background image

TFP402

Page 3 of 4

Installation

The TYCO RAPID RESPONSE Series 

LFII Residential Pendent Sprinklers 

(TY1234) must be installed in accor-

dance with this section:

General Instructions

Do not install any bulb-type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm).
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 7 to 14 

lb-ft (9,5 to 19,0 N

m). Higher levels 

of torque can distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment in an Escutch-

eon Plate by under-or over-tightening 

the Sprinkler. Re-adjust the position of 

the sprinkler fitting to suit.

Residential Sprinkler Design Guide

When conditions exist that are outside 

the scope of the provided criteria, refer 

to the Residential Pendent Sprinkler 

Design Guide TFP490 for the manufac-

turer’s recommendations that may be 

acceptable to the local authority having 

jurisdiction.

System Type

Only wet pipe systems may be utilized.

Ceiling Types

Smooth flat horizontal, or beamed, or 

sloped, in accordance with the 2013 

Edition of NFPA 13D, 13R, or 13 as 

applicable.

Hydraulic Design

(NFPA 13D and 13R)

The minimum re 

quired sprinkler 

flow rate for systems designed to 

NFPA 13D or NFPA 13R are given in  

Table A as a function of temperature 

rating and the maximum allowable cov-

erage areas. The sprinkler flow rate is 

the minimum required discharge from 

each of the total number of design 

sprinklers as specified in NFPA 13D or 

NFPA 13R.

Hydraulic Design

(NFPA 13)

For systems designed to NFPA 13, the 

number of design sprinklers is to be 

the four most hydraulically demanding 

sprinklers. The minimum required dis-

charge from each of the four sprinklers 

is to be the greater of the following:

•  The flow rates given in Table A for 

NFPA 13D and 13R as a function of 

TFP402 temperature rating and the 

maximum allowable coverage area.

•  A minimum discharge of 0.1 

 

gpm/ft

2

 over the “design area” 

comprised of the four most hydrau-

lically demanding sprinklers for 

actual coverage areas protected by 

the four sprinklers.

Obstruction to Water Distribution

Sprinklers are to be located in accor-

dance with the obstruction rules of 

NFPA 13D, 13R, and 13 as applica-

ble for residential sprinklers as well as 

with the obstruction criteria described 

within the TYCO technical data sheet 

TFP490.

Operational Sensitivity

Sprinklers are to be installed with 

a deflector-to-ceiling distance of 

 

1-1/4 in. to 4 in.

Sprinkler Spacing

The minimum spacing between sprin-

klers is 8 ft (2,4 m). The maximum 

spacing between sprinklers cannot 

exceed the length of the coverage 

area being hydraulically calculated 

(for example a maximum of 12 ft for a  

12 ft x 12 ft coverage area, or 16 ft for a 

16 ft x 16 ft coverage area.) See Table 

A.

Max. 

Coverage 

Area 

(a)

ft x ft 

(m x m)

WET PIPE SYSTEM 

Minimum Flow and Residual Pressure 

(b, c)

Ordinary Temp. Rating 

155°F (68°C)

Intermediate Temp. Rating 

175°F (79°C)

Deflector to 

Ceiling

Installation 

Type

Minimum 

Spacing  

ft  

(m)

Flow 

GPM 

(L/min)

Pressure  

PSI  

(bar)

Flow 

GPM 

(L/min)

Pressure 

PSI  

(bar)

12 x 12 

(3,7 x 3,7)

(30,3)

7.1 

(0,49)

(30,3)

7.1 

(0,49)

Smooth  

Ceilings  

1-1/4 in. to 4 in.

Beamed  

Ceilings per 

NFPA 13D  

or 13R

1-1/4 in. to 

1-3/4 in. below 

bottom of 

beam.

Recessed 

using Style 20 

Escutcheon or 

non-recessed 

per NFPA 13D, 

13R, or 13

8

(2,4)

14 x 14 

(4,3 x 4,3) 

11 

(41,6)

13.4 

(0,92)

11 

(41,6)

13,4 

(0,92)

15 x 15 

(4,6 x 4,6)

12 

(45,4)

16 

(1,10)

12 

(45,4)

16 

(1,10)

16 x 16 

(4,9 x 4,9)

13 

(49,2)

18.8 

(1,29)

13 

(49,2)

18.8 

(1,29)

18 x 18 

(5,5 x 5,5)

17 

(64,3)

32,1 

(2,21)

18 

(68,1)

36.0 

(2,48)

Notes:

a.  For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which 

hydraulic design criteria are stated.

b.  Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal  

K-factor. See Hydraulic Design under the Design Criteria section.

c.  For NFPA 13 residential applications, the greater of 0.1 gpm/ft

2

 over the design area or the flow in accordance with the criteria in this table must be 

used.

TABLE A 

WET PIPE SYSTEM 

SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY1234)  

NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

Reviews: