Figure 15: KT-1-PCB lock setup
Callout
Description
A
Door locking device: 12 VDC, 750 mA maximum.
B
Connect a 1000 ohm resistor between LK- and +12 V if you do not use a locking
device.
Connecting inputs
The controller can monitor four input points. Each onboard input is supervised with or without end-
of-line (EOL) resistors. The resistors for all inputs are 5.6K ohm, if selected. The maximum distance
of one line is 2,000 ft (600 m) with AWG #22 in a single or double EOL configuration.
1.
Connect devices to inputs 1 to 4.
2.
Define onboard inputs with none, single, or double EOL resistors.
Note:
For UL listed installations, you must use supervised EOL resistors.
Note:
Inputs 1 and 2 are automatically reserved for the controlled door. The door contact is
assigned to input 1 and the associated request-to-exit detector is assigned to input 2. You do
not have to follow this convention but it facilitates servicing.