Johnson Controls TRUE RH HC-67x3 Installation Instructions Manual Download Page 6

 

6

    T

RUE

RH Series HC-67x3 Humidity Controllers Installation Instructions 

Jumpers 

To set the jumpers, refer to Figure 11. Turn the circuit 
board over, and position the action and output jumpers 
to suit the application. Reinstall the circuit board. 

Disengage the tabs

to remove the

circuit board.

Reverse
(Factory Set)

Direct

Action

0 to 10 VDC
(Factory Set)

6 to 9 VDC

Output

Circuit Board

Disengage the tabs

to remove the

circuit board.

Reverse
(Factory Set)

Direct

Action

0 to 10 VDC
(Factory Set)

6 to 9 VDC

Output

Circuit Board

 

Figure 11: Jumper Settings 

Proportional Band 

To set the proportional band, see Figure 8. Use a 
1/8 in. (3 mm) flat-blade screwdriver to turn the 
potentiometer to the position desired. 

Duct Probe Humidity Controller 

Setpoint, Proportional Band, and Jumpers 

Refer to Figure 9 to change the setpoint, proportional 
band, or the action and output jumpers for the 
application desired. 

1.  Use a 1/8 in. (3 mm) flat-blade screwdriver to turn 

the setpoint or proportional band potentiometer to 
the desired setting. 

2.  Select the appropriate control action and output 

setting using the jumpers. 

Troubleshooting 

If the humidity controller is not functioning properly: 

1.  Verify the unit is mounted in a location that is 

indicative of space humidity (away from drafts and 
sunlight, for example). 

2.  Check all supply voltage connections, and make 

sure the wiring is correct. (Refer to Figure 8 and 
Figure 9.) 

3.  Check the proportional band and setpoint settings. 

If the humidity control equipment is cycling 
excessively, the proportional band setting may be 
too low. 

4.  Verify the jumper positions. If the unit is not 

delivering an output, make sure the jumpers are 
appropriately selected for the application. 

5.  Replace the unit if the troubleshooting suggestions 

fail to remedy the problem. 

Repairs and Replacement 

The HC-67x3 units are not field repairable. As with any 
electrical device, keep the air vents clean and free 
from dust or obstruction. The HC-67x3 controllers 
have been designed for maintenance-free operation. 
Sturdy packaging, solid-state components, and 
high-quality element construction combine for a 
long-lasting, high performance sensor. To order 
replacement parts, contact the nearest 
Johnson Controls representative. 

Summary of Contents for TRUE RH HC-67x3

Page 1: ...intain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the HC 67x3 Series Humidity Controllers IMPORTANT...

Page 2: ...the base as described in Figure 2 Base Cover 1 Loosen do not remove the cover screw with a 1 16 in 1 5 mm Allen wrench 2 Swing the cover down from the base Figure 2 Removing the Cover from the Base Wa...

Page 3: ...ace where the unit is to be mounted and pull the wiring through the drilled hole 3 Mark the location of the two mounting screws and drill the holes 4 Insert the spring clips on each side of the drille...

Page 4: ...rge side of the fan Recommended location is at least 8 ft 2 4 m downstream from the humidification equipment where duct air and water vapor are sufficiently mixed Avoid areas where the probe may be ex...

Page 5: ...er provided to support the fitting in the housing If the washer is not used the fitting could stress the plastic housing 1 Route the wires from the equipment to the unit through the conduit hole in th...

Page 6: ...setting 2 Select the appropriate control action and output setting using the jumpers Troubleshooting If the humidity controller is not functioning properly 1 Verify the unit is mounted in a location t...

Page 7: ...29 C maximum dew point Ambient Storage Conditions 40 to 176 F 40 to 80 C 0 to 100 RH non condensing 85 F 29 C maximum dew point Materials Wall Mount White plastic enclosure for surface or wallbox moun...

Reviews: