1083288-UIM-A-0114
Johnson Controls Unitary Products
33
ADJUSTMENT OF TEMPERATURE RISE
After about 5 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.83 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.
This furnace has a standard ECM motor. The blower motor speed taps
are located on the furnace control board in the blower compartment.
Refer to Figure 39 and the unit wiring label to change the blower speed.
Place all unused motor leads on the PARK terminal. One PARK termi-
nal is provided. To use the same speed tap for heating and cooling, the
terminals must be jumpered together. This control has a continuous fan
speed jumper. On a fan call only (G), the control will energize which
ever blower tap is selected by the jumper. This control will change
blower speeds based on other 24V thermostat inputs (Y1, Y/Y2, W)
respectively.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 39.
The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 6.
The supply air temperature cannot exceed the
ìMaximum Supply
Air Temperatureî
specified in these instructions and on the furnace
rating plate. Under NO circumstances can the furnace be allowed to
operate above the Maximum Supply Air Temperature. Operating the
furnace above the Maximum Supply Air Temperature will cause pre-
mature heat exchanger failure, high levels of Carbon Monoxide, a fire
hazard, personal injury, property damage, and/or death.
DANGER
Do not energize more than one motor speed at a time or damage to
the motor will result.
FIGURE 39:
Furnace Control Board
ELECTRONIC AIR
CLEANER TERMINAL
HUMIDIFIER TERMINAL
DIAGNOSTIC ERROR CODE
RETRIEVAL BUTTON
BLOWER OFF DELAY JUMPER
CONTINUOUS FAN SPEED
JUMPER