Installation

The TYCO Type IFP AQUAMIST 

Recessed Nozzle Fittings must be 

installed in accordance with this 

section.

General Instructions

A leak-tight 1/2 inch NPT Nozzle joint 

should be obtained by applying a 

minimum-to-maximum torque of 7 to  

14 lb-ft (9,5 to 19,0 N·m). Higher levels 

of torque can distort the nozzle inlet 

and cause leakage or impairment of 

the nozzle.

NOTICE

The Type AM10 or AM31 AQUAMIST 

Nozzle may be factory assembled with 

a Recessed IFP Fitting and Cap. If the 

nozzles have been pre-assembled, 

proceed to Step 5.

Step 1.

 Prepare nozzle by applying 

TEFLON paste thread sealant to pipe 

threads.

Step 2.

 Assemble nozzle with Cap 

Assembly. Engage nozzle wrench boss 

by Link flanges shown in Figures 1 and 

2.

Step 3.

 Hand tighten nozzle into IFP 

fitting until nozzle diffuser is located 

3/16 inch (4,8 mm) minimum from face 

of fitting.

Step 4.

 Tighten nozzle into fitting 

using only W-Type 29 Wrench (Figure 

5). Guide wrench arm slots over nozzle 

frame arms, guide Cap Retention Chain 

through wrench chain slot, and engage 

Link flanges by wrench tines.

NOTICE

The Recessed IFP Fitting and Cap 

may be factory assembled with a Type 

AM10 or AM31 AQUAMIST Nozzle. If 

pre-assembled, ensure the cap is dis-

lodged from the fitting exposing the 

nozzle to facilitate proper orientation 

and alignment. Observe nozzle orien-

tation and chain alignment notices pre-

ceding Step 7.

Step 5.

 From equipment interior, insert 

IFP Fitting (NPT Threaded or Socket-

Weld) through clearance hole until 

flange is flush against interior surface 

of hood and hold in place.

Step 6.

 Install one Washer and Locknut 

on 1-1/2 NPS threaded portion of fitting 

extending through exterior of hood. 

Tighten Locknut and ensure fitting 

flange is flush against interior surface 

of hood.

NOTICE

To facilitate effective nozzle tighten-

ing it may be necessary to immobilize 

the IFP fitting by applying appropriate 

wrench to fitting wrench flats.
For proper installation ensure the 

Nozzle Frame Arms are aligned per 

Technical Data Sheet TFP2240.
For proper installation ensure Cap 

Retention Chain is aligned with nozzle 

frame arm on low side of hood slope as 

applicable (Figures 3 and 4).

Step 7.

 Insert the chain into the Cap 

and snap cap into IFP fitting. Ensure 

fitting groove is fully engaged by Cap 

dimples.

NOZZLE

WRENCH

BOSS

ENGAGED

BY LINK

ALIGN CHAIN WITH

NOZZLE FRAME ARM

AND GUIDE THROUGH

CHAIN SLOT

IFP FITTING

AND MOUNTING

HARDWARE

INTERIOR

SURFACE

OF HOOD

CHAIN

SLOT

NOZZLE

CAVITY

ACCEPTS 1/2"

SOCKET DRIVE

NOZZLE FRAME

ARM SLOTS

LINK

ENGAGEMENT

TINES

NOZZLE

CAP

RETENTION

CHAIN

 LINK ENGAGED

BY WRENCH

TINES

IFP FITTING

WRENCH FLATS

CAP

EJECTED

IN SYSTEM

DISCHARGE

CONDITION

CAP

RETENTION

CHAIN

NOZZLE

EXPOSED

IN SYSTEM

DISCHARGE

CONDITION

CAP

IN SYSTEM

STANDBY

CONDITION

FIGURE 5 