TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
27
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object, which sets the
Occupancy Schedule command.
Note:
If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set to Schedule, you
can control the unit with the LOCAL-OCC object externally; however, we do not recommend this method.
See Table 7 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by settings shown in the
Occupancy Determination table. See Table 6.
The occupancy schedule comes from either the weekly scheduler built into the TEC or as an input from the BAS.
The Schedule Source must be selected to tell the controller where to read the occupancy source from. To select
the schedule source:
1.
Press the
Menu
icon.
2.
Press
Schedule
.
3.
Press
Schedule Options
.
4.
Press
Schedule Source
and select
Schedule
(Local) or
External
(BAS).
5.
Press
to save and
to return to the previous screen.
This option is also exposed to the BAS through the point OCC-CONFIG. If BAS is configured as the occupancy
source, map the point NET-OCC in and write to that point to control the schedule remotely. If the supervisor goes
offline (as identified by the network icon going away on the home screen of the TEC), the control logic
automatically falls back to the local schedule as the occupancy source. If that schedule is not set, the default
occupancy is continuously occupied.
Setting the Local Schedule
A weekly occupancy schedule with up to four occupancy events for each day can be set locally on the TEC and
operate independently of a supervisor. To set the schedule:
1.
See
Selecting Schedule Source
to ensure the schedule source is set to Local.
2.
Press the
Menu
icon.
3.
Press
Schedule
.
4.
Press
Set Schedule
.
Table 7: BAS Objects for Scheduling
BAS Objects for Scheduling
OCC-CONFIG
LOCAL-OCC
(Commanded by
Internal Schedule)
NET-OCC
Occupancy Schedule
Command
1
1.
The effective occupancy can be affected by other factors listed in Table 6.
External
Any State
(Internal Schedule in
Control)
Occupied
Occupied
Unoccupied
Unoccupied
Standby
Standby
Not Set
Not Set
Schedule
Occupied
Not Applicable
Occupied
Unoccupied
Unoccupied
Standby
Standby
Not Set
Not Set