Johnson Controls TRUE RH HC-67x3 Installation Instructions Manual Download Page 2

 

2

    T

RUE

RH Series HC-67x3 Humidity Controllers Installation Instructions 

Accessories 

Table 1: Accessories and Replacement Parts for the Wall Mount Humidity Controller 

Product Code Number 

Description 

ACC-DWCLIP-0 

Drywall Clip Mounting Kit (10/bag) 

ACC-INSL-0* 

Wallbox Mounting Pad (10/bag) 

ACC-INSL-1* 

Surface Mounting Pad (10/bag) 

GRD10A-608 

Plastic Guard with Baseplate and Mounting Ring 

T-4000-119 

Allen-head Adjustment Tool (30/bag) 

TE-67MB-600 

Mounting Base Kit 

TE-67D0-601** 

Door Replacement Kit with Johnson Controls logo 

TE-67D0-602** 

Door Replacement Kit without logo 

*  These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting 
on an uneven surface. 

**  Contains 10 original style and 10 new style doors. 

Mounting 

Location Considerations 

IMPORTANT: 

To avoid damage to the 

circuit board and components, do not mount the 
unit in a location where high concentrations of 
corrosive vapors are present. 

The HC-67x3 controller is shipped with one 
mounting base for both surface and wallbox 
mounting. To mount the HC-67x3, release the cover 
from the base as described in Figure 2. 

Base

Cover

1.  Loosen (do not
     remove) the cover
     screw with a 1/16 in.
     (1.5 mm) Allen
     wrench.

2.  Swing the cover
     down from the
     base.

 

Figure 2: Removing the Cover from the Base 

Wallbox Mounting: Special Tools Needed 

Use a 1/16 in. (1.5 mm) Allen wrench or 
T-4000-119 Allen-head adjustment tool for 
mounting. 

Wallbox Mounting: Location Considerations 

Locate the humidity transmitter on an inside wall, 
free from drafts, and out of direct sunlight. The 
HC-67x3 is shock and vibration resistant; however, 

be careful not to drop or mount the unit where it could be 
exposed to excessive vibration. The following ambient 
operating conditions apply: 

 

Temperature: 32 to 122°F (0 to 50°C) 

 

Humidity: 0 to 100% Relative Humidity (RH), 
non-condensing; 85°F (29°C) maximum dew point 

To mount the HC-67x3 to a wallbox: 

1.  Pull the cable or wiring through the wallbox and 

base. 

2.  Rotate the mounting base, so one of the arrows on 

the base points up. 

3.  Fasten the base to the wallbox with the 

No. 6 screws provided. (See Figure 3.) 

Note:

  These instructions assume a standard 

2 x 4 in. (52 x 104 mm) U.S. wallbox is used. 

No. 6

Screws

Cover

Screw

 

Figure 3: Wallbox Mounting

 

4.  Place the bottom edge of the cover against the 

bottom lip of the base, and rotate it up onto the 
base. (See Figure 4.) 

5.  Tighten the cover screw. 

Summary of Contents for TRUE RH HC-67x3

Page 1: ...intain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the HC 67x3 Series Humidity Controllers IMPORTANT...

Page 2: ...the base as described in Figure 2 Base Cover 1 Loosen do not remove the cover screw with a 1 16 in 1 5 mm Allen wrench 2 Swing the cover down from the base Figure 2 Removing the Cover from the Base Wa...

Page 3: ...ace where the unit is to be mounted and pull the wiring through the drilled hole 3 Mark the location of the two mounting screws and drill the holes 4 Insert the spring clips on each side of the drille...

Page 4: ...rge side of the fan Recommended location is at least 8 ft 2 4 m downstream from the humidification equipment where duct air and water vapor are sufficiently mixed Avoid areas where the probe may be ex...

Page 5: ...er provided to support the fitting in the housing If the washer is not used the fitting could stress the plastic housing 1 Route the wires from the equipment to the unit through the conduit hole in th...

Page 6: ...setting 2 Select the appropriate control action and output setting using the jumpers Troubleshooting If the humidity controller is not functioning properly 1 Verify the unit is mounted in a location t...

Page 7: ...29 C maximum dew point Ambient Storage Conditions 40 to 176 F 40 to 80 C 0 to 100 RH non condensing 85 F 29 C maximum dew point Materials Wall Mount White plastic enclosure for surface or wallbox moun...

Reviews: