Johnson Controls TRUE RH HC-67x3 Installation Instructions Manual Download Page 7

 

T

RUE

RH Series HC-67x3 Humidity Controllers Installation Instructions    

7

 

Technical Specifications 

Product 

T

RUE

RH Series HC-67x3 Humidity Controllers 

Power Requirements 

14 to 30 VDC at 10 mA or 20 to 30 VAC, 50/60 Hz at 15 mA with no load, Class 2 

Control Action 

Jumper selectable, direct or reverse (factory set for reverse acting) 

Output Range 

Jumper selectable, 0 to 10 VDC (factory set) or 6 to 9 VDC; 5 k ohm minimum load 
impedance 

Humidity 

Element:  

All-Polymer™ element 

Sensing Range: 

0 to 100% RH, non-condensing 

Setpoint:  

Adjustable from 20 to 80% RH 

Proportional Band: 

Adjustable from 2 to 20% RH 

Temperature Coefficient 

-0.1 to 0.05% RH/°C at 5°C (41°F) to -0.07 to -0.21% RH/°C at 65°C (149°F) 

Electrical Connections 

3-position screw terminal block 

Ambient Operating 

Conditions 

32 to 122°F (0 to 50°C) 
0 to 100% RH, non-condensing; 85°F (29°C) maximum dew point 

Survival Operating 

Conditions 

-22 to 140

°

F (-30 to 60

°

C) 

0 to 100% RH, non-condensing; 85°F (29°C) maximum dew point 

Ambient Storage 

Conditions 

-40 to 176°F (-40 to 80°C) 
0 to 100% RH, non-condensing; 85°F (29°C) maximum dew point 

Materials 

Wall Mount: 

White plastic enclosure for surface or wallbox mounting, including  

 

hardware 

Duct Probe: 

Light gray plastic cover with dark gray plastic housing and probe 

Dimensions 

Wall Mount (H x W x D): 

3.20 x 3.20 x 1.34 in. (81 x 81 x 34 mm) 

Duct Probe (H x W x D): 

3.25 in. x 3.25 in. x 8.27 in. (83 mm x 83 mm x 210 mm) 

Probe (L x D): 

6.25 in. x 0.98 in. (159 mm x 25 mm) 

Shipping Weight 

0.7 lb (0.3 kg) 

Agency Compliance 

Duct Probe Material: 

94-5 V flammability rated per UL 94 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products. 

Building Efficiency

 

507 E. Michigan Street, Milwaukee, WI  53202 

 

 

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.  

All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.

 

 

Summary of Contents for TRUE RH HC-67x3

Page 1: ...intain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the HC 67x3 Series Humidity Controllers IMPORTANT...

Page 2: ...the base as described in Figure 2 Base Cover 1 Loosen do not remove the cover screw with a 1 16 in 1 5 mm Allen wrench 2 Swing the cover down from the base Figure 2 Removing the Cover from the Base Wa...

Page 3: ...ace where the unit is to be mounted and pull the wiring through the drilled hole 3 Mark the location of the two mounting screws and drill the holes 4 Insert the spring clips on each side of the drille...

Page 4: ...rge side of the fan Recommended location is at least 8 ft 2 4 m downstream from the humidification equipment where duct air and water vapor are sufficiently mixed Avoid areas where the probe may be ex...

Page 5: ...er provided to support the fitting in the housing If the washer is not used the fitting could stress the plastic housing 1 Route the wires from the equipment to the unit through the conduit hole in th...

Page 6: ...setting 2 Select the appropriate control action and output setting using the jumpers Troubleshooting If the humidity controller is not functioning properly 1 Verify the unit is mounted in a location t...

Page 7: ...29 C maximum dew point Ambient Storage Conditions 40 to 176 F 40 to 80 C 0 to 100 RH non condensing 85 F 29 C maximum dew point Materials Wall Mount White plastic enclosure for surface or wallbox moun...

Reviews: