLECTOR ASSEMBLY IN OPERATED POSITION SPRINKLER DEFLECTOR ASSEMBLY IN OPERATED POSITION ESCUTCHEON ESCUTCHEON ESCUTCHEON MOUNTING SURFACE ESCUTCHEON MOUNTING SURFACE RAVEN STUDIO SPRINKLER RAVEN STUDIO SPRINKLER 4 102 mm TO 12 305 mm FACE OF FINISHED CEILING FIGURE 15 RAVEN STUDIO SPRINKLERS OPERATED CONDITION ...

Page 12: ...nkler with shipping cap attached to remain in original packaging until ready for installation To avoid damage to link assembly do not pull cap away from sprinkler at an angle Step 3 Apply TEFLON tape sealant to external threads of thread adapter and install into sprinkler fitting A leak tight 1 2 in NPT thread adapter joint should be obtained by applying a minimum to maximum torque of 7 to 14 lb f...

Page 13: ... Paint ceiling or wall to suit Note Paint cap to remain attached while painting ceiling or wall Note Install primed escutcheon for best painting results refer to Ordering Procedure Step 10 Orient escutcheon base flange toward mounting surface align ing escutcheon centerline with sprin kler centerline Push escutcheon onto sprinkler engaging body by prongs until flange is flush against mounting surf...

Page 14: ...wrench prongs Ref Figures 1 7 and 8 Apply sealant to sprinkler inlet threads steel pipe system installations Ref Figure 9 CPVC pipe system installations Ref Figure 10 NOTICE Assure sealant avoids contact with internal waterway of sprinkler Failure to do so may result in equipment failure Step C Remove shipping cap from sprinkler by pulling away from body along sprinkler centerline NOTICE Sprinkler...

Page 15: ...lant to set before proceeding to Step J 5 minutes for LOCTITE 243 30 minutes for PERM ABOND LH056 Step L Paint ceiling or wall to suit Note Paint cap to remain attached while painting ceiling or wall Note Install primed escutcheon for best painting results refer to Ordering Procedure Step K Orient escutcheon base flange toward mounting surface align ing escutcheon centerline with sprin kler center...

Page 16: ...med White 56 306 0 004 Primed Grey 56 306 0 007 Custom Color 56 306 X 010 Stainless Steel White 56 307 4 010 Grey 56 307 7 010 Electropolish 56 307 9 010 Primed White 56 307 0 004 Primed Grey 56 307 0 007 Custom Color 56 307 X 010 Chrome coated appearance Style K Escutcheons 4 Inch Diameter Specify RAVEN Studio Sprinkler Escutcheon Style K 4 inch diameter specify material specify finish P N specif...

Reviews: